All MIBs › CPI-UNITY-MIB
Organization: Chatsworth Products Inc.
Last Updated: 2019-03-01
Description: Chatsworth Products Inc. eConnect Unity MIB consolidating SNMP OIDs for all CPI rack PDU and intelligent cabinet management models
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is CPI-UNITY-MIB?
CPI-UNITY-MIB is Chatsworth Products Inc.'s consolidated "eConnect Unity" MIB, unifying SNMP object definitions across CPI's rack power distribution unit (PDU) and intelligent cabinet management product line. It exposes device identification and configuration data (version, modelCode, hwAddress), network settings (pduIP, autoIP, autoDNS, ipV4Enable, snmpEnable, telnetEnable), and polling/alarm timing parameters (logInterval, alarmInterval, logDifference) for each managed PDU/cabinet unit. This makes it useful for monitoring the configuration and management-interface status of rack PDU hardware - confirming firmware version, network reachability settings, and alarm-reporting cadence - as a foundation for the broader environmental/power data the eConnect line also collects. It is a consolidating module spanning "all CPI models," implying it depends on and unifies several previously separate CPI product-specific MIBs into one OID tree. It is typically deployed in data center racks where CPI eConnect intelligent PDUs are managed and monitored over SNMP alongside power and environmental sensors, and administrators can explore its full object tree using the CPI-UNITY-MIB MIB Browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in CPI-UNITY-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Chatsworth Products (CPI) eConnect rack PDU
- intelligent cabinet/rack management unit
Monitoring Examples
An administrator would poll version and modelCode to inventory which eConnect PDU firmware/model is installed in a rack, and check pduIP, autoIP, and snmpEnable to confirm the unit's management network configuration is correct and reachable. alarmInterval and logInterval reveal how frequently the PDU reports alarms and logs data, so an unexpectedly long interval could delay detection of a power event. Disabling telnetEnable while snmpEnable remains on would indicate the unit has been hardened to use only SNMP for remote access.
What Can Be Monitored
- firmware/model version
- hardware (MAC) address
- PDU IP/network configuration
- SNMP/Telnet management access status
- log and alarm reporting interval
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-CONF
| MODULE-COMPLIANCE | |
| NOTIFICATION-GROUP | |
| OBJECT-GROUP |
From SNMPv2-SMI
| Counter64 | |
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| Unsigned32 | |
| enterprises |
From SNMPv2-TC
| DisplayString | |
| MacAddress | |
| TruthValue |
How to Use in IPNetwork Monitor
Example using energyxy1s OID:
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| cpi | 1.3.6.1.4.1.30932 | |||
| products | 1.3.6.1.4.1.30932.1 | The MIB module is used to register Chatsworth eConnect related SNMP OIDs for all models. Copyright 2014-2019 Chatsworth Products, Inc. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Chatsworth Products, Inc makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification. | ||
| cpiPDU | 1.3.6.1.4.1.30932.1.1 | |||
| STR version | 1.3.6.1.4.1.30932.1.1.1.1 | DisplayString | read-only | Software Version. |
| STR modelCode | 1.3.6.1.4.1.30932.1.1.1.2 | DisplayString | read-only | Model code for the PDU. |
| STR hwAddress | 1.3.6.1.4.1.30932.1.1.1.3 | DisplayString | read-only | PDU hardware MAC address. |
| configuration | 1.3.6.1.4.1.30932.1.1.2 | |||
| I32 logInterval | 1.3.6.1.4.1.30932.1.1.2.1 | Integer32 | read-write | The time interval in seconds for logging metrics (disabled if < 10). |
| I32 alarmInterval | 1.3.6.1.4.1.30932.1.1.2.2 | Integer32 | read-write | The time interval in seconds for alarm cycle (disabled if < 10). |
| I32 logDifference | 1.3.6.1.4.1.30932.1.1.2.3 | Integer32 | read-write | The current difference in 1/100 Amps that triggers logging metrics. |
| IP pduIP | 1.3.6.1.4.1.30932.1.1.2.4 | IpAddress | read-write | PDU IP address. |
| netOptions | 1.3.6.1.4.1.30932.1.1.2.5 | |||
| I32 autoIP | 1.3.6.1.4.1.30932.1.1.2.5.1 | Integer32 | read-write | Select dynamic (Auto) or static IP, 0=static and 1=dynamic. |
| I32 autoDNS | 1.3.6.1.4.1.30932.1.1.2.5.2 | Integer32 | read-write | Select dynamic (Auto) or static DNS, 0=static and 1=dynamic. |
| I32 ipV4Enable | 1.3.6.1.4.1.30932.1.1.2.5.3 | Integer32 | read-write | Enable IPV4 Network, 0=disable and 1=enable. |
| I32 snmpEnable | 1.3.6.1.4.1.30932.1.1.2.5.4 | Integer32 | read-write | Enable SNMP network service, 0=disable and 1=enable. |
| I32 telnetEnable | 1.3.6.1.4.1.30932.1.1.2.5.5 | Integer32 | read-write | Enable Telnet service, 0=disable and 1=enable. |
| I32 sshEnable | 1.3.6.1.4.1.30932.1.1.2.5.6 | Integer32 | read-write | Enable SSH Service, 0=disable and 1=enable. |
| I32 httpEnable | 1.3.6.1.4.1.30932.1.1.2.5.7 | Integer32 | read-write | Enable HTTP Service, 0=disable and 1=enable. |
| I32 httpsEnable | 1.3.6.1.4.1.30932.1.1.2.5.8 | Integer32 | read-write | Enable HTTPS Service, 0=disable and 1=enable. |
| IP subnetMask | 1.3.6.1.4.1.30932.1.1.2.6 | IpAddress | read-write | PDU Subnet Mask. |
| IP gateway | 1.3.6.1.4.1.30932.1.1.2.7 | IpAddress | read-write | PDU Gateway Address. |
| dnsHosts | 1.3.6.1.4.1.30932.1.1.2.8 | |||
| IP dns1 | 1.3.6.1.4.1.30932.1.1.2.8.1 | IpAddress | read-write | PDU DNS 1 IP. |
| IP dns2 | 1.3.6.1.4.1.30932.1.1.2.8.2 | IpAddress | read-write | PDU DNS 2 IP. |
| IP dns3 | 1.3.6.1.4.1.30932.1.1.2.8.3 | IpAddress | read-write | PDU DNS 3 IP. |
| snmpHosts | 1.3.6.1.4.1.30932.1.1.2.9 | |||
| IP snmpHost1 | 1.3.6.1.4.1.30932.1.1.2.9.1 | IpAddress | read-write | SNMP Host 1 IP address. |
| IP snmpHost2 | 1.3.6.1.4.1.30932.1.1.2.9.2 | IpAddress | read-write | SNMP Host 2 IP address. |
| IP snmpHost3 | 1.3.6.1.4.1.30932.1.1.2.9.3 | IpAddress | read-write | SNMP Host 3 IP address. |
| STR pduIPv6 | 1.3.6.1.4.1.30932.1.1.2.10 | DisplayString | read-write | PDU IPV6 address. |
| netOptionsIPv6 | 1.3.6.1.4.1.30932.1.1.2.11 | |||
| I32 autoIPv6 | 1.3.6.1.4.1.30932.1.1.2.11.1 | Integer32 | read-write | Select IPV6 dynamic (Auto) or static IP, 0=static and 1=dynamic. |
| I32 autoDNSIPv6 | 1.3.6.1.4.1.30932.1.1.2.11.2 | Integer32 | read-write | Select IPV6 dynamic (Auto) or static DNS, 0=static and 1=dynamic. |
| I32 ipV6Enable | 1.3.6.1.4.1.30932.1.1.2.11.3 | Integer32 | read-write | Enable IPV6 Network, 0=disable and 1=enable. |
| I32 linkLocalEnable | 1.3.6.1.4.1.30932.1.1.2.11.4 | Integer32 | read-write | Enable IPV6 Link-Local, 0=disable and 1=enable. |
| I32 globalAddrEnable | 1.3.6.1.4.1.30932.1.1.2.11.5 | Integer32 | read-write | Enable IPV6 Global Address, 0=disable and 1=enable. |
| I32 subnetMaskIPv6 | 1.3.6.1.4.1.30932.1.1.2.12 | Integer32 | read-write | PDU IPV6 Subnet Mask. |
| STR gatewayIPv6 | 1.3.6.1.4.1.30932.1.1.2.13 | DisplayString | read-write | PDU IPV6 Gateway Address. |
| dnsHostIPv6 | 1.3.6.1.4.1.30932.1.1.2.14 | |||
| STR dns1IPv6 | 1.3.6.1.4.1.30932.1.1.2.14.1 | DisplayString | read-write | PDU DNS 2 for IPV6. |
| STR dns2IPv6 | 1.3.6.1.4.1.30932.1.1.2.14.2 | DisplayString | read-write | PDU DNS 3 for IPV6. |
| STR dns3IPv6 | 1.3.6.1.4.1.30932.1.1.2.14.3 | DisplayString | read-write | PDU DNS 4 for IPV6. |
| snmpHostsIPv6 | 1.3.6.1.4.1.30932.1.1.2.15 | |||
| STR snmpHost1IPv6 | 1.3.6.1.4.1.30932.1.1.2.15.1 | DisplayString | read-write | SNMP Host 1 IPV6. |
| STR snmpHost2IPv6 | 1.3.6.1.4.1.30932.1.1.2.15.2 | DisplayString | read-write | SNMP Host 2 IPV6. |
| STR snmpHost3IPv6 | 1.3.6.1.4.1.30932.1.1.2.15.3 | DisplayString | read-write | SNMP Host 3 IPV6. |
| receptacleControl | 1.3.6.1.4.1.30932.1.1.2.16 | |||
| I32 outlet1Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.1 | Integer32 | read-write | Outlet1 power state, 0=OFF, 1=ON. |
| I32 outlet2Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.2 | Integer32 | read-write | Outlet2 power state, 0=OFF, 1=ON. |
| I32 outlet3Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.3 | Integer32 | read-write | Outlet3 power state, 0=OFF, 1=ON. |
| I32 outlet4Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.4 | Integer32 | read-write | Outlet4 power state, 0=OFF, 1=ON. |
| I32 outlet5Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.5 | Integer32 | read-write | Outlet5 power state, 0=OFF, 1=ON. |
| I32 outlet6Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.6 | Integer32 | read-write | Outlet6 power state, 0=OFF, 1=ON. |
| I32 outlet7Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.7 | Integer32 | read-write | Outlet7 power state, 0=OFF, 1=ON. |
| I32 outlet8Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.8 | Integer32 | read-write | Outlet8 power state, 0=OFF, 1=ON. |
| I32 outlet9Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.9 | Integer32 | read-write | Outlet9 power state, 0=OFF, 1=ON. |
| I32 outlet10Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.10 | Integer32 | read-write | Outlet10 power state, 0=OFF, 1=ON. |
| I32 outlet11Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.11 | Integer32 | read-write | Outlet11 power state, 0=OFF, 1=ON. |
| I32 outlet12Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.12 | Integer32 | read-write | Outlet12 power state, 0=OFF, 1=ON. |
| I32 outlet13Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.13 | Integer32 | read-write | Outlet13 power state, 0=OFF, 1=ON. |
| I32 outlet14Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.14 | Integer32 | read-write | Outlet14 power state, 0=OFF, 1=ON. |
| I32 outlet15Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.15 | Integer32 | read-write | Outlet15 power state, 0=OFF, 1=ON. |
| I32 outlet16Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.16 | Integer32 | read-write | Outlet16 power state, 0=OFF, 1=ON. |
| I32 outlet17Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.17 | Integer32 | read-write | Outlet17 power state, 0=OFF, 1=ON. |
| I32 outlet18Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.18 | Integer32 | read-write | Outlet18 power state, 0=OFF, 1=ON. |
| I32 outlet19Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.19 | Integer32 | read-write | Outlet19 power state, 0=OFF, 1=ON. |
| I32 outlet20Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.20 | Integer32 | read-write | Outlet20 power state, 0=OFF, 1=ON. |
| I32 outlet21Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.21 | Integer32 | read-write | Outlet21 power state, 0=OFF, 1=ON. |
| I32 outlet22Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.22 | Integer32 | read-write | Outlet22 power state, 0=OFF, 1=ON. |
| I32 outlet23Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.23 | Integer32 | read-write | Outlet23 power state, 0=OFF, 1=ON. |
| I32 outlet24Ctrl | 1.3.6.1.4.1.30932.1.1.2.16.24 | Integer32 | read-write | Outlet24 power state, 0=OFF, 1=ON. |
| receptacleONdelay | 1.3.6.1.4.1.30932.1.1.2.17 | |||
| I32 outlet1ONdly | 1.3.6.1.4.1.30932.1.1.2.17.1 | Integer32 | read-write | Outlet1 power-on delay in seconds. |
| I32 outlet2ONdly | 1.3.6.1.4.1.30932.1.1.2.17.2 | Integer32 | read-write | Outlet2 power-on delay in seconds. |
| I32 outlet3ONdly | 1.3.6.1.4.1.30932.1.1.2.17.3 | Integer32 | read-write | Outlet3 power-on delay in seconds. |
| I32 outlet4ONdly | 1.3.6.1.4.1.30932.1.1.2.17.4 | Integer32 | read-write | Outlet4 power-on delay in seconds. |
| I32 outlet5ONdly | 1.3.6.1.4.1.30932.1.1.2.17.5 | Integer32 | read-write | Outlet5 power-on delay in seconds. |
| I32 outlet6ONdly | 1.3.6.1.4.1.30932.1.1.2.17.6 | Integer32 | read-write | Outlet6 power-on delay in seconds. |
| I32 outlet7ONdly | 1.3.6.1.4.1.30932.1.1.2.17.7 | Integer32 | read-write | Outlet7 power-on delay in seconds. |
| I32 outlet8ONdly | 1.3.6.1.4.1.30932.1.1.2.17.8 | Integer32 | read-write | Outlet8 power-on delay in seconds. |
| I32 outlet9ONdly | 1.3.6.1.4.1.30932.1.1.2.17.9 | Integer32 | read-write | Outlet9 power-on delay in seconds. |
| I32 outlet10ONdly | 1.3.6.1.4.1.30932.1.1.2.17.10 | Integer32 | read-write | Outlet10 power-on delay in seconds. |
| I32 outlet11ONdly | 1.3.6.1.4.1.30932.1.1.2.17.11 | Integer32 | read-write | Outlet11 power-on delay in seconds. |
| I32 outlet12ONdly | 1.3.6.1.4.1.30932.1.1.2.17.12 | Integer32 | read-write | Outlet12 power-on delay in seconds. |
| I32 outlet13ONdly | 1.3.6.1.4.1.30932.1.1.2.17.13 | Integer32 | read-write | Outlet13 power-on delay in seconds. |
| I32 outlet14ONdly | 1.3.6.1.4.1.30932.1.1.2.17.14 | Integer32 | read-write | Outlet14 power-on delay in seconds. |
| I32 outlet15ONdly | 1.3.6.1.4.1.30932.1.1.2.17.15 | Integer32 | read-write | Outlet15 power-on delay in seconds. |
| I32 outlet16ONdly | 1.3.6.1.4.1.30932.1.1.2.17.16 | Integer32 | read-write | Outlet16 power-on delay in seconds. |
| I32 outlet17ONdly | 1.3.6.1.4.1.30932.1.1.2.17.17 | Integer32 | read-write | Outlet17 power-on delay in seconds. |
| I32 outlet18ONdly | 1.3.6.1.4.1.30932.1.1.2.17.18 | Integer32 | read-write | Outlet18 power-on delay in seconds. |
| I32 outlet19ONdly | 1.3.6.1.4.1.30932.1.1.2.17.19 | Integer32 | read-write | Outlet19 power-on delay in seconds. |
| I32 outlet20ONdly | 1.3.6.1.4.1.30932.1.1.2.17.20 | Integer32 | read-write | Outlet20 power-on delay in seconds. |
| I32 outlet21ONdly | 1.3.6.1.4.1.30932.1.1.2.17.21 | Integer32 | read-write | Outlet21 power-on delay in seconds. |
| I32 outlet22ONdly | 1.3.6.1.4.1.30932.1.1.2.17.22 | Integer32 | read-write | Outlet22 power-on delay in seconds. |
| I32 outlet23ONdly | 1.3.6.1.4.1.30932.1.1.2.17.23 | Integer32 | read-write | Outlet23 power-on delay in seconds. |
| I32 outlet24ONdly | 1.3.6.1.4.1.30932.1.1.2.17.24 | Integer32 | read-write | Outlet24 power-on delay in seconds. |
| receptacleResetDelay | 1.3.6.1.4.1.30932.1.1.2.18 | |||
| I32 outlet1RESdly | 1.3.6.1.4.1.30932.1.1.2.18.1 | Integer32 | read-write | Outlet1 reset delay in seconds. |
| I32 outlet2RESdly | 1.3.6.1.4.1.30932.1.1.2.18.2 | Integer32 | read-write | Outlet2 reset delay in seconds. |
| I32 outlet3RESdly | 1.3.6.1.4.1.30932.1.1.2.18.3 | Integer32 | read-write | Outlet3 reset delay in seconds. |
| I32 outlet4RESdly | 1.3.6.1.4.1.30932.1.1.2.18.4 | Integer32 | read-write | Outlet4 reset delay in seconds. |
| I32 outlet5RESdly | 1.3.6.1.4.1.30932.1.1.2.18.5 | Integer32 | read-write | Outlet5 reset delay in seconds. |
| I32 outlet6RESdly | 1.3.6.1.4.1.30932.1.1.2.18.6 | Integer32 | read-write | Outlet6 reset delay in seconds. |
| I32 outlet7RESdly | 1.3.6.1.4.1.30932.1.1.2.18.7 | Integer32 | read-write | Outlet7 reset delay in seconds. |
| I32 outlet8RESdly | 1.3.6.1.4.1.30932.1.1.2.18.8 | Integer32 | read-write | Outlet8 reset delay in seconds. |
| I32 outlet9RESdly | 1.3.6.1.4.1.30932.1.1.2.18.9 | Integer32 | read-write | Outlet9 reset delay in seconds. |
| I32 outlet10RESdly | 1.3.6.1.4.1.30932.1.1.2.18.10 | Integer32 | read-write | Outlet10 reset delay in seconds. |
| I32 outlet11RESdly | 1.3.6.1.4.1.30932.1.1.2.18.11 | Integer32 | read-write | Outlet11 reset delay in seconds. |
| I32 outlet12RESdly | 1.3.6.1.4.1.30932.1.1.2.18.12 | Integer32 | read-write | Outlet12 reset delay in seconds. |
| I32 outlet13RESdly | 1.3.6.1.4.1.30932.1.1.2.18.13 | Integer32 | read-write | Outlet13 reset delay in seconds. |
| I32 outlet14RESdly | 1.3.6.1.4.1.30932.1.1.2.18.14 | Integer32 | read-write | Outlet14 reset delay in seconds. |
| I32 outlet15RESdly | 1.3.6.1.4.1.30932.1.1.2.18.15 | Integer32 | read-write | Outlet15 reset delay in seconds. |
| I32 outlet16RESdly | 1.3.6.1.4.1.30932.1.1.2.18.16 | Integer32 | read-write | Outlet16 reset delay in seconds. |
| I32 outlet17RESdly | 1.3.6.1.4.1.30932.1.1.2.18.17 | Integer32 | read-write | Outlet17 reset delay in seconds. |
| I32 outlet18RESdly | 1.3.6.1.4.1.30932.1.1.2.18.18 | Integer32 | read-write | Outlet18 reset delay in seconds. |
| I32 outlet19RESdly | 1.3.6.1.4.1.30932.1.1.2.18.19 | Integer32 | read-write | Outlet19 reset delay in seconds. |
| I32 outlet20RESdly | 1.3.6.1.4.1.30932.1.1.2.18.20 | Integer32 | read-write | Outlet20 reset delay in seconds. |
| I32 outlet21RESdly | 1.3.6.1.4.1.30932.1.1.2.18.21 | Integer32 | read-write | Outlet21 reset delay in seconds. |
| I32 outlet22RESdly | 1.3.6.1.4.1.30932.1.1.2.18.22 | Integer32 | read-write | Outlet22 reset delay in seconds. |
| I32 outlet23RESdly | 1.3.6.1.4.1.30932.1.1.2.18.23 | Integer32 | read-write | Outlet23 reset delay in seconds. |
| I32 outlet24RESdly | 1.3.6.1.4.1.30932.1.1.2.18.24 | Integer32 | read-write | Outlet24 reset delay in seconds. |
| maxCurrentLimits | 1.3.6.1.4.1.30932.1.1.2.19 | |||
| I32 xy1MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.1 | Integer32 | read-write | Maximum current that XY1 can draw in 1/100 Amps, 0=ignore. |
| I32 yz1MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.2 | Integer32 | read-write | Maximum current that YZ1 can draw in 1/100 Amps, 0=ignore. |
| I32 zx1MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.3 | Integer32 | read-write | Maximum current that ZX1 can draw in 1/100 Amps, 0=ignore. |
| I32 xy2MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.4 | Integer32 | read-write | Maximum current that XY2 can draw in 1/100 Amps, 0=ignore. |
| I32 yz2MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.5 | Integer32 | read-write | Maximum current that YZ2 can draw in 1/100 Amps, 0=ignore. |
| I32 zx2MaxCurr | 1.3.6.1.4.1.30932.1.1.2.19.6 | Integer32 | read-write | Maximum current that ZX2 can draw in 1/100 Amps, 0=ignore. |
| minCurrentLimits | 1.3.6.1.4.1.30932.1.1.2.20 | |||
| I32 xy1MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.1 | Integer32 | read-write | Minimum current that XY1 should draw in 1/100 Amps, 0=ignore. |
| I32 yz1MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.2 | Integer32 | read-write | Minimum current that YZ1 should draw in 1/100 Amps, 0=ignore. |
| I32 zx1MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.3 | Integer32 | read-write | Minimum current that ZX1 should draw in 1/100 Amps, 0=ignore. |
| I32 xy2MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.4 | Integer32 | read-write | Minimum current that XY2 should draw in 1/100 Amps, 0=ignore. |
| I32 yz2MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.5 | Integer32 | read-write | Minimum current that YZ2 should draw in 1/100 Amps, 0=ignore. |
| I32 zx2MinCurr | 1.3.6.1.4.1.30932.1.1.2.20.6 | Integer32 | read-write | Minimum current that ZX2 should draw in 1/100 Amps, 0=ignore. |
| warnHiCurrentLimits | 1.3.6.1.4.1.30932.1.1.2.21 | |||
| I32 xy1WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.1 | Integer32 | read-write | Warning upper current limit that XY1 can draw in 1/100 Amps, 0=ignore. |
| I32 yz1WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.2 | Integer32 | read-write | Warning upper current limit that YZ1 can draw in 1/100 Amps, 0=ignore. |
| I32 zx1WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.3 | Integer32 | read-write | Warning upper current limit that ZX1 can draw in 1/100 Amps, 0=ignore. |
| I32 xy2WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.4 | Integer32 | read-write | Warning upper current limit that XY2 can draw in 1/100 Amps, 0=ignore. |
| I32 yz2WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.5 | Integer32 | read-write | Warning upper current limit that YZ2 can draw in 1/100 Amps, 0=ignore. |
| I32 zx2WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.21.6 | Integer32 | read-write | Warning upper current limit that ZX2 can draw in 1/100 Amps, 0=ignore. |
| warnLoCurrentLimits | 1.3.6.1.4.1.30932.1.1.2.22 | |||
| I32 xy1WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.1 | Integer32 | read-write | Warning lower current limit that XY1 can draw in 1/100 Amps, 0=ignore. |
| I32 yz1WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.2 | Integer32 | read-write | Warning lower current limit that YZ1 can draw in 1/100 Amps, 0=ignore. |
| I32 zx1WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.3 | Integer32 | read-write | Warning lower current limit that ZX1 can draw in 1/100 Amps, 0=ignore. |
| I32 xy2WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.4 | Integer32 | read-write | Warning lower current limit that XY2 can draw in 1/100 Amps, 0=ignore. |
| I32 yz2WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.5 | Integer32 | read-write | Warning lower current limit that YZ2 can draw in 1/100 Amps, 0=ignore. |
| I32 zx2WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.22.6 | Integer32 | read-write | Warning lower current limit that ZX2 can draw in 1/100 Amps, 0=ignore. |
| maxVoltageLimits | 1.3.6.1.4.1.30932.1.1.2.24 | |||
| I32 xy1MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.1 | Integer32 | read-write | Maximum voltage that XY1 can reach up to in volts, 0=ignore. |
| I32 yz1MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.2 | Integer32 | read-write | Maximum voltage that YZ1 can reach up to in volts, 0=ignore. |
| I32 zx1MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.3 | Integer32 | read-write | Maximum voltage that ZX1 can reach up to in volts, 0=ignore. |
| I32 xy2MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.4 | Integer32 | read-write | Maximum voltage that XY2 can reach up to in volts, 0=ignore. |
| I32 yz2MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.5 | Integer32 | read-write | Maximum voltage that YZ2 can reach up to in volts, 0=ignore. |
| I32 zx2MaxVolt | 1.3.6.1.4.1.30932.1.1.2.24.6 | Integer32 | read-write | Maximum voltage that ZX2 can reach up to in volts, 0=ignore. |
| minVoltageLimits | 1.3.6.1.4.1.30932.1.1.2.25 | |||
| I32 xy1MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.1 | Integer32 | read-write | Minimum voltage that XY1 can sag in volts, 0=ignore. |
| I32 yz1MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.2 | Integer32 | read-write | Minimum voltage that YZ1 can sag in volts, 0=ignore. |
| I32 zx1MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.3 | Integer32 | read-write | Minimum voltage that ZX1 can sag in volts, 0=ignore. |
| I32 xy2MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.4 | Integer32 | read-write | Minimum voltage that XY2 can sag in volts, 0=ignore. |
| I32 yz2MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.5 | Integer32 | read-write | Minimum voltage that YZ2 can sag in volts, 0=ignore. |
| I32 zx2MinVolt | 1.3.6.1.4.1.30932.1.1.2.25.6 | Integer32 | read-write | Minimum voltage that ZX2 can sag in volts, 0=ignore. |
| warnHiVoltageLimits | 1.3.6.1.4.1.30932.1.1.2.26 | |||
| I32 xy1WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.1 | Integer32 | read-write | Warning High voltage in volts that XY1 can reach before triggering warning notifications, 0=ignore. |
| I32 yz1WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.2 | Integer32 | read-write | Warning High voltage in volts that YZ1 can reach before triggering warning notifications, 0=ignore. |
| I32 zx1WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.3 | Integer32 | read-write | Warning High voltage in volts that ZX1 can reach before triggering warning notifications, 0=ignore. |
| I32 xy2WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.4 | Integer32 | read-write | Warning High voltage in volts that XY2 can reach before triggering warning notifications, 0=ignore. |
| I32 yz2WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.5 | Integer32 | read-write | Warning High voltage in volts that YZ2 can reach before triggering warning notifications, 0=ignore. |
| I32 zx2WarnHiVolt | 1.3.6.1.4.1.30932.1.1.2.26.6 | Integer32 | read-write | Warning High voltage in volts that ZX2 can reach before triggering warning notifications, 0=ignore. |
| warnLoVoltageLimits | 1.3.6.1.4.1.30932.1.1.2.27 | |||
| I32 xy1WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.1 | Integer32 | read-write | Warning Low voltage in volts that XY1 can sag before triggering notifications, 0=ignore. |
| I32 yz1WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.2 | Integer32 | read-write | Warning Low voltage in volts that YZ1 can sag before triggering notifications, 0=ignore. |
| I32 zx1WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.3 | Integer32 | read-write | Warning Low voltage in volts that ZX1 can sag before triggering notifications, 0=ignore. |
| I32 xy2WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.4 | Integer32 | read-write | Warning Low voltage in volts that XY2 can sag before triggering notifications, 0=ignore. |
| I32 yz2WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.5 | Integer32 | read-write | Warning Low voltage in volts that YZ2 can sag before triggering notifications, 0=ignore. |
| I32 zx2WarnLoVolt | 1.3.6.1.4.1.30932.1.1.2.27.6 | Integer32 | read-write | Warning Low voltage in volts that ZX2 can sag before triggering notifications, 0=ignore. |
| receptacleMaxCurrent | 1.3.6.1.4.1.30932.1.1.2.28 | |||
| I32 outlet1MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.1 | Integer32 | read-write | Outlet1 maximum current in 1/100 Amps. |
| I32 outlet2MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.2 | Integer32 | read-write | Outlet2 maximum current in 1/100 Amps. |
| I32 outlet3MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.3 | Integer32 | read-write | Outlet3 maximum current in 1/100 Amps. |
| I32 outlet4MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.4 | Integer32 | read-write | Outlet4 maximum current in 1/100 Amps. |
| I32 outlet5MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.5 | Integer32 | read-write | Outlet5 maximum current in 1/100 Amps. |
| I32 outlet6MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.6 | Integer32 | read-write | Outlet6 maximum current in 1/100 Amps. |
| I32 outlet7MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.7 | Integer32 | read-write | Outlet7 maximum current in 1/100 Amps. |
| I32 outlet8MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.8 | Integer32 | read-write | Outlet8 maximum current in 1/100 Amps. |
| I32 outlet9MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.9 | Integer32 | read-write | Outlet9 maximum current in 1/100 Amps. |
| I32 outlet10MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.10 | Integer32 | read-write | Outlet10 maximum current in 1/100 Amps. |
| I32 outlet11MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.11 | Integer32 | read-write | Outlet11 maximum current in 1/100 Amps. |
| I32 outlet12MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.12 | Integer32 | read-write | Outlet12 maximum current in 1/100 Amps. |
| I32 outlet13MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.13 | Integer32 | read-write | Outlet13 maximum current in 1/100 Amps. |
| I32 outlet14MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.14 | Integer32 | read-write | Outlet14 maximum current in 1/100 Amps. |
| I32 outlet15MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.15 | Integer32 | read-write | Outlet15 maximum current in 1/100 Amps. |
| I32 outlet16MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.16 | Integer32 | read-write | Outlet16 maximum current in 1/100 Amps. |
| I32 outlet17MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.17 | Integer32 | read-write | Outlet17 maximum current in 1/100 Amps. |
| I32 outlet18MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.18 | Integer32 | read-write | Outlet18 maximum current in 1/100 Amps. |
| I32 outlet19MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.19 | Integer32 | read-write | Outlet19 maximum current in 1/100 Amps. |
| I32 outlet20MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.20 | Integer32 | read-write | Outlet20 maximum current in 1/100 Amps. |
| I32 outlet21MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.21 | Integer32 | read-write | Outlet21 maximum current in 1/100 Amps. |
| I32 outlet22MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.22 | Integer32 | read-write | Outlet22 maximum current in 1/100 Amps. |
| I32 outlet23MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.23 | Integer32 | read-write | Outlet23 maximum current in 1/100 Amps. |
| I32 outlet24MaxCurr | 1.3.6.1.4.1.30932.1.1.2.28.24 | Integer32 | read-write | Outlet24 maximum current in 1/100 Amps. |
| receptacleMinCurrent | 1.3.6.1.4.1.30932.1.1.2.29 | |||
| I32 outlet1MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.1 | Integer32 | read-write | Outlet1 minimum current in 1/100 Amps. |
| I32 outlet2MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.2 | Integer32 | read-write | Outlet2 minimum current in 1/100 Amps. |
| I32 outlet3MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.3 | Integer32 | read-write | Outlet3 minimum current in 1/100 Amps. |
| I32 outlet4MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.4 | Integer32 | read-write | Outlet4 minimum current in 1/100 Amps. |
| I32 outlet5MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.5 | Integer32 | read-write | Outlet5 minimum current in 1/100 Amps. |
| I32 outlet6MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.6 | Integer32 | read-write | Outlet6 minimum current in 1/100 Amps. |
| I32 outlet7MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.7 | Integer32 | read-write | Outlet7 minimum current in 1/100 Amps. |
| I32 outlet8MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.8 | Integer32 | read-write | Outlet8 minimum current in 1/100 Amps. |
| I32 outlet9MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.9 | Integer32 | read-write | Outlet9 minimum current in 1/100 Amps. |
| I32 outlet10MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.10 | Integer32 | read-write | Outlet10 minimum current in 1/100 Amps. |
| I32 outlet11MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.11 | Integer32 | read-write | Outlet11 minimum current in 1/100 Amps. |
| I32 outlet12MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.12 | Integer32 | read-write | Outlet12 minimum current in 1/100 Amps. |
| I32 outlet13MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.13 | Integer32 | read-write | Outlet13 minimum current in 1/100 Amps. |
| I32 outlet14MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.14 | Integer32 | read-write | Outlet14 minimum current in 1/100 Amps. |
| I32 outlet15MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.15 | Integer32 | read-write | Outlet15 minimum current in 1/100 Amps. |
| I32 outlet16MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.16 | Integer32 | read-write | Outlet16 minimum current in 1/100 Amps. |
| I32 outlet17MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.17 | Integer32 | read-write | Outlet17 minimum current in 1/100 Amps. |
| I32 outlet18MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.18 | Integer32 | read-write | Outlet18 minimum current in 1/100 Amps. |
| I32 outlet19MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.19 | Integer32 | read-write | Outlet19 minimum current in 1/100 Amps. |
| I32 outlet20MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.20 | Integer32 | read-write | Outlet20 minimum current in 1/100 Amps. |
| I32 outlet21MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.21 | Integer32 | read-write | Outlet21 minimum current in 1/100 Amps. |
| I32 outlet22MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.22 | Integer32 | read-write | Outlet22 minimum current in 1/100 Amps. |
| I32 outlet23MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.23 | Integer32 | read-write | Outlet23 minimum current in 1/100 Amps. |
| I32 outlet24MinCurr | 1.3.6.1.4.1.30932.1.1.2.29.24 | Integer32 | read-write | Outlet24 minimum current in 1/100 Amps. |
| receptacleWarnHiCurrent | 1.3.6.1.4.1.30932.1.1.2.30 | |||
| I32 outlet1WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.1 | Integer32 | read-write | Outlet1 warning high current in 1/100 Amps. |
| I32 outlet2WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.2 | Integer32 | read-write | Outlet2 warning high current in 1/100 Amps. |
| I32 outlet3WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.3 | Integer32 | read-write | Outlet3 warning high current in 1/100 Amps. |
| I32 outlet4WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.4 | Integer32 | read-write | Outlet4 warning high current in 1/100 Amps. |
| I32 outlet5WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.5 | Integer32 | read-write | Outlet5 warning high current in 1/100 Amps. |
| I32 outlet6WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.6 | Integer32 | read-write | Outlet6 warning high current in 1/100 Amps. |
| I32 outlet7WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.7 | Integer32 | read-write | Outlet7 warning high current in 1/100 Amps. |
| I32 outlet8WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.8 | Integer32 | read-write | Outlet8 warning high current in 1/100 Amps. |
| I32 outlet9WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.9 | Integer32 | read-write | Outlet9 warning high current in 1/100 Amps. |
| I32 outlet10WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.10 | Integer32 | read-write | Outlet10 warning high current in 1/100 Amps. |
| I32 outlet11WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.11 | Integer32 | read-write | Outlet11 warning high current in 1/100 Amps. |
| I32 outlet12WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.12 | Integer32 | read-write | Outlet12 warning high current in 1/100 Amps. |
| I32 outlet13WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.13 | Integer32 | read-write | Outlet13 warning high current in 1/100 Amps. |
| I32 outlet14WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.14 | Integer32 | read-write | Outlet14 warning high current in 1/100 Amps. |
| I32 outlet15WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.15 | Integer32 | read-write | Outlet15 warning high current in 1/100 Amps. |
| I32 outlet16WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.16 | Integer32 | read-write | Outlet16 warning high current in 1/100 Amps. |
| I32 outlet17WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.17 | Integer32 | read-write | Outlet17 warning high current in 1/100 Amps. |
| I32 outlet18WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.18 | Integer32 | read-write | Outlet18 warning high current in 1/100 Amps. |
| I32 outlet19WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.19 | Integer32 | read-write | Outlet19 warning high current in 1/100 Amps. |
| I32 outlet20WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.20 | Integer32 | read-write | Outlet20 warning high current in 1/100 Amps. |
| I32 outlet21WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.21 | Integer32 | read-write | Outlet21 warning high current in 1/100 Amps. |
| I32 outlet22WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.22 | Integer32 | read-write | Outlet22 warning high current in 1/100 Amps. |
| I32 outlet23WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.23 | Integer32 | read-write | Outlet23 warning high current in 1/100 Amps. |
| I32 outlet24WarnHiCurr | 1.3.6.1.4.1.30932.1.1.2.30.24 | Integer32 | read-write | Outlet24 warning high current in 1/100 Amps. |
| receptacleWarnLoCurrent | 1.3.6.1.4.1.30932.1.1.2.31 | |||
| I32 outlet1WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.1 | Integer32 | read-write | Outlet1 warning low current in 1/100 Amps. |
| I32 outlet2WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.2 | Integer32 | read-write | Outlet2 warning low current in 1/100 Amps. |
| I32 outlet3WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.3 | Integer32 | read-write | Outlet3 warning low current in 1/100 Amps. |
| I32 outlet4WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.4 | Integer32 | read-write | Outlet4 warning low current in 1/100 Amps. |
| I32 outlet5WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.5 | Integer32 | read-write | Outlet5 warning low current in 1/100 Amps. |
| I32 outlet6WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.6 | Integer32 | read-write | Outlet6 warning low current in 1/100 Amps. |
| I32 outlet7WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.7 | Integer32 | read-write | Outlet7 warning low current in 1/100 Amps. |
| I32 outlet8WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.8 | Integer32 | read-write | Outlet8 warning low current in 1/100 Amps. |
| I32 outlet9WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.9 | Integer32 | read-write | Outlet9 warning low current in 1/100 Amps. |
| I32 outlet10WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.10 | Integer32 | read-write | Outlet10 warning low current in 1/100 Amps. |
| I32 outlet11WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.11 | Integer32 | read-write | Outlet11 warning low current in 1/100 Amps. |
| I32 outlet12WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.12 | Integer32 | read-write | Outlet12 warning low current in 1/100 Amps. |
| I32 outlet13WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.13 | Integer32 | read-write | Outlet13 warning low current in 1/100 Amps. |
| I32 outlet14WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.14 | Integer32 | read-write | Outlet14 warning low current in 1/100 Amps. |
| I32 outlet15WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.15 | Integer32 | read-write | Outlet15 warning low current in 1/100 Amps. |
| I32 outlet16WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.16 | Integer32 | read-write | Outlet16 warning low current in 1/100 Amps. |
| I32 outlet17WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.17 | Integer32 | read-write | Outlet17 warning low current in 1/100 Amps. |
| I32 outlet18WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.18 | Integer32 | read-write | Outlet18 warning low current in 1/100 Amps. |
| I32 outlet19WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.19 | Integer32 | read-write | Outlet19 warning low current in 1/100 Amps. |
| I32 outlet20WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.20 | Integer32 | read-write | Outlet20 warning low current in 1/100 Amps. |
| I32 outlet21WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.21 | Integer32 | read-write | Outlet21 warning low current in 1/100 Amps. |
| I32 outlet22WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.22 | Integer32 | read-write | Outlet22 warning low current in 1/100 Amps. |
| I32 outlet23WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.23 | Integer32 | read-write | Outlet23 warning low current in 1/100 Amps. |
| I32 outlet24WarnLoCurr | 1.3.6.1.4.1.30932.1.1.2.31.24 | Integer32 | read-write | Outlet24 warning low current in 1/100 Amps. |
| maxTempLimits | 1.3.6.1.4.1.30932.1.1.2.32 | |||
| I32 maxTempProbe1 | 1.3.6.1.4.1.30932.1.1.2.32.1 | Integer32 | read-write | Maximum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore. |
| I32 maxTempProbe2 | 1.3.6.1.4.1.30932.1.1.2.32.2 | Integer32 | read-write | Maximum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore. |
| minTempLimits | 1.3.6.1.4.1.30932.1.1.2.33 | |||
| I32 minTempProbe1 | 1.3.6.1.4.1.30932.1.1.2.33.1 | Integer32 | read-write | Minimum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore. |
| I32 minTempProbe2 | 1.3.6.1.4.1.30932.1.1.2.33.2 | Integer32 | read-write | Minimum temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore. |
| warnHiTempLimits | 1.3.6.1.4.1.30932.1.1.2.34 | |||
| I32 warnHiTempProbe1 | 1.3.6.1.4.1.30932.1.1.2.34.1 | Integer32 | read-write | Warning High temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore. |
| I32 warnHiTempProbe2 | 1.3.6.1.4.1.30932.1.1.2.34.2 | Integer32 | read-write | Warning High temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore. |
| warnLoTempLimits | 1.3.6.1.4.1.30932.1.1.2.35 | |||
| I32 warnLoTempProbe1 | 1.3.6.1.4.1.30932.1.1.2.35.1 | Integer32 | read-write | Warning Low temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore. |
| I32 warnLoTempProbe2 | 1.3.6.1.4.1.30932.1.1.2.35.2 | Integer32 | read-write | Warning Low temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore. |
| maxHumidityLimits | 1.3.6.1.4.1.30932.1.1.2.36 | |||
| I32 maxHumidProbe1 | 1.3.6.1.4.1.30932.1.1.2.36.1 | Integer32 | read-write | Maximum humidity for Probe 1 in 1/100 of %, 0=ignore. |
| I32 maxHumidProbe2 | 1.3.6.1.4.1.30932.1.1.2.36.2 | Integer32 | read-write | Maximum humidity for Probe 2 in 1/100 of %, 0=ignore. |
| minHumidityLimits | 1.3.6.1.4.1.30932.1.1.2.37 | |||
| I32 minHumidProbe1 | 1.3.6.1.4.1.30932.1.1.2.37.1 | Integer32 | read-write | Minimum humidity for Probe 1 in 1/100 of %, 0=ignore. |
| I32 minHumidProbe2 | 1.3.6.1.4.1.30932.1.1.2.37.2 | Integer32 | read-write | Minimum humidity for Probe 2 in 1/100 of %, 0=ignore. |
| warnHiHumidityLimits | 1.3.6.1.4.1.30932.1.1.2.38 | |||
| I32 warnHiHumidProbe1 | 1.3.6.1.4.1.30932.1.1.2.38.1 | Integer32 | read-write | Warning High humidity for Probe 1 in 1/100 of %, 0=ignore. |
| I32 warnHiHumidProbe2 | 1.3.6.1.4.1.30932.1.1.2.38.2 | Integer32 | read-write | Warning High humidity for Probe 2 in 1/100 of %, 0=ignore. |
| warnLoHumidityLimits | 1.3.6.1.4.1.30932.1.1.2.39 | |||
| I32 warnLoHumidProbe1 | 1.3.6.1.4.1.30932.1.1.2.39.1 | Integer32 | read-write | Warning Low humidity for Probe 1 in 1/100 of %, 0=ignore. |
| I32 warnLoHumidProbe2 | 1.3.6.1.4.1.30932.1.1.2.39.2 | Integer32 | read-write | Warning Low humidity for Probe 2 in 1/100 of %, 0=ignore. |
| STR pduName | 1.3.6.1.4.1.30932.1.1.2.40 | DisplayString | read-write | PDU Name. |
| STR pduDescrip | 1.3.6.1.4.1.30932.1.1.2.41 | DisplayString | read-write | PDU Description. |
| receptacleNames | 1.3.6.1.4.1.30932.1.1.2.42 | |||
| STR outlet1Name | 1.3.6.1.4.1.30932.1.1.2.42.1 | DisplayString | read-write | Outlet1 Name. |
| STR outlet2Name | 1.3.6.1.4.1.30932.1.1.2.42.2 | DisplayString | read-write | Outlet2 Name. |
| STR outlet3Name | 1.3.6.1.4.1.30932.1.1.2.42.3 | DisplayString | read-write | Outlet3 Name. |
| STR outlet4Name | 1.3.6.1.4.1.30932.1.1.2.42.4 | DisplayString | read-write | Outlet4 Name. |
| STR outlet5Name | 1.3.6.1.4.1.30932.1.1.2.42.5 | DisplayString | read-write | Outlet5 Name. |
| STR outlet6Name | 1.3.6.1.4.1.30932.1.1.2.42.6 | DisplayString | read-write | Outlet6 Name. |
| STR outlet7Name | 1.3.6.1.4.1.30932.1.1.2.42.7 | DisplayString | read-write | Outlet7 Name. |
| STR outlet8Name | 1.3.6.1.4.1.30932.1.1.2.42.8 | DisplayString | read-write | Outlet8 Name. |
| STR outlet9Name | 1.3.6.1.4.1.30932.1.1.2.42.9 | DisplayString | read-write | Outlet9 Name. |
| STR outlet10Name | 1.3.6.1.4.1.30932.1.1.2.42.10 | DisplayString | read-write | Outlet10 Name. |
| STR outlet11Name | 1.3.6.1.4.1.30932.1.1.2.42.11 | DisplayString | read-write | Outlet11 Name. |
| STR outlet12Name | 1.3.6.1.4.1.30932.1.1.2.42.12 | DisplayString | read-write | Outlet12 Name. |
| STR outlet13Name | 1.3.6.1.4.1.30932.1.1.2.42.13 | DisplayString | read-write | Outlet13 Name. |
| STR outlet14Name | 1.3.6.1.4.1.30932.1.1.2.42.14 | DisplayString | read-write | Outlet14 Name. |
| STR outlet15Name | 1.3.6.1.4.1.30932.1.1.2.42.15 | DisplayString | read-write | Outlet15 Name. |
| STR outlet16Name | 1.3.6.1.4.1.30932.1.1.2.42.16 | DisplayString | read-write | Outlet16 Name. |
| STR outlet17Name | 1.3.6.1.4.1.30932.1.1.2.42.17 | DisplayString | read-write | Outlet17 Name. |
| STR outlet18Name | 1.3.6.1.4.1.30932.1.1.2.42.18 | DisplayString | read-write | Outlet18 Name. |
| STR outlet19Name | 1.3.6.1.4.1.30932.1.1.2.42.19 | DisplayString | read-write | Outlet19 Name. |
| STR outlet20Name | 1.3.6.1.4.1.30932.1.1.2.42.20 | DisplayString | read-write | Outlet20 Name. |
| STR outlet21Name | 1.3.6.1.4.1.30932.1.1.2.42.21 | DisplayString | read-write | Outlet21 Name. |
| STR outlet22Name | 1.3.6.1.4.1.30932.1.1.2.42.22 | DisplayString | read-write | Outlet22 Name. |
| STR outlet23Name | 1.3.6.1.4.1.30932.1.1.2.42.23 | DisplayString | read-write | Outlet23 Name. |
| STR outlet24Name | 1.3.6.1.4.1.30932.1.1.2.42.24 | DisplayString | read-write | Outlet24 Name. |
| receptacleDescrips | 1.3.6.1.4.1.30932.1.1.2.43 | |||
| STR outlet1Descrip | 1.3.6.1.4.1.30932.1.1.2.43.1 | DisplayString | read-write | Outlet1 Description. |
| STR outlet2Descrip | 1.3.6.1.4.1.30932.1.1.2.43.2 | DisplayString | read-write | Outlet2 Description. |
| STR outlet3Descrip | 1.3.6.1.4.1.30932.1.1.2.43.3 | DisplayString | read-write | Outlet3 Description. |
| STR outlet4Descrip | 1.3.6.1.4.1.30932.1.1.2.43.4 | DisplayString | read-write | Outlet4 Description. |
| STR outlet5Descrip | 1.3.6.1.4.1.30932.1.1.2.43.5 | DisplayString | read-write | Outlet5 Description. |
| STR outlet6Descrip | 1.3.6.1.4.1.30932.1.1.2.43.6 | DisplayString | read-write | Outlet6 Description. |
| STR outlet7Descrip | 1.3.6.1.4.1.30932.1.1.2.43.7 | DisplayString | read-write | Outlet7 Description. |
| STR outlet8Descrip | 1.3.6.1.4.1.30932.1.1.2.43.8 | DisplayString | read-write | Outlet8 Description. |
| STR outlet9Descrip | 1.3.6.1.4.1.30932.1.1.2.43.9 | DisplayString | read-write | Outlet9 Description. |
| STR outlet10Descrip | 1.3.6.1.4.1.30932.1.1.2.43.10 | DisplayString | read-write | Outlet10 Description. |
| STR outlet11Descrip | 1.3.6.1.4.1.30932.1.1.2.43.11 | DisplayString | read-write | Outlet11 Description. |
| STR outlet12Descrip | 1.3.6.1.4.1.30932.1.1.2.43.12 | DisplayString | read-write | Outlet12 Description. |
| STR outlet13Descrip | 1.3.6.1.4.1.30932.1.1.2.43.13 | DisplayString | read-write | Outlet13 Description. |
| STR outlet14Descrip | 1.3.6.1.4.1.30932.1.1.2.43.14 | DisplayString | read-write | Outlet14 Description. |
| STR outlet15Descrip | 1.3.6.1.4.1.30932.1.1.2.43.15 | DisplayString | read-write | Outlet15 Description. |
| STR outlet16Descrip | 1.3.6.1.4.1.30932.1.1.2.43.16 | DisplayString | read-write | Outlet16 Description. |
| STR outlet17Descrip | 1.3.6.1.4.1.30932.1.1.2.43.17 | DisplayString | read-write | Outlet17 Description. |
| STR outlet18Descrip | 1.3.6.1.4.1.30932.1.1.2.43.18 | DisplayString | read-write | Outlet18 Description. |
| STR outlet19Descrip | 1.3.6.1.4.1.30932.1.1.2.43.19 | DisplayString | read-write | Outlet19 Description. |
| STR outlet20Descrip | 1.3.6.1.4.1.30932.1.1.2.43.20 | DisplayString | read-write | Outlet20 Description. |
| STR outlet21Descrip | 1.3.6.1.4.1.30932.1.1.2.43.21 | DisplayString | read-write | Outlet21 Description. |
| STR outlet22Descrip | 1.3.6.1.4.1.30932.1.1.2.43.22 | DisplayString | read-write | Outlet22 Description. |
| STR outlet23Descrip | 1.3.6.1.4.1.30932.1.1.2.43.23 | DisplayString | read-write | Outlet23 Description. |
| STR outlet24Descrip | 1.3.6.1.4.1.30932.1.1.2.43.24 | DisplayString | read-write | Outlet24 Description. |
| groupNames | 1.3.6.1.4.1.30932.1.1.2.50 | |||
| STR group1Name | 1.3.6.1.4.1.30932.1.1.2.50.1 | DisplayString | read-write | Name for GROUP 1 of receptacles. |
| STR group2Name | 1.3.6.1.4.1.30932.1.1.2.50.2 | DisplayString | read-write | Name for GROUP 2 of receptacles. |
| STR group3Name | 1.3.6.1.4.1.30932.1.1.2.50.3 | DisplayString | read-write | Name for GROUP 3 of receptacles. |
| STR group4Name | 1.3.6.1.4.1.30932.1.1.2.50.4 | DisplayString | read-write | Name for GROUP 4 of receptacles. |
| STR group5Name | 1.3.6.1.4.1.30932.1.1.2.50.5 | DisplayString | read-write | Name for GROUP 5 of receptacles. |
| STR group6Name | 1.3.6.1.4.1.30932.1.1.2.50.6 | DisplayString | read-write | Name for GROUP 6 of receptacles. |
| STR group7Name | 1.3.6.1.4.1.30932.1.1.2.50.7 | DisplayString | read-write | Name for GROUP 7 of receptacles. |
| STR group8Name | 1.3.6.1.4.1.30932.1.1.2.50.8 | DisplayString | read-write | Name for GROUP 8 of receptacles. |
| STR group9Name | 1.3.6.1.4.1.30932.1.1.2.50.9 | DisplayString | read-write | Name for GROUP 9 of receptacles. |
| STR group10Name | 1.3.6.1.4.1.30932.1.1.2.50.10 | DisplayString | read-write | Name for GROUP 10 of receptacles. |
| STR group11Name | 1.3.6.1.4.1.30932.1.1.2.50.11 | DisplayString | read-write | Name for GROUP 11 of receptacles. |
| STR group12Name | 1.3.6.1.4.1.30932.1.1.2.50.12 | DisplayString | read-write | Name for GROUP 12 of receptacles. |
| STR group13Name | 1.3.6.1.4.1.30932.1.1.2.50.13 | DisplayString | read-write | Name for GROUP 13 of receptacles. |
| STR group14Name | 1.3.6.1.4.1.30932.1.1.2.50.14 | DisplayString | read-write | Name for GROUP 14 of receptacles. |
| STR group15Name | 1.3.6.1.4.1.30932.1.1.2.50.15 | DisplayString | read-write | Name for GROUP 15 of receptacles. |
| STR group16Name | 1.3.6.1.4.1.30932.1.1.2.50.16 | DisplayString | read-write | Name for GROUP 16 of receptacles. |
| groupMaps | 1.3.6.1.4.1.30932.1.1.2.51 | |||
| OCT group1Map | 1.3.6.1.4.1.30932.1.1.2.51.1 | OCTET STRING | read-write | Map for Group 1 of receptacels. |
| OCT group2Map | 1.3.6.1.4.1.30932.1.1.2.51.2 | OCTET STRING | read-write | Map for Group 2 of receptacels. |
| OCT group3Map | 1.3.6.1.4.1.30932.1.1.2.51.3 | OCTET STRING | read-write | Map for Group 3 of receptacels. |
| OCT group4Map | 1.3.6.1.4.1.30932.1.1.2.51.4 | OCTET STRING | read-write | Map for Group 4 of receptacels. |
| OCT group5Map | 1.3.6.1.4.1.30932.1.1.2.51.5 | OCTET STRING | read-write | Map for Group 5 of receptacels. |
| OCT group6Map | 1.3.6.1.4.1.30932.1.1.2.51.6 | OCTET STRING | read-write | Map for Group 6 of receptacels. |
| OCT group7Map | 1.3.6.1.4.1.30932.1.1.2.51.7 | OCTET STRING | read-write | Map for Group 7 of receptacels. |
| OCT group8Map | 1.3.6.1.4.1.30932.1.1.2.51.8 | OCTET STRING | read-write | Map for Group 8 of receptacels. |
| OCT group9Map | 1.3.6.1.4.1.30932.1.1.2.51.9 | OCTET STRING | read-write | Map for Group 9 of receptacels. |
| OCT group10Map | 1.3.6.1.4.1.30932.1.1.2.51.10 | OCTET STRING | read-write | Map for Group 10 of receptacels. |
| OCT group11Map | 1.3.6.1.4.1.30932.1.1.2.51.11 | OCTET STRING | read-write | Map for Group 11 of receptacels. |
| OCT group12Map | 1.3.6.1.4.1.30932.1.1.2.51.12 | OCTET STRING | read-write | Map for Group 12 of receptacels. |
| OCT group13Map | 1.3.6.1.4.1.30932.1.1.2.51.13 | OCTET STRING | read-write | Map for Group 13 of receptacels. |
| OCT group14Map | 1.3.6.1.4.1.30932.1.1.2.51.14 | OCTET STRING | read-write | Map for Group 14 of receptacels. |
| OCT group15Map | 1.3.6.1.4.1.30932.1.1.2.51.15 | OCTET STRING | read-write | Map for Group 15 of receptacels. |
| OCT group16Map | 1.3.6.1.4.1.30932.1.1.2.51.16 | OCTET STRING | read-write | Map for Group 16 of receptacels. |
| I32 dispTimeout | 1.3.6.1.4.1.30932.1.1.2.55 | Integer32 | read-write | Inactivity timeout in minutes to blank the local display (minimum is 1 minute). |
| I32 loginTimeout | 1.3.6.1.4.1.30932.1.1.2.56 | Integer32 | read-write | Inactivity timeout in minutes to terminate a logged in session (minimum is 1 minute). |
| I32 dispBrightness | 1.3.6.1.4.1.30932.1.1.2.57 | Integer32 | read-write | The relative brightness of the local display (0 in min, 9 is max). |
| pduOptions | 1.3.6.1.4.1.30932.1.1.2.58 | |||
| I32 inputTop | 1.3.6.1.4.1.30932.1.1.2.58.1 | Integer32 | read-write | Input cord entry orientation, 1 = top, 0 = bottom. |
| I32 pduRole | 1.3.6.1.4.1.30932.1.1.2.58.2 | Integer32 | read-write | PDU Role, 1 = primary, 0 = secondary. |
| I32 celsiusTemp | 1.3.6.1.4.1.30932.1.1.2.58.3 | Integer32 | read-write | Temperature units, 1=Celsius, 0=Fahrenheit. |
| I32 enableWeb | 1.3.6.1.4.1.30932.1.1.2.58.4 | Integer32 | read-write | Enable Web Access, 1 = enable, 0 = disable. |
| I32 snmpHostOnly | 1.3.6.1.4.1.30932.1.1.2.58.5 | Integer32 | read-write | Restrict access to SNMP via listed Hosts only, 1 = listed SNMP hosts only, 0 = any host. |
| I32 disLocalAuth | 1.3.6.1.4.1.30932.1.1.2.58.6 | Integer32 | read-write | Disable local authentication, 1 = disable, 0 = enable. |
| I32 enaRadiusAuth | 1.3.6.1.4.1.30932.1.1.2.58.7 | Integer32 | read-write | Enable Radius authentication, 1 = disable, 0 = enable. |
| I32 enaADAuth | 1.3.6.1.4.1.30932.1.1.2.58.8 | Integer32 | read-write | Enable Active Directory authentication, 1 = disable, 0 = enable. |
| I32 enaSMTP | 1.3.6.1.4.1.30932.1.1.2.58.9 | Integer32 | read-write | Enable Mail Notification, 1 = disable, 0 = enable. |
| I32 pduAltRole | 1.3.6.1.4.1.30932.1.1.2.58.10 | Integer32 | read-write | PDU Alternate Role, 1 = alternate, 0 = secondary. |
| I32 shareRole | 1.3.6.1.4.1.30932.1.1.2.58.11 | Integer32 | read-write | Allow sharing of PDU Primary and Alternate Roles, 1 = shared, 0 = backup only. |
| I32 outOfService | 1.3.6.1.4.1.30932.1.1.2.58.12 | Integer32 | read-write | Remove a PDU from normal operation, 1 = out of service, 0 = normal operation. |
| I32 missingPDUNotify | 1.3.6.1.4.1.30932.1.1.2.58.13 | Integer32 | read-write | Notify when a PDU is missing from the link, 1 = enable, 0 = disable. |
| I32 roleChangeNotify | 1.3.6.1.4.1.30932.1.1.2.58.14 | Integer32 | read-write | Notify when a PDU changes role in the link, 1 = enable, 0 = disable. |
| I32 sumAmp | 1.3.6.1.4.1.30932.1.1.2.58.15 | Integer32 | read-write | Display the sum of the current across branches, 1 = enable, 0 = disable. |
| httpPorts | 1.3.6.1.4.1.30932.1.1.2.59 | |||
| I32 httpPort | 1.3.6.1.4.1.30932.1.1.2.59.1 | Integer32 | read-write | Port for unsecure HTTP access. |
| I32 httpsPort | 1.3.6.1.4.1.30932.1.1.2.59.2 | Integer32 | read-write | Port for secure HTTPS access. |
| sshPorts | 1.3.6.1.4.1.30932.1.1.2.60 | |||
| I32 sshPort | 1.3.6.1.4.1.30932.1.1.2.60.1 | Integer32 | read-write | Port for secure SSH access. |
| I32 telnetPort | 1.3.6.1.4.1.30932.1.1.2.60.2 | Integer32 | read-write | Port for non secure Telnet access. |
| snmpPorts | 1.3.6.1.4.1.30932.1.1.2.61 | |||
| I32 snmpQueryPort | 1.3.6.1.4.1.30932.1.1.2.61.1 | Integer32 | read-write | Port for SNMP query access. |
| I32 snmpTrapPort | 1.3.6.1.4.1.30932.1.1.2.61.2 | Integer32 | read-write | Port for SNMP trap. |
| smtpPorts | 1.3.6.1.4.1.30932.1.1.2.62 | |||
| I32 smtpSendPort | 1.3.6.1.4.1.30932.1.1.2.62.1 | Integer32 | read-write | Port for SMTP send. |
| I32 smtpReceivePort | 1.3.6.1.4.1.30932.1.1.2.62.2 | Integer32 | read-write | Port for SMTP Receive. |
| STR rfcTimeServer | 1.3.6.1.4.1.30932.1.1.2.63 | DisplayString | read-write | RFC Time Server Address. |
| STR ntpTimeServer | 1.3.6.1.4.1.30932.1.1.2.64 | DisplayString | read-write | NTP Time Server Address. |
| STR smtpServer | 1.3.6.1.4.1.30932.1.1.2.65 | DisplayString | read-write | Email Server Address. |
| STR snmpReadComm | 1.3.6.1.4.1.30932.1.1.2.66 | DisplayString | read-write | SNMP Read Community. |
| STR snmpWriteComm | 1.3.6.1.4.1.30932.1.1.2.67 | DisplayString | read-write | SNMP Write Community. |
| STR snmpUSMuserName | 1.3.6.1.4.1.30932.1.1.2.68 | DisplayString | read-write | SNMP USM User Name. |
| snmpSecurityLevelAlgorithm | 1.3.6.1.4.1.30932.1.1.2.69 | |||
| I32 snmpSecurityLevel | 1.3.6.1.4.1.30932.1.1.2.69.1 | Integer32 | read-write | Security Level for SNMP: 0 = v1, 1 = v2c, 2 = v3 no authentication, 3 = v3 with authentication only, 4 = v3 with authentication and privacy |
| I32 snmpAuthAlgo | 1.3.6.1.4.1.30932.1.1.2.69.2 | Integer32 | read-write | Authentication Algorithm for SNMP: 0 = SHA, 1 = MD5. |
| I32 snmpPrivAlgo | 1.3.6.1.4.1.30932.1.1.2.69.3 | Integer32 | read-write | Privacy Algorithm for SNMP: 0 = DES, 1 = AES. |
| STR snmpAuthPasswd | 1.3.6.1.4.1.30932.1.1.2.70 | DisplayString | read-write | SNMP Authentication Password. |
| STR snmpPrivPasswd | 1.3.6.1.4.1.30932.1.1.2.71 | DisplayString | read-write | SNMP Privacy Password. |
| STR snmpContextName | 1.3.6.1.4.1.30932.1.1.2.72 | DisplayString | read-write | SNMP Context Name. |
| STR snmpEngineID | 1.3.6.1.4.1.30932.1.1.2.73 | DisplayString | read-write | SNMP Engine ID. |
| STR snmpLocAuthKey | 1.3.6.1.4.1.30932.1.1.2.74 | DisplayString | read-write | SNMP Local Authentication Key. |
| STR snmpLocPrivKey | 1.3.6.1.4.1.30932.1.1.2.75 | DisplayString | read-write | SNMP Local Privacy Key. |
| STR smtpUserName | 1.3.6.1.4.1.30932.1.1.2.76 | DisplayString | read-write | PDU Email User Login Name. |
| STR smtpUserPasswd | 1.3.6.1.4.1.30932.1.1.2.77 | DisplayString | read-write | PDU Email User Login Password. |
| STR smtpEmailAddr | 1.3.6.1.4.1.30932.1.1.2.78 | DisplayString | read-write | PDU Email address. |
| smtpEmailDestinations | 1.3.6.1.4.1.30932.1.1.2.79 | |||
| STR smtpEmailDestination1 | 1.3.6.1.4.1.30932.1.1.2.79.1 | DisplayString | read-write | Email destination for recipient 0. |
| STR smtpEmailDestination2 | 1.3.6.1.4.1.30932.1.1.2.79.2 | DisplayString | read-write | Email destination for recipient 1. |
| STR smtpEmailDestination3 | 1.3.6.1.4.1.30932.1.1.2.79.3 | DisplayString | read-write | Email destination for recipient 2. |
| I32 smtpServOptions | 1.3.6.1.4.1.30932.1.1.2.80 | Integer32 | read-write | SMTP Server Options. |
| STR radiusServer | 1.3.6.1.4.1.30932.1.1.2.81 | DisplayString | read-write | Radius Authentication Server. |
| STR radiusSHSecret | 1.3.6.1.4.1.30932.1.1.2.82 | DisplayString | read-write | Radius Shared Secret. |
| STR radiusNASServer | 1.3.6.1.4.1.30932.1.1.2.83 | DisplayString | read-write | Radius Network Access Service. |
| radiusNASPorts | 1.3.6.1.4.1.30932.1.1.2.84 | |||
| I32 radiusPort | 1.3.6.1.4.1.30932.1.1.2.84.1 | Integer32 | read-write | Port for radius authentication. |
| I32 nasPort | 1.3.6.1.4.1.30932.1.1.2.84.2 | Integer32 | read-write | Port for Radius Network Access Service. |
| STR adServer | 1.3.6.1.4.1.30932.1.1.2.85 | DisplayString | read-write | Active Directory Server. |
| STR adDomain | 1.3.6.1.4.1.30932.1.1.2.86 | DisplayString | read-write | Active Directory Domain. |
| adAllPorts | 1.3.6.1.4.1.30932.1.1.2.87 | |||
| I32 adPort | 1.3.6.1.4.1.30932.1.1.2.87.1 | Integer32 | read-write | Port for Active Directory authentication. |
| I32 adResvPort | 1.3.6.1.4.1.30932.1.1.2.87.2 | Integer32 | read-write | Alternate or reserved port for Active Directory Authentication. |
| envProbeNames | 1.3.6.1.4.1.30932.1.1.2.88 | |||
| STR probe1Name | 1.3.6.1.4.1.30932.1.1.2.88.1 | DisplayString | read-write | Name for Environmental Probe 1. |
| STR probe2Name | 1.3.6.1.4.1.30932.1.1.2.88.2 | DisplayString | read-write | Name for Environmental Probe 2. |
| dLogOptions | 1.3.6.1.4.1.30932.1.1.2.89 | |||
| I32 dLogEnable | 1.3.6.1.4.1.30932.1.1.2.89.1 | Integer32 | read-write | Enable data logging feature, 0=disable and 1=enable. |
| I32 stdmeterdLog | 1.3.6.1.4.1.30932.1.1.2.89.2 | Integer32 | read-write | Enable logging of branch, receptacle and environmental metrics, 0=disable and 1=enable. |
| I32 groupmeterdLog | 1.3.6.1.4.1.30932.1.1.2.89.3 | Integer32 | read-write | Enable logging of grouped receptacle metrics, 0=disable and 1=enable. |
| I32 alarmdLog | 1.3.6.1.4.1.30932.1.1.2.89.4 | Integer32 | read-write | Enable logging of alarm events, 0=disable and 1=enable. |
| I32 userlogindLog | 1.3.6.1.4.1.30932.1.1.2.89.5 | Integer32 | read-write | Enable logging of user login events, 0=disable and 1=enable. |
| I32 usersetupdLog | 1.3.6.1.4.1.30932.1.1.2.89.6 | Integer32 | read-write | Enable logging of user setup change events, 0=disable and 1=enable. |
| I32 fwupdatedLog | 1.3.6.1.4.1.30932.1.1.2.89.7 | Integer32 | read-write | Enable data logging feature, 0=disable and 1=enable. |
| I32 setupchangedLog | 1.3.6.1.4.1.30932.1.1.2.89.8 | Integer32 | read-write | Enable logging of setup change events, 0=disable and 1=enable. |
| I32 recepchangedLog | 1.3.6.1.4.1.30932.1.1.2.89.9 | Integer32 | read-write | Enable logging of receptacle state changes, 0=disable and 1=enable. |
| I32 pduopchangedLog | 1.3.6.1.4.1.30932.1.1.2.89.10 | Integer32 | read-write | Enable logging of PDU operation and state changes, 0=disable and 1=enable. |
| I32 netservdLog | 1.3.6.1.4.1.30932.1.1.2.89.11 | Integer32 | read-write | Enable data logging to log server over network, 0=disable and 1=enable. |
| I32 autonetLog | 1.3.6.1.4.1.30932.1.1.2.89.12 | Integer32 | read-write | Enable automatic transfer to log server every 6 hours, 0=disable and 1=enable. |
| I32 dLogCycle | 1.3.6.1.4.1.30932.1.1.2.90 | Integer32 | read-write | The time interval in minutes for internal data logging to occur. |
| I32 dLogFullWarnLevel | 1.3.6.1.4.1.30932.1.1.2.91 | Integer32 | read-write | The warning threshold for percentage of storage full (min=50, max=100). |
| STR netdLogServer | 1.3.6.1.4.1.30932.1.1.2.92 | DisplayString | read-write | The network address for the data log server. |
| I32 netdLogPort | 1.3.6.1.4.1.30932.1.1.2.93 | Integer32 | read-write | The port used by the data log server. |
| STR netdLogUser | 1.3.6.1.4.1.30932.1.1.2.94 | DisplayString | read-write | The user name to access the data log server. |
| STR netdLogPasswd | 1.3.6.1.4.1.30932.1.1.2.95 | DisplayString | read-write | The user password to access the data log server. |
| STR netdLogDestdir | 1.3.6.1.4.1.30932.1.1.2.96 | DisplayString | read-write | The destination directory in the data log server. |
| STR netdLogOptions | 1.3.6.1.4.1.30932.1.1.2.97 | DisplayString | read-write | The options string when accessing the data log server. |
| snmpTrapHosts | 1.3.6.1.4.1.30932.1.1.2.98 | |||
| IP snmpTrapHost1 | 1.3.6.1.4.1.30932.1.1.2.98.1 | IpAddress | read-write | SNMP Trap Host 1 IP address. |
| IP snmpTrapHost2 | 1.3.6.1.4.1.30932.1.1.2.98.2 | IpAddress | read-write | SNMP Trap Host 2 IP address. |
| IP snmpTrapHost3 | 1.3.6.1.4.1.30932.1.1.2.98.3 | IpAddress | read-write | SNMP Trap Host 3 IP address. |
| snmpTrapHostsIPv6 | 1.3.6.1.4.1.30932.1.1.2.99 | |||
| STR snmpTrapHost1IPv6 | 1.3.6.1.4.1.30932.1.1.2.99.1 | DisplayString | read-write | SNMP Trap Host 1 IPV6. |
| STR snmpTrapHost2IPv6 | 1.3.6.1.4.1.30932.1.1.2.99.2 | DisplayString | read-write | SNMP Trap Host 2 IPV6. |
| STR snmpTrapHost3IPv6 | 1.3.6.1.4.1.30932.1.1.2.99.3 | DisplayString | read-write | SNMP Trap Host 3 IPV6. |
| I32 lnkAttachCount | 1.3.6.1.4.1.30932.1.1.2.100 | Integer32 | read-write | Count of secondary PDUs that are attached to the link. |
| metrics | 1.3.6.1.4.1.30932.1.1.3 | |||
| mcurrent | 1.3.6.1.4.1.30932.1.1.3.1 | |||
| I32 currentxy1 | 1.3.6.1.4.1.30932.1.1.3.1.1 | Integer32 | read-only | XY1 current draw in 1/100 Amps. |
| I32 currentyz1 | 1.3.6.1.4.1.30932.1.1.3.1.2 | Integer32 | read-only | YZ1 current draw in 1/100 Amps. |
| I32 currentzx1 | 1.3.6.1.4.1.30932.1.1.3.1.3 | Integer32 | read-only | ZX1 current draw in 1/100 Amps. |
| I32 currentxy2 | 1.3.6.1.4.1.30932.1.1.3.1.4 | Integer32 | read-only | XY2 current draw in 1/100 Amps. |
| I32 currentyz2 | 1.3.6.1.4.1.30932.1.1.3.1.5 | Integer32 | read-only | YZ2 current draw in 1/100 Amps. |
| I32 currentzx2 | 1.3.6.1.4.1.30932.1.1.3.1.6 | Integer32 | read-only | ZX2 current draw in 1/100 Amps. |
| mvoltage | 1.3.6.1.4.1.30932.1.1.3.2 | |||
| I32 voltagexy1 | 1.3.6.1.4.1.30932.1.1.3.2.1 | Integer32 | read-only | XY1 voltage in 1/10 volts. |
| I32 voltageyz1 | 1.3.6.1.4.1.30932.1.1.3.2.2 | Integer32 | read-only | YZ1 voltage in 1/10 volts. |
| I32 voltagezx1 | 1.3.6.1.4.1.30932.1.1.3.2.3 | Integer32 | read-only | ZX1 voltage in 1/10 volts. |
| I32 voltagexy2 | 1.3.6.1.4.1.30932.1.1.3.2.4 | Integer32 | read-only | XY2 voltage in 1/10 volts. |
| I32 voltageyz2 | 1.3.6.1.4.1.30932.1.1.3.2.5 | Integer32 | read-only | YZ2 voltage in 1/10 volts. |
| I32 voltagezx2 | 1.3.6.1.4.1.30932.1.1.3.2.6 | Integer32 | read-only | ZX2 voltage in 1/10 volts. |
| mpower | 1.3.6.1.4.1.30932.1.1.3.3 | |||
| I32 powerxy1 | 1.3.6.1.4.1.30932.1.1.3.3.1 | Integer32 | read-only | XY1 power consumption in Watts. |
| I32 poweryz1 | 1.3.6.1.4.1.30932.1.1.3.3.2 | Integer32 | read-only | YZ1 power consumption in Watts. |
| I32 powerzx1 | 1.3.6.1.4.1.30932.1.1.3.3.3 | Integer32 | read-only | ZX1 power consumption in Watts. |
| I32 powerxy2 | 1.3.6.1.4.1.30932.1.1.3.3.4 | Integer32 | read-only | XY2 power consumption in Watts. |
| I32 poweryz2 | 1.3.6.1.4.1.30932.1.1.3.3.5 | Integer32 | read-only | YZ2 power consumption in Watts. |
| I32 powerzx2 | 1.3.6.1.4.1.30932.1.1.3.3.6 | Integer32 | read-only | ZX2 power consumption in Watts. |
| mpowerFactor | 1.3.6.1.4.1.30932.1.1.3.4 | |||
| I32 powerFactxy1 | 1.3.6.1.4.1.30932.1.1.3.4.1 | Integer32 | read-only | XY1 power factor x 100. |
| I32 powerFactyz1 | 1.3.6.1.4.1.30932.1.1.3.4.2 | Integer32 | read-only | YZ1 power factor x 100. |
| I32 powerFactzx1 | 1.3.6.1.4.1.30932.1.1.3.4.3 | Integer32 | read-only | ZX1 power factor x 100. |
| I32 powerFactxy2 | 1.3.6.1.4.1.30932.1.1.3.4.4 | Integer32 | read-only | XY2 power factor x 100. |
| I32 powerFactyz2 | 1.3.6.1.4.1.30932.1.1.3.4.5 | Integer32 | read-only | YZ2 power factor x 100. |
| I32 powerFactzx2 | 1.3.6.1.4.1.30932.1.1.3.4.6 | Integer32 | read-only | ZX2 power factor x 100. |
| receptacleCurrent | 1.3.6.1.4.1.30932.1.1.3.5 | |||
| I32 outlet1Current | 1.3.6.1.4.1.30932.1.1.3.5.1 | Integer32 | read-only | Outlet1 current draw in 1/100 Amps. |
| I32 outlet2Current | 1.3.6.1.4.1.30932.1.1.3.5.2 | Integer32 | read-only | Outlet2 current draw in 1/100 Amps. |
| I32 outlet3Current | 1.3.6.1.4.1.30932.1.1.3.5.3 | Integer32 | read-only | Outlet3 current draw in 1/100 Amps. |
| I32 outlet4Current | 1.3.6.1.4.1.30932.1.1.3.5.4 | Integer32 | read-only | Outlet4 current draw in 1/100 Amps. |
| I32 outlet5Current | 1.3.6.1.4.1.30932.1.1.3.5.5 | Integer32 | read-only | Outlet5 current draw in 1/100 Amps. |
| I32 outlet6Current | 1.3.6.1.4.1.30932.1.1.3.5.6 | Integer32 | read-only | Outlet6 current draw in 1/100 Amps. |
| I32 outlet7Current | 1.3.6.1.4.1.30932.1.1.3.5.7 | Integer32 | read-only | Outlet7 current draw in 1/100 Amps. |
| I32 outlet8Current | 1.3.6.1.4.1.30932.1.1.3.5.8 | Integer32 | read-only | Outlet8 current draw in 1/100 Amps. |
| I32 outlet9Current | 1.3.6.1.4.1.30932.1.1.3.5.9 | Integer32 | read-only | Outlet9 current draw in 1/100 Amps. |
| I32 outlet10Current | 1.3.6.1.4.1.30932.1.1.3.5.10 | Integer32 | read-only | Outlet10 current draw in 1/100 Amps. |
| I32 outlet11Current | 1.3.6.1.4.1.30932.1.1.3.5.11 | Integer32 | read-only | Outlet11 current draw in 1/100 Amps. |
| I32 outlet12Current | 1.3.6.1.4.1.30932.1.1.3.5.12 | Integer32 | read-only | Outlet12 current draw in 1/100 Amps. |
| I32 outlet13Current | 1.3.6.1.4.1.30932.1.1.3.5.13 | Integer32 | read-only | Outlet13 current draw in 1/100 Amps. |
| I32 outlet14Current | 1.3.6.1.4.1.30932.1.1.3.5.14 | Integer32 | read-only | Outlet14 current draw in 1/100 Amps. |
| I32 outlet15Current | 1.3.6.1.4.1.30932.1.1.3.5.15 | Integer32 | read-only | Outlet15 current draw in 1/100 Amps. |
| I32 outlet16Current | 1.3.6.1.4.1.30932.1.1.3.5.16 | Integer32 | read-only | Outlet16 current draw in 1/100 Amps. |
| I32 outlet17Current | 1.3.6.1.4.1.30932.1.1.3.5.17 | Integer32 | read-only | Outlet17 current draw in 1/100 Amps. |
| I32 outlet18Current | 1.3.6.1.4.1.30932.1.1.3.5.18 | Integer32 | read-only | Outlet18 current draw in 1/100 Amps. |
| I32 outlet19Current | 1.3.6.1.4.1.30932.1.1.3.5.19 | Integer32 | read-only | Outlet19 current draw in 1/100 Amps. |
| I32 outlet20Current | 1.3.6.1.4.1.30932.1.1.3.5.20 | Integer32 | read-only | Outlet20 current draw in 1/100 Amps. |
| I32 outlet21Current | 1.3.6.1.4.1.30932.1.1.3.5.21 | Integer32 | read-only | Outlet21 current draw in 1/100 Amps. |
| I32 outlet22Current | 1.3.6.1.4.1.30932.1.1.3.5.22 | Integer32 | read-only | Outlet22 current draw in 1/100 Amps. |
| I32 outlet23Current | 1.3.6.1.4.1.30932.1.1.3.5.23 | Integer32 | read-only | Outlet23 current draw in 1/100 Amps. |
| I32 outlet24Current | 1.3.6.1.4.1.30932.1.1.3.5.24 | Integer32 | read-only | Outlet24 current draw in 1/100 Amps. |
| STR receptacleCurrentMap | 1.3.6.1.4.1.30932.1.1.3.6 | DisplayString | read-only | Map of receptacle currents in ascending order and delimited by space. |
| receptacleStatus | 1.3.6.1.4.1.30932.1.1.3.7 | |||
| I32 outlet1State | 1.3.6.1.4.1.30932.1.1.3.7.1 | Integer32 | read-only | Outlet1 power state, 0=OFF, 1=ON. |
| I32 outlet2State | 1.3.6.1.4.1.30932.1.1.3.7.2 | Integer32 | read-only | Outlet2 power state, 0=OFF, 1=ON. |
| I32 outlet3State | 1.3.6.1.4.1.30932.1.1.3.7.3 | Integer32 | read-only | Outlet3 power state, 0=OFF, 1=ON. |
| I32 outlet4State | 1.3.6.1.4.1.30932.1.1.3.7.4 | Integer32 | read-only | Outlet4 power state, 0=OFF, 1=ON. |
| I32 outlet5State | 1.3.6.1.4.1.30932.1.1.3.7.5 | Integer32 | read-only | Outlet5 power state, 0=OFF, 1=ON. |
| I32 outlet6State | 1.3.6.1.4.1.30932.1.1.3.7.6 | Integer32 | read-only | Outlet6 power state, 0=OFF, 1=ON. |
| I32 outlet7State | 1.3.6.1.4.1.30932.1.1.3.7.7 | Integer32 | read-only | Outlet7 power state, 0=OFF, 1=ON. |
| I32 outlet8State | 1.3.6.1.4.1.30932.1.1.3.7.8 | Integer32 | read-only | Outlet8 power state, 0=OFF, 1=ON. |
| I32 outlet9State | 1.3.6.1.4.1.30932.1.1.3.7.9 | Integer32 | read-only | Outlet9 power state, 0=OFF, 1=ON. |
| I32 outlet10State | 1.3.6.1.4.1.30932.1.1.3.7.10 | Integer32 | read-only | Outlet10 power state, 0=OFF, 1=ON. |
| I32 outlet11State | 1.3.6.1.4.1.30932.1.1.3.7.11 | Integer32 | read-only | Outlet11 power state, 0=OFF, 1=ON. |
| I32 outlet12State | 1.3.6.1.4.1.30932.1.1.3.7.12 | Integer32 | read-only | Outlet12 power state, 0=OFF, 1=ON. |
| I32 outlet13State | 1.3.6.1.4.1.30932.1.1.3.7.13 | Integer32 | read-only | Outlet13 power state, 0=OFF, 1=ON. |
| I32 outlet14State | 1.3.6.1.4.1.30932.1.1.3.7.14 | Integer32 | read-only | Outlet14 power state, 0=OFF, 1=ON. |
| I32 outlet15State | 1.3.6.1.4.1.30932.1.1.3.7.15 | Integer32 | read-only | Outlet15 power state, 0=OFF, 1=ON. |
| I32 outlet16State | 1.3.6.1.4.1.30932.1.1.3.7.16 | Integer32 | read-only | Outlet16 power state, 0=OFF, 1=ON. |
| I32 outlet17State | 1.3.6.1.4.1.30932.1.1.3.7.17 | Integer32 | read-only | Outlet17 power state, 0=OFF, 1=ON. |
| I32 outlet18State | 1.3.6.1.4.1.30932.1.1.3.7.18 | Integer32 | read-only | Outlet18 power state, 0=OFF, 1=ON. |
| I32 outlet19State | 1.3.6.1.4.1.30932.1.1.3.7.19 | Integer32 | read-only | Outlet19 power state, 0=OFF, 1=ON. |
| I32 outlet20State | 1.3.6.1.4.1.30932.1.1.3.7.20 | Integer32 | read-only | Outlet20 power state, 0=OFF, 1=ON. |
| I32 outlet21State | 1.3.6.1.4.1.30932.1.1.3.7.21 | Integer32 | read-only | Outlet21 power state, 0=OFF, 1=ON. |
| I32 outlet22State | 1.3.6.1.4.1.30932.1.1.3.7.22 | Integer32 | read-only | Outlet22 power state, 0=OFF, 1=ON. |
| I32 outlet23State | 1.3.6.1.4.1.30932.1.1.3.7.23 | Integer32 | read-only | Outlet23 power state, 0=OFF, 1=ON. |
| I32 outlet24State | 1.3.6.1.4.1.30932.1.1.3.7.24 | Integer32 | read-only | Outlet24 power state, 0=OFF, 1=ON. |
| temperature | 1.3.6.1.4.1.30932.1.1.3.8 | |||
| I32 temperatureProbe1 | 1.3.6.1.4.1.30932.1.1.3.8.1 | Integer32 | read-only | Probe 1 temperature in 1/100 degree Fahrenheit. |
| I32 temperatureProbe2 | 1.3.6.1.4.1.30932.1.1.3.8.2 | Integer32 | read-only | Probe 2 temperature in 1/100 degree Fahrenheit. |
| humidity | 1.3.6.1.4.1.30932.1.1.3.9 | |||
| I32 humidityProbe1 | 1.3.6.1.4.1.30932.1.1.3.9.1 | Integer32 | read-only | Probe 1 humidity in 1/100 %. |
| I32 humidityProbe2 | 1.3.6.1.4.1.30932.1.1.3.9.2 | Integer32 | read-only | Probe 2 humidity in 1/100 %. |
| alarms | 1.3.6.1.4.1.30932.1.1.3.10 | |||
| I32 alarmsMaxMap | 1.3.6.1.4.1.30932.1.1.3.10.1 | Integer32 | read-only | Max threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ... bit6=voltA, bit7=voltB, bit8=voltC ... bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2 |
| I32 alarmsMinMap | 1.3.6.1.4.1.30932.1.1.3.10.2 | Integer32 | read-only | Min threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ... bit6=voltA, bit7=voltB, bit8=voltC ... bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2 |
| I32 alarmsWarnHiMap | 1.3.6.1.4.1.30932.1.1.3.10.3 | Integer32 | read-only | High threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ... bit6=voltA, bit7=voltB, bit8=voltC ... bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2 |
| I32 alarmsWarnLoMap | 1.3.6.1.4.1.30932.1.1.3.10.4 | Integer32 | read-only | Low threshold warning state bitmap: bit0=currA, bit1=currB, bit2=currC ... bit6=voltA, bit7=voltB, bit8=voltC ... bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2 |
| I32 recep1To32AlarmsMaxMap | 1.3.6.1.4.1.30932.1.1.3.10.5 | Integer32 | read-only | Max threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32 |
| I32 recep1To32AlarmsMinMap | 1.3.6.1.4.1.30932.1.1.3.10.7 | Integer32 | read-only | Min threshold alarmed receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32 |
| I32 recep1To32WarnHiMap | 1.3.6.1.4.1.30932.1.1.3.10.9 | Integer32 | read-only | High threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32 |
| I32 recep1To32WarnLoMap | 1.3.6.1.4.1.30932.1.1.3.10.11 | Integer32 | read-only | Low threshold warning receptacle state bitmap: bit0=recep1, bit1=recep2, ... bit31=recep32 |
| menergy | 1.3.6.1.4.1.30932.1.1.3.11 | |||
| C64 energyxy1sEx | 1.3.6.1.4.1.30932.1.1.3.11.1 | Counter64 | read-only | XY1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 energyyz1s | 1.3.6.1.4.1.30932.1.1.3.11.2 | Counter64 | read-only | YZ1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 energyzx1s | 1.3.6.1.4.1.30932.1.1.3.11.3 | Counter64 | read-only | ZX1 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 energyxy2s | 1.3.6.1.4.1.30932.1.1.3.11.4 | Counter64 | read-only | XY2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 energyyz2s | 1.3.6.1.4.1.30932.1.1.3.11.5 | Counter64 | read-only | YZ2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 energyzx2s | 1.3.6.1.4.1.30932.1.1.3.11.6 | Counter64 | read-only | ZX2 branch energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| receptacleEnergy | 1.3.6.1.4.1.30932.1.1.3.12 | |||
| C64 receptacleEnergyoutlet1s | 1.3.6.1.4.1.30932.1.1.3.12.1 | Counter64 | read-only | Outlet1 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet2s | 1.3.6.1.4.1.30932.1.1.3.12.2 | Counter64 | read-only | Outlet2 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet3s | 1.3.6.1.4.1.30932.1.1.3.12.3 | Counter64 | read-only | Outlet3 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet4s | 1.3.6.1.4.1.30932.1.1.3.12.4 | Counter64 | read-only | Outlet4 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet5s | 1.3.6.1.4.1.30932.1.1.3.12.5 | Counter64 | read-only | Outlet5 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet6s | 1.3.6.1.4.1.30932.1.1.3.12.6 | Counter64 | read-only | Outlet6 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet7s | 1.3.6.1.4.1.30932.1.1.3.12.7 | Counter64 | read-only | Outlet7 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet8s | 1.3.6.1.4.1.30932.1.1.3.12.8 | Counter64 | read-only | Outlet8 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet9s | 1.3.6.1.4.1.30932.1.1.3.12.9 | Counter64 | read-only | Outlet9 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet10s | 1.3.6.1.4.1.30932.1.1.3.12.10 | Counter64 | read-only | Outlet10 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet11s | 1.3.6.1.4.1.30932.1.1.3.12.11 | Counter64 | read-only | Outlet11 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet12s | 1.3.6.1.4.1.30932.1.1.3.12.12 | Counter64 | read-only | Outlet12 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet13s | 1.3.6.1.4.1.30932.1.1.3.12.13 | Counter64 | read-only | Outlet13 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet14s | 1.3.6.1.4.1.30932.1.1.3.12.14 | Counter64 | read-only | Outlet14 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet15s | 1.3.6.1.4.1.30932.1.1.3.12.15 | Counter64 | read-only | Outlet15 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet16s | 1.3.6.1.4.1.30932.1.1.3.12.16 | Counter64 | read-only | Outlet16 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet17s | 1.3.6.1.4.1.30932.1.1.3.12.17 | Counter64 | read-only | Outlet17 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet18s | 1.3.6.1.4.1.30932.1.1.3.12.18 | Counter64 | read-only | Outlet18 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet19s | 1.3.6.1.4.1.30932.1.1.3.12.19 | Counter64 | read-only | Outlet19 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet20s | 1.3.6.1.4.1.30932.1.1.3.12.20 | Counter64 | read-only | Outlet20 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet21s | 1.3.6.1.4.1.30932.1.1.3.12.21 | Counter64 | read-only | Outlet21 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet22s | 1.3.6.1.4.1.30932.1.1.3.12.22 | Counter64 | read-only | Outlet22 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet23s | 1.3.6.1.4.1.30932.1.1.3.12.23 | Counter64 | read-only | Outlet23 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| C64 receptacleEnergyoutlet24s | 1.3.6.1.4.1.30932.1.1.3.12.24 | Counter64 | read-only | Outlet24 receptacle energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| mline | 1.3.6.1.4.1.30932.1.1.3.13 | |||
| I32 line1curr | 1.3.6.1.4.1.30932.1.1.3.13.1 | Integer32 | read-only | Line 1 current draw in 1/100 Amps. |
| I32 line2curr | 1.3.6.1.4.1.30932.1.1.3.13.2 | Integer32 | read-only | Line 2 current draw in 1/100 Amps. |
| I32 line3curr | 1.3.6.1.4.1.30932.1.1.3.13.3 | Integer32 | read-only | Line 3 current draw in 1/100 Amps. |
| control | 1.3.6.1.4.1.30932.1.1.4 | |||
| creceptacleControl | 1.3.6.1.4.1.30932.1.1.4.1 | |||
| I32 outlet1ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.1 | Integer32 | read-write | Turn ON or OFF power to Outlet1, 1=ON, 0=OFF. |
| I32 outlet2ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.2 | Integer32 | read-write | Turn ON or OFF power to Outlet2, 1=ON, 0=OFF. |
| I32 outlet3ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.3 | Integer32 | read-write | Turn ON or OFF power to Outlet3, 1=ON, 0=OFF. |
| I32 outlet4ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.4 | Integer32 | read-write | Turn ON or OFF power to Outlet4, 1=ON, 0=OFF. |
| I32 outlet5ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.5 | Integer32 | read-write | Turn ON or OFF power to Outlet5, 1=ON, 0=OFF. |
| I32 outlet6ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.6 | Integer32 | read-write | Turn ON or OFF power to Outlet6, 1=ON, 0=OFF. |
| I32 outlet7ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.7 | Integer32 | read-write | Turn ON or OFF power to Outlet7, 1=ON, 0=OFF. |
| I32 outlet8ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.8 | Integer32 | read-write | Turn ON or OFF power to Outlet8, 1=ON, 0=OFF. |
| I32 outlet9ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.9 | Integer32 | read-write | Turn ON or OFF power to Outlet9, 1=ON, 0=OFF. |
| I32 outlet10ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.10 | Integer32 | read-write | Turn ON or OFF power to Outlet10, 1=ON, 0=OFF. |
| I32 outlet11ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.11 | Integer32 | read-write | Turn ON or OFF power to Outlet11, 1=ON, 0=OFF. |
| I32 outlet12ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.12 | Integer32 | read-write | Turn ON or OFF power to Outlet12, 1=ON, 0=OFF. |
| I32 outlet13ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.13 | Integer32 | read-write | Turn ON or OFF power to Outlet13, 1=ON, 0=OFF. |
| I32 outlet14ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.14 | Integer32 | read-write | Turn ON or OFF power to Outlet14, 1=ON, 0=OFF. |
| I32 outlet15ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.15 | Integer32 | read-write | Turn ON or OFF power to Outlet15, 1=ON, 0=OFF. |
| I32 outlet16ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.16 | Integer32 | read-write | Turn ON or OFF power to Outlet16, 1=ON, 0=OFF. |
| I32 outlet17ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.17 | Integer32 | read-write | Turn ON or OFF power to Outlet17, 1=ON, 0=OFF. |
| I32 outlet18ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.18 | Integer32 | read-write | Turn ON or OFF power to Outlet18, 1=ON, 0=OFF. |
| I32 outlet19ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.19 | Integer32 | read-write | Turn ON or OFF power to Outlet19, 1=ON, 0=OFF. |
| I32 outlet20ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.20 | Integer32 | read-write | Turn ON or OFF power to Outlet20, 1=ON, 0=OFF. |
| I32 outlet21ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.21 | Integer32 | read-write | Turn ON or OFF power to Outlet21, 1=ON, 0=OFF. |
| I32 outlet22ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.22 | Integer32 | read-write | Turn ON or OFF power to Outlet22, 1=ON, 0=OFF. |
| I32 outlet23ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.23 | Integer32 | read-write | Turn ON or OFF power to Outlet23, 1=ON, 0=OFF. |
| I32 outlet24ONOFF | 1.3.6.1.4.1.30932.1.1.4.1.24 | Integer32 | read-write | Turn ON or OFF power to Outlet24, 1=ON, 0=OFF. |
| receptacleReset | 1.3.6.1.4.1.30932.1.1.4.2 | |||
| I32 outlet1Reset | 1.3.6.1.4.1.30932.1.1.4.2.1 | Integer32 | read-write | Reset power to Outlet1, 1=reset. |
| I32 outlet2Reset | 1.3.6.1.4.1.30932.1.1.4.2.2 | Integer32 | read-write | Reset power to Outlet2, 1=reset. |
| I32 outlet3Reset | 1.3.6.1.4.1.30932.1.1.4.2.3 | Integer32 | read-write | Reset power to Outlet3, 1=reset. |
| I32 outlet4Reset | 1.3.6.1.4.1.30932.1.1.4.2.4 | Integer32 | read-write | Reset power to Outlet4, 1=reset. |
| I32 outlet5Reset | 1.3.6.1.4.1.30932.1.1.4.2.5 | Integer32 | read-write | Reset power to Outlet5, 1=reset. |
| I32 outlet6Reset | 1.3.6.1.4.1.30932.1.1.4.2.6 | Integer32 | read-write | Reset power to Outlet6, 1=reset. |
| I32 outlet7Reset | 1.3.6.1.4.1.30932.1.1.4.2.7 | Integer32 | read-write | Reset power to Outlet7, 1=reset. |
| I32 outlet8Reset | 1.3.6.1.4.1.30932.1.1.4.2.8 | Integer32 | read-write | Reset power to Outlet8, 1=reset. |
| I32 outlet9Reset | 1.3.6.1.4.1.30932.1.1.4.2.9 | Integer32 | read-write | Reset power to Outlet9, 1=reset. |
| I32 outlet10Reset | 1.3.6.1.4.1.30932.1.1.4.2.10 | Integer32 | read-write | Reset power to Outlet10, 1=reset. |
| I32 outlet11Reset | 1.3.6.1.4.1.30932.1.1.4.2.11 | Integer32 | read-write | Reset power to Outlet11, 1=reset. |
| I32 outlet12Reset | 1.3.6.1.4.1.30932.1.1.4.2.12 | Integer32 | read-write | Reset power to Outlet12, 1=reset. |
| I32 outlet13Reset | 1.3.6.1.4.1.30932.1.1.4.2.13 | Integer32 | read-write | Reset power to Outlet13, 1=reset. |
| I32 outlet14Reset | 1.3.6.1.4.1.30932.1.1.4.2.14 | Integer32 | read-write | Reset power to Outlet14, 1=reset. |
| I32 outlet15Reset | 1.3.6.1.4.1.30932.1.1.4.2.15 | Integer32 | read-write | Reset power to Outlet15, 1=reset. |
| I32 outlet16Reset | 1.3.6.1.4.1.30932.1.1.4.2.16 | Integer32 | read-write | Reset power to Outlet16, 1=reset. |
| I32 outlet17Reset | 1.3.6.1.4.1.30932.1.1.4.2.17 | Integer32 | read-write | Reset power to Outlet17, 1=reset. |
| I32 outlet18Reset | 1.3.6.1.4.1.30932.1.1.4.2.18 | Integer32 | read-write | Reset power to Outlet18, 1=reset. |
| I32 outlet19Reset | 1.3.6.1.4.1.30932.1.1.4.2.19 | Integer32 | read-write | Reset power to Outlet19, 1=reset. |
| I32 outlet20Reset | 1.3.6.1.4.1.30932.1.1.4.2.20 | Integer32 | read-write | Reset power to Outlet20, 1=reset. |
| I32 outlet21Reset | 1.3.6.1.4.1.30932.1.1.4.2.21 | Integer32 | read-write | Reset power to Outlet21, 1=reset. |
| I32 outlet22Reset | 1.3.6.1.4.1.30932.1.1.4.2.22 | Integer32 | read-write | Reset power to Outlet22, 1=reset. |
| I32 outlet23Reset | 1.3.6.1.4.1.30932.1.1.4.2.23 | Integer32 | read-write | Reset power to Outlet23, 1=reset. |
| I32 outlet24Reset | 1.3.6.1.4.1.30932.1.1.4.2.24 | Integer32 | read-write | Reset power to Outlet24, 1=reset. |
| STR receptacleCtrlMap | 1.3.6.1.4.1.30932.1.1.4.3 | DisplayString | read-only | Map of receptacle status in ascending order, 1=ON, 0=OFF. |
| chained | 1.3.6.1.4.1.30932.1.1.5 | |||
| I32 pduCount | 1.3.6.1.4.1.30932.1.1.5.1 | Integer32 | read-only | Count of number of PDUs in the chain. |
| OCT pduMap | 1.3.6.1.4.1.30932.1.1.5.2 | OCTET STRING | read-only | Table map of PDU IDs in the chain, each ID consists of 4 bytes. |
| I32 pduSelect | 1.3.6.1.4.1.30932.1.1.5.3 | Integer32 | read-write | Selects the PDUs in the chain for access. |
| OCT pduNamelist | 1.3.6.1.4.1.30932.1.1.5.4 | OCTET STRING | read-only | List of PDU Names in the chain link, delimited by '|' and in matching order with pduMap. |
| cpiTraps | 1.3.6.1.4.1.30932.1.1.6 | |||
| cpiSpecific | 1.3.6.1.4.1.30932.1.1.6.0 | |||
| NTF maxCurrentxy1 | 1.3.6.1.4.1.30932.1.1.6.0.1 | Trap is sent when current in XY1 exceeds set limit. | ||
| NTF maxCurrentyz1 | 1.3.6.1.4.1.30932.1.1.6.0.2 | Trap is sent when current in YZ1 exceeds set limit. | ||
| NTF maxCurrentzx1 | 1.3.6.1.4.1.30932.1.1.6.0.3 | Trap is sent when current in ZX1 exceeds set limit. | ||
| NTF maxCurrentxy2 | 1.3.6.1.4.1.30932.1.1.6.0.4 | Trap is sent when current in XY2 exceeds set limit. | ||
| NTF maxCurrentyz2 | 1.3.6.1.4.1.30932.1.1.6.0.5 | Trap is sent when current in YZ2 exceeds set limit. | ||
| NTF maxCurrentzx2 | 1.3.6.1.4.1.30932.1.1.6.0.6 | Trap is sent when current in ZX2 exceeds set limit. | ||
| NTF minCurrentxy1 | 1.3.6.1.4.1.30932.1.1.6.0.7 | Trap is sent when current in XY1 drops below set limit. | ||
| NTF minCurrentyz1 | 1.3.6.1.4.1.30932.1.1.6.0.8 | Trap is sent when current in YZ1 drops below set limit. | ||
| NTF minCurrentzx1 | 1.3.6.1.4.1.30932.1.1.6.0.9 | Trap is sent when current in ZX1 drops below set limit. | ||
| NTF minCurrentxy2 | 1.3.6.1.4.1.30932.1.1.6.0.10 | Trap is sent when current in XY2 drops below set limit. | ||
| NTF minCurrentyz2 | 1.3.6.1.4.1.30932.1.1.6.0.11 | Trap is sent when current in YZ2 drops below set limit. | ||
| NTF minCurrentzx2 | 1.3.6.1.4.1.30932.1.1.6.0.12 | Trap is sent when current in ZX2 drops below set limit. | ||
| NTF maxVoltxy1 | 1.3.6.1.4.1.30932.1.1.6.0.13 | Trap is sent when voltage in XY1 exceeds high limit. | ||
| NTF maxVoltyz1 | 1.3.6.1.4.1.30932.1.1.6.0.14 | Trap is sent when voltage in YZ1 exceeds high limit. | ||
| NTF maxVoltzx1 | 1.3.6.1.4.1.30932.1.1.6.0.15 | Trap is sent when voltage in ZX1 exceeds high limit. | ||
| NTF maxVoltxy2 | 1.3.6.1.4.1.30932.1.1.6.0.16 | Trap is sent when voltage in XY2 exceeds high limit. | ||
| NTF maxVoltyz2 | 1.3.6.1.4.1.30932.1.1.6.0.17 | Trap is sent when voltage in YZ2 exceeds high limit. | ||
| NTF maxVoltzx2 | 1.3.6.1.4.1.30932.1.1.6.0.18 | Trap is sent when voltage in ZX2 exceeds high limit. | ||
| NTF minVoltxy1 | 1.3.6.1.4.1.30932.1.1.6.0.19 | Trap is sent when voltage in XY1 drops below low limit. | ||
| NTF minVoltyz1 | 1.3.6.1.4.1.30932.1.1.6.0.20 | Trap is sent when voltage in YZ1 drops below low limit. | ||
| NTF minVoltzx1 | 1.3.6.1.4.1.30932.1.1.6.0.21 | Trap is sent when voltage in ZX1 drops below low limit. | ||
| NTF minVoltxy2 | 1.3.6.1.4.1.30932.1.1.6.0.22 | Trap is sent when voltage in XY2 drops below low limit. | ||
| NTF minVoltyz2 | 1.3.6.1.4.1.30932.1.1.6.0.23 | Trap is sent when voltage in YZ2 drops below low limit. | ||
| NTF minVoltzx2 | 1.3.6.1.4.1.30932.1.1.6.0.24 | Trap is sent when voltage in ZX2 drops below low limit. | ||
| NTF maxTemperature1 | 1.3.6.1.4.1.30932.1.1.6.0.25 | Trap is sent when temperature exceeds high limit. | ||
| NTF maxTemperature2 | 1.3.6.1.4.1.30932.1.1.6.0.26 | Trap is sent when temperature exceeds high limit. | ||
| NTF minTemperature1 | 1.3.6.1.4.1.30932.1.1.6.0.27 | Trap is sent when temperature drops below low limit. | ||
| NTF minTemperature2 | 1.3.6.1.4.1.30932.1.1.6.0.28 | Trap is sent when temperature drops below low limit. | ||
| NTF maxHumidity1 | 1.3.6.1.4.1.30932.1.1.6.0.29 | Trap is sent when humidity exceeds high limit. | ||
| NTF maxHumidity2 | 1.3.6.1.4.1.30932.1.1.6.0.30 | Trap is sent when humidity exceeds high limit. | ||
| NTF minHumidity1 | 1.3.6.1.4.1.30932.1.1.6.0.31 | Trap is sent when humidity drops below low limit. | ||
| NTF minHumidity2 | 1.3.6.1.4.1.30932.1.1.6.0.32 | Trap is sent when humidity drops below low limit. | ||
| NTF changeLog | 1.3.6.1.4.1.30932.1.1.6.0.33 | Trap is sent when changes in current exceed the amount set in LOGDIFFERENCE. | ||
| NTF dataLog | 1.3.6.1.4.1.30932.1.1.6.0.34 | Trap is sent when the data logging interval time is reached | ||
| NTF alarmChange | 1.3.6.1.4.1.30932.1.1.6.0.35 | Trap is sent when all alarms have been resolved/cleared | ||
| cpiMIBConformance | 1.3.6.1.4.1.30932.1.2 | |||
| cpiMIBCompliances | 1.3.6.1.4.1.30932.1.2.1 | |||
| cpiMIBComplianceRev1 | 1.3.6.1.4.1.30932.1.2.1.1 | The compliance statement for this MIB. | ||
| cpiMIBGroups | 1.3.6.1.4.1.30932.1.2.2 | |||
| cpiMIBGroupsObjects | 1.3.6.1.4.1.30932.1.2.2.1 | A collection of objects for managing the PDU. | ||
| cpiMIBGroupNotifications | 1.3.6.1.4.1.30932.1.2.2.2 | A collection of notifications supported by PDU. | ||
| unity | 1.3.6.1.4.1.30932.1.10 | |||
| econnect | 1.3.6.1.4.1.30932.1.10.1 | |||
| econnectConfiguration | 1.3.6.1.4.1.30932.1.10.1.1 | |||
| network | 1.3.6.1.4.1.30932.1.10.1.1.1 | |||
| ipv4 | 1.3.6.1.4.1.30932.1.10.1.1.1.1 | |||
| INT ipv4IpV4Enable | 1.3.6.1.4.1.30932.1.10.1.1.1.1.1 | INTEGER | read-write | Controls whether the IPv4 network interface is enabled. |
| IP ipv4PduIP | 1.3.6.1.4.1.30932.1.10.1.1.1.1.2 | IpAddress | read-write | Set or get the IPv4 address of the PDU. |
| INT ipv4AutoIP | 1.3.6.1.4.1.30932.1.10.1.1.1.1.3 | INTEGER | read-write | Controls whether the IPv4 address is retrieved from a DHCP server or is set statically. |
| INT ipv4AutoDNS | 1.3.6.1.4.1.30932.1.10.1.1.1.1.4 | INTEGER | read-write | Controls whether the DNS addresses are retrieved from a DHCP server or are set statically. |
| IP ipv4SubnetMask | 1.3.6.1.4.1.30932.1.10.1.1.1.1.5 | IpAddress | read-write | The subnet mask associated with the IPv4 address of this entry. The value of the mask is an IPv4 address with all the network bits set to 1 and all the hosts bits set to 0. |
| IP ipv4Gateway | 1.3.6.1.4.1.30932.1.10.1.1.1.1.6 | IpAddress | read-write | Set or get the IPv4 address of the gateway router for the PDU. |
| IP ipv4Dns1 | 1.3.6.1.4.1.30932.1.10.1.1.1.1.7 | IpAddress | read-write | Set or get the IPv4 address of the first DNS entry for the PDU. |
| IP ipv4Dns2 | 1.3.6.1.4.1.30932.1.10.1.1.1.1.8 | IpAddress | read-write | Set or get the IPv4 address of the second DNS entry for the PDU. |
| IP ipv4Dns3 | 1.3.6.1.4.1.30932.1.10.1.1.1.1.9 | IpAddress | read-write | Set or get the IPv4 address of the third DNS entry for the PDU. |
| ipv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2 | |||
| INT ipv6LinkLocalEnable | 1.3.6.1.4.1.30932.1.10.1.1.1.2.2 | INTEGER | read-write | Controls whether the IPv6 link-local address is enabled. |
| INT ipv6GlobalAddrEnable | 1.3.6.1.4.1.30932.1.10.1.1.1.2.3 | INTEGER | read-write | Controls whether the IPv6 global address is enabled. |
| STR ipv6PduIPv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.4 | DisplayString | read-write | Set or get the IPv6 address of the PDU. |
| INT ipv6AutoIPv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.5 | INTEGER | read-write | Controls whether the IPv6 address is retrieved from a DHCP server or is set statically. |
| I32 autoDNSv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.6 | Integer32 | read-write | Controls whether the DNS IPv6 address is retrieved from a DHCP server or is set statically. |
| STR subnetMaskv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.7 | DisplayString | read-write | The subnet mask associated with the IPv6 address of this entry. The value of the mask is an IPv6 address with all the network bits set to 1 and all the hosts bits set to 0. |
| STR gatewayv6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.8 | DisplayString | read-write | Set or get the IPv6 address of the gateway router for the PDU. |
| STR dns1v6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.9 | DisplayString | read-write | Set or get the IPv6 address of the first DNS entry for the PDU. |
| STR dns2v6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.10 | DisplayString | read-write | Set or get the IPv6 address of the second DNS entry for the PDU. |
| STR dns3v6 | 1.3.6.1.4.1.30932.1.10.1.1.1.2.11 | DisplayString | read-write | Set or get the IPv6 address of the third DNS entry for the PDU. |
| time | 1.3.6.1.4.1.30932.1.10.1.1.1.3 | |||
| STR timeRfcTimeServer | 1.3.6.1.4.1.30932.1.10.1.1.1.3.1 | DisplayString | read-write | Set or get the IP address of the RFC Time Server. |
| STR timeNtpTimeServer | 1.3.6.1.4.1.30932.1.10.1.1.1.3.2 | DisplayString | read-write | Set or get the IP address of the NTP Time Server. |
| interfaces | 1.3.6.1.4.1.30932.1.10.1.1.2 | |||
| snmp | 1.3.6.1.4.1.30932.1.10.1.1.2.1 | |||
| INT snmpSnmpEnable | 1.3.6.1.4.1.30932.1.10.1.1.2.1.1 | INTEGER | read-write | Controls whether the SNMP network service is enabled. |
| econnectSnmpHosts | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2 | |||
| INT snmpHostsSnmpHostOnly | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.1 | INTEGER | read-write | Controls whether access to the SNMP service responsed to the listed hosts (snmpHost1, snmpHost2, snmpHost3) or to any host requesting data. |
| STR snmpHostsSnmpHost1 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.2 | DisplayString | read-write | Set or get the IPv4 address of the first host the SNMP service will reply to. |
| STR snmpHostsSnmpHost2 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.3 | DisplayString | read-write | Set or get the IPv4 address of the second host the SNMP service will reply to. |
| STR snmpHostsSnmpHost3 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.4 | DisplayString | read-write | Set or get the IPv4 address of the third host the SNMP service will reply to. |
| STR snmpHostIPv61 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.5 | DisplayString | read-write | Set or get the IPv6 address of the first host the SNMP service will reply to. |
| STR snmpHostIPv62 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.6 | DisplayString | read-write | Set or get the IPv6 address of the first host the SNMP service will reply to. |
| STR snmpHostIPV63 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.2.7 | DisplayString | read-write | Set or get the IPv6 address of the first host the SNMP service will reply to. |
| I32 snmpSnmpQueryPort | 1.3.6.1.4.1.30932.1.10.1.1.2.1.3 | Integer32 | read-write | Set or get the port for SNMP query access. |
| I32 snmpSnmpTrapPort | 1.3.6.1.4.1.30932.1.10.1.1.2.1.4 | Integer32 | read-write | Set or get the port for SNMP traps. |
| STR snmpSnmpReadComm | 1.3.6.1.4.1.30932.1.10.1.1.2.1.5 | DisplayString | read-write | Set or get the SNMP Read Community. |
| STR snmpSnmpWriteComm | 1.3.6.1.4.1.30932.1.10.1.1.2.1.6 | DisplayString | read-write | Set or get the SNMP Write Community. |
| STR snmpSnmpUSMuserName | 1.3.6.1.4.1.30932.1.10.1.1.2.1.7 | DisplayString | read-write | Set or get the SNMP USM User Name. |
| INT snmpSnmpSecurityLevel | 1.3.6.1.4.1.30932.1.10.1.1.2.1.8 | INTEGER | read-write | Set or get the security Level for SNMP: 0 = v1, 1 = v2c, 2 = v3 no authentication, 3 = v3 with authentication only, 4 = v3 with authentication and privacy |
| INT snmpSnmpAuthAlgo | 1.3.6.1.4.1.30932.1.10.1.1.2.1.9 | INTEGER | read-write | Set or get the Authentication Algorithm for SNMP. |
| INT snmpSnmpPrivAlgo | 1.3.6.1.4.1.30932.1.10.1.1.2.1.10 | INTEGER | read-write | Get or get the Privacy Algorithm for SNMP. |
| STR snmpSnmpAuthPasswd | 1.3.6.1.4.1.30932.1.10.1.1.2.1.11 | DisplayString | read-write | Set or Get the SNMP Authentication Password. |
| STR snmpSnmpPrivPasswd | 1.3.6.1.4.1.30932.1.10.1.1.2.1.12 | DisplayString | read-write | Set or get the SNMP Privacy Password. |
| STR snmpSnmpContextName | 1.3.6.1.4.1.30932.1.10.1.1.2.1.13 | DisplayString | read-write | Set or get the SNMP Context Name. |
| STR snmpSnmpEngineID | 1.3.6.1.4.1.30932.1.10.1.1.2.1.14 | DisplayString | read-write | Set or get the SNMP Engine ID. |
| STR snmpSnmpLocAuthKey | 1.3.6.1.4.1.30932.1.10.1.1.2.1.15 | DisplayString | read-write | Set or get the SNMP Local Authentication Key. |
| STR snmpSnmpLocPrivKey | 1.3.6.1.4.1.30932.1.10.1.1.2.1.16 | DisplayString | read-write | Set or get the SNMP Local Privacy Key. |
| econnectSnmpTrapHosts | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17 | |||
| STR snmpTrapHostsSnmpTrapHost1 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.1 | DisplayString | read-write | Set or get the IPv4 address of the first SNMP Trap Host. |
| STR snmpTrapHostsSnmpTrapHost2 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.2 | DisplayString | read-write | Set or get the IPv4 address of the second SNMP Trap Host. |
| STR snmpTrapHostsSnmpTrapHost3 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.3 | DisplayString | read-write | Set or get the IPv4 address of the third SNMP Trap Host. |
| STR snmpTrapHostIPv61 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.4 | DisplayString | read-write | Set or get the IPv6 address of the first SNMP Trap Host. |
| STR snmpTrapHostIPv62 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.5 | DisplayString | read-write | Set or get the IPv6 address of the second SNMP Trap Host. |
| STR snmpTrapHostIPv63 | 1.3.6.1.4.1.30932.1.10.1.1.2.1.17.6 | DisplayString | read-write | Set or get the IPv6 address of the third SNMP Trap Host. |
| snmpControl | 1.3.6.1.4.1.30932.1.10.1.1.2.1.18 | |||
| INT enableEASSNMPControl | 1.3.6.1.4.1.30932.1.10.1.1.2.1.18.5 | INTEGER | read-write | Allows the use of SNMP to open/close the door locks. It is recommended that this only be enabled with SNMP v3 configurations. |
| http | 1.3.6.1.4.1.30932.1.10.1.1.2.2 | |||
| INT httpEnableWeb | 1.3.6.1.4.1.30932.1.10.1.1.2.2.1 | INTEGER | read-write | Controls whether the web interface is enabled. |
| INT httpHttpEnable | 1.3.6.1.4.1.30932.1.10.1.1.2.2.2 | INTEGER | read-write | Controls whether the HTTP service is enabled. |
| INT httpHttpsEnable | 1.3.6.1.4.1.30932.1.10.1.1.2.2.3 | INTEGER | read-write | Controls whether the HTTPS service is enabled. |
| I32 httpHttpPort | 1.3.6.1.4.1.30932.1.10.1.1.2.2.4 | Integer32 | read-write | Set or get the port for unsecure HTTP access. |
| I32 httpHttpsPort | 1.3.6.1.4.1.30932.1.10.1.1.2.2.5 | Integer32 | read-write | Set or get the port for secure HTTPS access. |
| smtp | 1.3.6.1.4.1.30932.1.10.1.1.2.3 | |||
| INT enableSMTP | 1.3.6.1.4.1.30932.1.10.1.1.2.3.1 | INTEGER | read-write | Controls whether the mail notification service is enabled.. |
| I32 smtpSmtpSendPort | 1.3.6.1.4.1.30932.1.10.1.1.2.3.2 | Integer32 | read-write | Set or get the port for SMTP send. |
| I32 smtpSmtpReceivePort | 1.3.6.1.4.1.30932.1.10.1.1.2.3.3 | Integer32 | read-write | Set or get the port for SMTP Receive. |
| STR smtpSmtpServer | 1.3.6.1.4.1.30932.1.10.1.1.2.3.4 | DisplayString | read-write | Set or get the IP address of the e-mail server. |
| STR smtpSmtpUserName | 1.3.6.1.4.1.30932.1.10.1.1.2.3.5 | DisplayString | read-write | Set or get the PDU e-mail user login name. |
| STR smtpSmtpUserPasswd | 1.3.6.1.4.1.30932.1.10.1.1.2.3.6 | DisplayString | read-write | Set or get the PDU e-mail user login password. |
| STR smtpSmtpEmailAddr | 1.3.6.1.4.1.30932.1.10.1.1.2.3.7 | DisplayString | read-write | Set or get the PDU e-mail address. |
| STR smtpSmtpEmailDestination1 | 1.3.6.1.4.1.30932.1.10.1.1.2.3.8 | DisplayString | read-write | Set or get the e-mail address of the first recipient. |
| STR smtpSmtpEmailDestination2 | 1.3.6.1.4.1.30932.1.10.1.1.2.3.9 | DisplayString | read-write | Set or get the e-mail address of the second recipient. |
| STR smtpSmtpEmailDestination3 | 1.3.6.1.4.1.30932.1.10.1.1.2.3.10 | DisplayString | read-write | Set or get the e-mail address of the third recipient. |
| I32 smtpSmtpServOptions | 1.3.6.1.4.1.30932.1.10.1.1.2.3.11 | Integer32 | read-write | Set or get the SMTP server options. |
| logging | 1.3.6.1.4.1.30932.1.10.1.1.3 | |||
| INT logEnable | 1.3.6.1.4.1.30932.1.10.1.1.3.1 | INTEGER | read-write | Controls whether the data logging feature is enabled. |
| I32 loggingLogInterval | 1.3.6.1.4.1.30932.1.10.1.1.3.2 | Integer32 | read-write | Set or get the time interval in seconds for logging metrics (disabled if < 10). |
| I32 loggingLogDifference | 1.3.6.1.4.1.30932.1.10.1.1.3.3 | Integer32 | read-write | Set or get the current difference in 1/100 Amps that triggers logging metrics. |
| INT loggingNetservdLog | 1.3.6.1.4.1.30932.1.10.1.1.3.4 | INTEGER | read-write | Controls sending the data logs to log server over network. |
| INT loggingAutonetLog | 1.3.6.1.4.1.30932.1.10.1.1.3.5 | INTEGER | read-write | Controls whether automatic transfer to log server every 6 hours is enabled. |
| INT loggingStdmeterdLog | 1.3.6.1.4.1.30932.1.10.1.1.3.6 | INTEGER | read-write | Controls whether logging of branch, receptacle and environmental metrics is enabled. |
| INT loggingGroupmeterdLog | 1.3.6.1.4.1.30932.1.10.1.1.3.7 | INTEGER | read-write | Controls whether logging of grouped receptacle metrics is enabled. |
| INT loggingAlarmdLog | 1.3.6.1.4.1.30932.1.10.1.1.3.8 | INTEGER | read-write | Controls whether logging of alarm events is enabled. |
| INT loggingUserlogindLog | 1.3.6.1.4.1.30932.1.10.1.1.3.9 | INTEGER | read-write | Control whether logging of user login events is enabled. |
| INT loggingUsersetupdLog | 1.3.6.1.4.1.30932.1.10.1.1.3.10 | INTEGER | read-write | Control whether logging of user setup change events is enabled. |
| INT loggingFwupdatedLog | 1.3.6.1.4.1.30932.1.10.1.1.3.11 | INTEGER | read-write | Control whether the logging of firmware updates is enabled. |
| INT loggingSetupchangedLog | 1.3.6.1.4.1.30932.1.10.1.1.3.12 | INTEGER | read-write | Control whether the logging of setup change events is enabled. |
| INT loggingRecepchangedLog | 1.3.6.1.4.1.30932.1.10.1.1.3.13 | INTEGER | read-write | Control whether logging of receptacle state changes is enabled. |
| INT loggingPduopchangedLog | 1.3.6.1.4.1.30932.1.10.1.1.3.14 | INTEGER | read-write | Control whether logging of PDU operation and state changes is enabled. |
| I32 loggingDLogCycle | 1.3.6.1.4.1.30932.1.10.1.1.3.15 | Integer32 | read-write | Set or get the time interval in minutes for internal data logging to occur. |
| I32 loggingDLogFullWarnLevel | 1.3.6.1.4.1.30932.1.10.1.1.3.16 | Integer32 | read-write | Set or get the warning threshold for percentage of storage full (min=50, max=100). |
| STR loggingNetdLogServer | 1.3.6.1.4.1.30932.1.10.1.1.3.17 | DisplayString | read-write | Set or get the network address for the data server. |
| I32 loggingNetdLogPort | 1.3.6.1.4.1.30932.1.10.1.1.3.18 | Integer32 | read-write | Set or get the port used by the data server. |
| STR loggingNetdLogUser | 1.3.6.1.4.1.30932.1.10.1.1.3.19 | DisplayString | read-write | Set or get the user name to access the data server. |
| STR loggingNetdLogPasswd | 1.3.6.1.4.1.30932.1.10.1.1.3.20 | DisplayString | read-write | Set or get the user password to access the data server. |
| STR loggingNetdLogDestdir | 1.3.6.1.4.1.30932.1.10.1.1.3.21 | DisplayString | read-write | Get or get the destination directory in the data server. |
| STR loggingNetdLogOptions | 1.3.6.1.4.1.30932.1.10.1.1.3.22 | DisplayString | read-write | Get or set the options string when accessing the data server. |
| STR sysLogIdentity | 1.3.6.1.4.1.30932.1.10.1.1.3.23 | DisplayString | read-write | Get or set the identity to use with the syslog. The identity is an arbitrary identification string which syslog will prefix to each message. This is intended to identify the source of the message. |
| INT sysLogFacility | 1.3.6.1.4.1.30932.1.10.1.1.3.24 | INTEGER | read-write | Get or set the facility to use with the syslog. The facility argument is used to specify what type of program is logging the message. |
| STR sysLogCentralServerAddr | 1.3.6.1.4.1.30932.1.10.1.1.3.25 | DisplayString | read-write | Get or set the IP address for the central syslog server. |
| INT sysLogCentralServerPort | 1.3.6.1.4.1.30932.1.10.1.1.3.26 | INTEGER | read-write | Get or set the port for the central syslog server. |
| accesscontrol | 1.3.6.1.4.1.30932.1.10.1.1.4 | |||
| ldap | 1.3.6.1.4.1.30932.1.10.1.1.4.1 | |||
| INT enableADAuth | 1.3.6.1.4.1.30932.1.10.1.1.4.1.1 | INTEGER | read-write | Controls whether the Active Directory authentication is enabled. |
| STR ldapAdServer | 1.3.6.1.4.1.30932.1.10.1.1.4.1.2 | DisplayString | read-write | Set or get the IP address of the Active Directory Server. |
| STR ldapAdDomain | 1.3.6.1.4.1.30932.1.10.1.1.4.1.3 | DisplayString | read-write | Set or get the Active Directory Domain. |
| I32 ldapAdPort | 1.3.6.1.4.1.30932.1.10.1.1.4.1.4 | Integer32 | read-write | Set or get the port for Active Directory authentication. |
| I32 ldapAdResvPort | 1.3.6.1.4.1.30932.1.10.1.1.4.1.5 | Integer32 | read-write | Set or get the alternate or reserved port for Active Directory Authentication. |
| radius | 1.3.6.1.4.1.30932.1.10.1.1.4.2 | |||
| INT enableRadiusAuth | 1.3.6.1.4.1.30932.1.10.1.1.4.2.1 | INTEGER | read-write | Controls whether radius authentication is enabled. |
| STR radiusRadiusServer | 1.3.6.1.4.1.30932.1.10.1.1.4.2.2 | DisplayString | read-write | Set or get the IP address of the Radius Authentication Server. |
| STR radiusRadiusSHSecret | 1.3.6.1.4.1.30932.1.10.1.1.4.2.3 | DisplayString | read-write | Set or get the Radius Shared Secret. |
| STR radiusRadiusNASServer | 1.3.6.1.4.1.30932.1.10.1.1.4.2.4 | DisplayString | read-write | Set or get the Radius Network Access Service. |
| I32 radiusRadiusPort | 1.3.6.1.4.1.30932.1.10.1.1.4.2.5 | Integer32 | read-write | Set or get the port for radius authentication. |
| I32 radiusNasPort | 1.3.6.1.4.1.30932.1.10.1.1.4.2.6 | Integer32 | read-write | Set or get the port for Radius Network Access Service. |
| INT radiusip6 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.7 | INTEGER | read-write | Enable/Disable IPv6 for radius authentication. |
| INT radiuscardenable | 1.3.6.1.4.1.30932.1.10.1.1.4.2.8 | INTEGER | read-write | Enable/Disable Radius for card authentication. |
| STR cardradiusserver | 1.3.6.1.4.1.30932.1.10.1.1.4.2.9 | DisplayString | read-write | Set or get the IP address of the Primary Radius Card Authentication Server. |
| STR cardradiusshsecret | 1.3.6.1.4.1.30932.1.10.1.1.4.2.10 | DisplayString | read-write | Set or get the Radius Card Shared Secret. |
| I32 cardradiusPort | 1.3.6.1.4.1.30932.1.10.1.1.4.2.11 | Integer32 | read-write | Set or get the port for Radius Card Authentication. |
| INT cardradiusip6 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.12 | INTEGER | read-write | Enable/Disable IPv6 for Radius Card Authentication. |
| STR radiusServer2 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.13 | DisplayString | read-write | Set or get the IP address of the Secondary Radius Authentication Server. |
| I32 radiusPort2 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.14 | Integer32 | read-write | Set or get the port for Secondary Radius Authentication. |
| STR radiusServer3 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.15 | DisplayString | read-write | Set or get the IP address of the Tertiary Radius Authentication Server. |
| I32 radiusPort3 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.16 | Integer32 | read-write | Set or get the port for Tertiary Radius Authentication. |
| STR cardradiusServer2 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.17 | DisplayString | read-write | Set or get the IP address of the Secondary Radius Card Authentication Server. |
| I32 cardradiusPort2 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.18 | Integer32 | read-write | Set or get the port for Secondary Radius Card Authentication. |
| STR cardradiusServer3 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.19 | DisplayString | read-write | Set or get the IP address of the Tertiary Radius Card Authentication Server. |
| I32 cardradiusPort3 | 1.3.6.1.4.1.30932.1.10.1.1.4.2.20 | Integer32 | read-write | Set or get the port for Tertiary Radius Card Authentication. |
| pdu | 1.3.6.1.4.1.30932.1.10.1.1.6 | |||
| INT pduInputTop | 1.3.6.1.4.1.30932.1.10.1.1.6.1 | INTEGER | read-write | Set or get the input cord entry orientation. |
| INT pduCelsiusTemp | 1.3.6.1.4.1.30932.1.10.1.1.6.2 | INTEGER | read-write | Set or get the temperature units. |
| INT pduShareRole | 1.3.6.1.4.1.30932.1.10.1.1.6.3 | INTEGER | read-write | Controls whether to allow sharing of PDU Primary and Alternate Roles. |
| INT pduMissingPDUNotify | 1.3.6.1.4.1.30932.1.10.1.1.6.4 | INTEGER | read-write | Controls whether to notify when a PDU is missing from the link. |
| INT pduRoleChangeNotify | 1.3.6.1.4.1.30932.1.10.1.1.6.5 | INTEGER | read-write | Control whether to notify when a PDU changes role in the link. |
| I32 pduDispTimeout | 1.3.6.1.4.1.30932.1.10.1.1.6.6 | Integer32 | read-write | Set or get the inactivity timeout in minutes to blank the local display (minimum is 1 minute). |
| I32 pduLoginTimeout | 1.3.6.1.4.1.30932.1.10.1.1.6.7 | Integer32 | read-write | Set or get the inactivity timeout in minutes to terminate a logged in session (minimum is 1 minute). |
| I32 pduDispBrightness | 1.3.6.1.4.1.30932.1.10.1.1.6.8 | Integer32 | read-write | Set or get the relative brightness of the local display (0 in min, 9 is max). |
| INT sumAmps | 1.3.6.1.4.1.30932.1.10.1.1.6.9 | INTEGER | read-write | Control whether the PDU displays the amperage sum of all branchs. |
| alerts | 1.3.6.1.4.1.30932.1.10.1.1.7 | |||
| I32 alertsAlarmInterval | 1.3.6.1.4.1.30932.1.10.1.1.7.1 | Integer32 | read-write | Set or get the time interval in seconds for alarm cycle (disabled if < 10). |
| routing | 1.3.6.1.4.1.30932.1.10.1.1.8 | |||
| eventLogRouting | 1.3.6.1.4.1.30932.1.10.1.1.8.1 | |||
| INT logBranchCritLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.1.1 | INTEGER | read-write | Enable/Disable logging of Critical Low Voltage on the Branch to the event log. |
| INT logBranchWarnLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.1.2 | INTEGER | read-write | Enable/Disable logging of Warning Low Voltage on the Branch to the event log. |
| INT logBranchWarnHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.1.3 | INTEGER | read-write | Enable/Disable logging of Warning High Voltage on the Branch to the event log. |
| INT logBranchCritHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.1.4 | INTEGER | read-write | Enable/Disable logging of Critical High Voltage on the Branch to the event log. |
| INT logBranchCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.5 | INTEGER | read-write | Enable/Disable logging of Critical Low Current on the Branch to the event log. |
| INT logBranchWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.6 | INTEGER | read-write | Enable/Disable logging of Warning Low Current on the Branch to the event log. |
| INT logBranchWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.7 | INTEGER | read-write | Enable/Disable logging of Warning High Current on the Branch to the event log. |
| INT logBranchCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.8 | INTEGER | read-write | Enable/Disable logging of Critical High Current on the Branch to the event log. |
| INT logOutletCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.9 | INTEGER | read-write | Enable/Disable logging of Critical Low Current on the Outlet to the event log. |
| INT logOutletWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.10 | INTEGER | read-write | Enable/Disable logging of Warning Low Current on the Outlet to the event log. |
| INT logOutletWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.11 | INTEGER | read-write | Enable/Disable logging of Warning High Current on the Outlet to the event log. |
| INT logOutletCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.1.12 | INTEGER | read-write | Enable/Disable logging of Critical High Current to the event log. |
| INT logTempCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.1.13 | INTEGER | read-write | Enable/Disable logging of Critical Low Temperature to the event log. |
| INT logTempWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.1.14 | INTEGER | read-write | Enable/Disable logging of Warning Low Temperature to the event log. |
| INT logTempWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.1.15 | INTEGER | read-write | Enable/Disable logging of Warning High Temperature to the event log. |
| INT logTempCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.1.16 | INTEGER | read-write | Enable/Disable logging of Critical High Temperature to the event log. |
| INT logHumidCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.1.17 | INTEGER | read-write | Enable/Disable logging of Critical Low Humidity to the event log. |
| INT logHumidWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.1.18 | INTEGER | read-write | Enable/Disable logging of Warning Low Humidity to the event log. |
| INT logHumidWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.1.19 | INTEGER | read-write | Enable/Disable logging of Warning High Humidity to the event log. |
| INT logHumidCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.1.20 | INTEGER | read-write | Enable/Disable logging of Critical High Humidity to the event log. |
| INT logScanPass | 1.3.6.1.4.1.30932.1.10.1.1.8.1.21 | INTEGER | read-write | Enable/Disable logging of successful card scan events to the event log. |
| INT logScanFail | 1.3.6.1.4.1.30932.1.10.1.1.8.1.22 | INTEGER | read-write | Enable/Disable logging of failed card scan events to the event log. |
| INT logDoorState | 1.3.6.1.4.1.30932.1.10.1.1.8.1.23 | INTEGER | read-write | Enable/Disable logging of Door Open/Close events to the event log. |
| INT logLockState | 1.3.6.1.4.1.30932.1.10.1.1.8.1.24 | INTEGER | read-write | Enable/Disable logging of Lock Open/Close events to the event log. |
| INT logExtendedOpen | 1.3.6.1.4.1.30932.1.10.1.1.8.1.25 | INTEGER | read-write | Enable/Disable logging of extended door open events to the event log. |
| INT logFirmareUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.1.26 | INTEGER | read-write | Enable/Disable logging of Firmare Update events to the event log. |
| INT logConfigUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.1.27 | INTEGER | read-write | Enable/Disable logging of configuration change events to the event log. |
| INT logRecepChange | 1.3.6.1.4.1.30932.1.10.1.1.8.1.28 | INTEGER | read-write | Enable/Disable logging of receptacle change events to the event log. |
| INT logSystem | 1.3.6.1.4.1.30932.1.10.1.1.8.1.29 | INTEGER | read-write | Enable/Disable logging of system events to the event log. |
| INT logPduAccess | 1.3.6.1.4.1.30932.1.10.1.1.8.1.30 | INTEGER | read-write | Enable/Disable logging of access to PDU events to the event log. |
| INT logSecureArray | 1.3.6.1.4.1.30932.1.10.1.1.8.1.31 | INTEGER | read-write | Enable/Disable logging of SecureArray events to the event log. |
| emailRouting | 1.3.6.1.4.1.30932.1.10.1.1.8.2 | |||
| INT emailBranchCritLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.2.1 | INTEGER | read-write | Enable/Disable notification of Critical Low Voltage on the Branch in an email. |
| INT emailBranchWarnLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.2.2 | INTEGER | read-write | Enable/Disable notification of Warning Low Voltage on the Branch in an email. |
| INT emailBranchWarnHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.2.3 | INTEGER | read-write | Enable/Disable notification of Warning High Voltage on the Branch in an email. |
| INT emailBranchCritHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.2.4 | INTEGER | read-write | Enable/Disable notification of Critical High Voltage on the Branch in an email. |
| INT emailBranchCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.5 | INTEGER | read-write | Enable/Disable notification of Critical Low Current on the Branch in an email. |
| INT emailBranchWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.6 | INTEGER | read-write | Enable/Disable notification of Warning Low Current on the Branch in an email. |
| INT emailBranchWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.7 | INTEGER | read-write | Enable/Disable notification of Warning High Current on the Branch in an email. |
| INT emailBranchCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.8 | INTEGER | read-write | Enable/Disable notification of Critical High Current on the Branch in an email. |
| INT emailOutletCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.9 | INTEGER | read-write | Enable/Disable notification of Critical Low Current on the Outlet in an email. |
| INT emailOutletWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.10 | INTEGER | read-write | Enable/Disable notification of Warning Low Current on the Outlet in an email. |
| INT emailOutletWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.11 | INTEGER | read-write | Enable/Disable notification of Warning High Current on the Outlet in an email. |
| INT emailOutletCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.2.12 | INTEGER | read-write | Enable/Disable notification of Critical High Current in an email. |
| INT emailTempCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.2.13 | INTEGER | read-write | Enable/Disable notification of Critical Low Temperature in an email. |
| INT emailTempWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.2.14 | INTEGER | read-write | Enable/Disable notification of Warning Low Temperature in an email. |
| INT emailTempWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.2.15 | INTEGER | read-write | Enable/Disable notification of Warning High Temperature in an email. |
| INT emailTempCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.2.16 | INTEGER | read-write | Enable/Disable notification of Critical High Temperature in an email. |
| INT emailHumidCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.2.17 | INTEGER | read-write | Enable/Disable notification of Critical Low Humidity in an email. |
| INT emailHumidWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.2.18 | INTEGER | read-write | Enable/Disable notification of Warning Low Humidity in an email. |
| INT emailHumidWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.2.19 | INTEGER | read-write | Enable/Disable notification of Warning High Humidity in an email. |
| INT emailHumidCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.2.20 | INTEGER | read-write | Enable/Disable notification of Critical High Humidity in an email. |
| INT emailScanPass | 1.3.6.1.4.1.30932.1.10.1.1.8.2.21 | INTEGER | read-write | Enable/Disable notification of successful card scan events in an email. |
| INT emailScanFail | 1.3.6.1.4.1.30932.1.10.1.1.8.2.22 | INTEGER | read-write | Enable/Disable notification of failed card scan events in an email. |
| INT emailDoorState | 1.3.6.1.4.1.30932.1.10.1.1.8.2.23 | INTEGER | read-write | Enable/Disable notification of Door Open/Close events in an email. |
| INT emailLockState | 1.3.6.1.4.1.30932.1.10.1.1.8.2.24 | INTEGER | read-write | Enable/Disable notification of Lock Open/Close events in an email. |
| INT emailExtendedOpen | 1.3.6.1.4.1.30932.1.10.1.1.8.2.25 | INTEGER | read-write | Enable/Disable notification of extended door open events in an email. |
| INT emailFirmareUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.2.26 | INTEGER | read-write | Enable/Disable notification of Firmare Update events in an email. |
| INT emailConfigUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.2.27 | INTEGER | read-write | Enable/Disable notification of configuration change events in an email. |
| INT emailRecepChange | 1.3.6.1.4.1.30932.1.10.1.1.8.2.28 | INTEGER | read-write | Enable/Disable notification of receptacle change events in an email. |
| INT emailSystem | 1.3.6.1.4.1.30932.1.10.1.1.8.2.29 | INTEGER | read-write | Enable/Disable notification of system events in an email. |
| INT emailPduAccess | 1.3.6.1.4.1.30932.1.10.1.1.8.2.30 | INTEGER | read-write | Enable/Disable notification of access to PDU events in an email. |
| INT emailSecureArray | 1.3.6.1.4.1.30932.1.10.1.1.8.2.31 | INTEGER | read-write | Enable/Disable notification of SecureArray events in an email. |
| trapRouting | 1.3.6.1.4.1.30932.1.10.1.1.8.3 | |||
| INT trapBranchCritLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.3.1 | INTEGER | read-write | Enable/Disable notification of Critical Low Voltage on the Branch in a trap. |
| INT trapBranchWarnLowVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.3.2 | INTEGER | read-write | Enable/Disable notification of Warning Low Voltage on the Branch in a trap. |
| INT trapBranchWarnHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.3.3 | INTEGER | read-write | Enable/Disable notification of Warning High Voltage on the Branch in a trap. |
| INT trapBranchCritHighVoltage | 1.3.6.1.4.1.30932.1.10.1.1.8.3.4 | INTEGER | read-write | Enable/Disable notification of Critical High Voltage on the Branch in a trap. |
| INT trapBranchCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.5 | INTEGER | read-write | Enable/Disable notification of Critical Low Current on the Branch in a trap. |
| INT trapBranchWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.6 | INTEGER | read-write | Enable/Disable notification of Warning Low Current on the Branch in a trap. |
| INT trapBranchWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.7 | INTEGER | read-write | Enable/Disable notification of Warning High Current on the Branch in a trap. |
| INT trapBranchCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.8 | INTEGER | read-write | Enable/Disable notification of Critical High Current on the Branch in a trap. |
| INT trapOutletCritLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.9 | INTEGER | read-write | Enable/Disable notification of Critical Low Current on the Outlet in a trap. |
| INT trapOutletWarnLowCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.10 | INTEGER | read-write | Enable/Disable notification of Warning Low Current on the Outlet in a trap. |
| INT trapOutletWarnHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.11 | INTEGER | read-write | Enable/Disable notification of Warning High Current on the Outlet in a trap. |
| INT trapOutletCritHighCurrent | 1.3.6.1.4.1.30932.1.10.1.1.8.3.12 | INTEGER | read-write | Enable/Disable notification of Critical High Current in a trap. |
| INT trapTempCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.3.13 | INTEGER | read-write | Enable/Disable notification of Critical Low Temperature in a trap. |
| INT trapTempWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.3.14 | INTEGER | read-write | Enable/Disable notification of Warning Low Temperature in a trap. |
| INT trapTempWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.3.15 | INTEGER | read-write | Enable/Disable notification of Warning High Temperature in a trap. |
| INT trapTempCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.3.16 | INTEGER | read-write | Enable/Disable notification of Critical High Temperature in a trap. |
| INT trapHumidCritLow | 1.3.6.1.4.1.30932.1.10.1.1.8.3.17 | INTEGER | read-write | Enable/Disable notification of Critical Low Humidity in a trap. |
| INT trapHumidWarnLow | 1.3.6.1.4.1.30932.1.10.1.1.8.3.18 | INTEGER | read-write | Enable/Disable notification of Warning Low Humidity in a trap. |
| INT trapHumidWarnHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.3.19 | INTEGER | read-write | Enable/Disable notification of Warning High Humidity in a trap. |
| INT trapHumidCritHigh | 1.3.6.1.4.1.30932.1.10.1.1.8.3.20 | INTEGER | read-write | Enable/Disable notification of Critical High Humidity in a trap. |
| INT trapScanPass | 1.3.6.1.4.1.30932.1.10.1.1.8.3.21 | INTEGER | read-write | Enable/Disable notification of successful card ID scans in a trap. |
| INT trapScanFail | 1.3.6.1.4.1.30932.1.10.1.1.8.3.22 | INTEGER | read-write | Enable/Disable notification of failed card ID scans in a trap. |
| INT trapDoorState | 1.3.6.1.4.1.30932.1.10.1.1.8.3.23 | INTEGER | read-write | Enable/Disable notification of Door Open/Closed events in a trap. |
| INT trapLockState | 1.3.6.1.4.1.30932.1.10.1.1.8.3.24 | INTEGER | read-write | Enable/Disable notification of Lock Open/Closed events in a trap. |
| INT trapExtendedOpen | 1.3.6.1.4.1.30932.1.10.1.1.8.3.25 | INTEGER | read-write | Enable/Disable notification of extended door open events in an trap. |
| INT trapFirmareUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.3.26 | INTEGER | read-write | Enable/Disable notification of Firmare Update events in a trap. |
| INT trapConfigUpdate | 1.3.6.1.4.1.30932.1.10.1.1.8.3.27 | INTEGER | read-write | Enable/Disable notification of configuration change events in a trap. |
| INT trapRecepChange | 1.3.6.1.4.1.30932.1.10.1.1.8.3.28 | INTEGER | read-write | Enable/Disable notification of receptacle change events in a trap. |
| INT trapSystem | 1.3.6.1.4.1.30932.1.10.1.1.8.3.29 | INTEGER | read-write | Enable/Disable notification of system events in a trap. |
| INT trapPduAccess | 1.3.6.1.4.1.30932.1.10.1.1.8.3.30 | INTEGER | read-write | Enable/Disable notification of access to PDU events in a trap. |
| INT trapSecureArray | 1.3.6.1.4.1.30932.1.10.1.1.8.3.31 | INTEGER | read-write | Enable/Disable notification of SecureArray events in a trap. |
| systemInfo | 1.3.6.1.4.1.30932.1.10.1.2 | |||
| U32 cpiPduTableCount | 1.3.6.1.4.1.30932.1.10.1.2.1 | Unsigned32 | read-only | Get the number of PDUs being monitored by this PDU. This is the number of entries in the cpiPduTable. |
| cpiPduTable | 1.3.6.1.4.1.30932.1.10.1.2.10 | not-accessible | This table contains a list of PDU entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored. Each row in the table represents a PDU in the daisy chain. This table always contains at least one entry and a maximum of 32 entries. The MAC address is used as an index on the table to allow data collectors to ensure that information can be retrieved for a specific PDU. | |
| cpiPduEntry | 1.3.6.1.4.1.30932.1.10.1.2.10.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU MAC that is globally unique. | |
| MAC cpiPduMac | 1.3.6.1.4.1.30932.1.10.1.2.10.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| STR cpiPduModel | 1.3.6.1.4.1.30932.1.10.1.2.10.1.2 | DisplayString | read-only | Get the model number of the PDU. |
| STR cpiPduName | 1.3.6.1.4.1.30932.1.10.1.2.10.1.3 | DisplayString | read-write | Set or get the user assigned name of the PDU. |
| STR cpiPduDescription | 1.3.6.1.4.1.30932.1.10.1.2.10.1.4 | DisplayString | read-write | Set or get the user assigned description of the PDU. |
| INT cpiPduHasBranchMonitor | 1.3.6.1.4.1.30932.1.10.1.2.10.1.5 | INTEGER | read-only | An indicator if the PDU supports monitoring voltage, and current on branches in the PDU. |
| INT cpiPduHasOutletMonitor | 1.3.6.1.4.1.30932.1.10.1.2.10.1.6 | INTEGER | read-only | An indicator if the PDU supports monitoring current on the individual outlets in the PDU. |
| INT cpiPduHasOutletControl | 1.3.6.1.4.1.30932.1.10.1.2.10.1.7 | INTEGER | read-only | An indicator if the PDU supports control (turn on/off) individual outlets in the PDU. |
| I32 cpiPduNumberBranches | 1.3.6.1.4.1.30932.1.10.1.2.10.1.8 | Integer32 | read-only | Get the number of branches (breakers) in the PDU. |
| I32 cpiPduNumberOutlets | 1.3.6.1.4.1.30932.1.10.1.2.10.1.9 | Integer32 | read-only | Get the number of outlets in the PDU. |
| INT cpiPduOutOfService | 1.3.6.1.4.1.30932.1.10.1.2.10.1.10 | INTEGER | read-write | Set or get whether the PDU is in-service. |
| STR cpiPduVersion | 1.3.6.1.4.1.30932.1.10.1.2.10.1.11 | DisplayString | read-only | Get the firmware version number of the PDU. |
| INT cpiPduUpgrade | 1.3.6.1.4.1.30932.1.10.1.2.10.1.12 | INTEGER | read-only | An indicator if the PDU firmware is being upgraded. |
| INT cpiPduChainRole | 1.3.6.1.4.1.30932.1.10.1.2.10.1.13 | INTEGER | read-write | Get the role of the PDU in a daisy chain. |
| IP cpiPduIp | 1.3.6.1.4.1.30932.1.10.1.2.10.1.14 | IpAddress | read-only | Get IP address of the PDU. |
| STR cpiPduIpv6 | 1.3.6.1.4.1.30932.1.10.1.2.10.1.15 | DisplayString | read-only | Get the IPv6 address of the PDU. |
| I32 cpiPduTotalPower | 1.3.6.1.4.1.30932.1.10.1.2.10.1.16 | Integer32 | read-only | Get the power in volt-amps for the entire PDU. |
| STR cpiPduCabinetId | 1.3.6.1.4.1.30932.1.10.1.2.10.1.17 | DisplayString | read-only | Get/set the name of the cabinet the PDU is in. |
| STR cpiPduSerialNum | 1.3.6.1.4.1.30932.1.10.1.2.10.1.18 | DisplayString | read-only | Get the serial number of the PDU. |
| branch | 1.3.6.1.4.1.30932.1.10.1.3 | |||
| U32 cpiLineTableCount | 1.3.6.1.4.1.30932.1.10.1.3.1 | Unsigned32 | read-only | Get the number of PDU input lines being monitored by this PDU. This is the number of entries in the cpiLineTable and accounts for all input lines in a daisy chain. |
| cpiPduLineTable | 1.3.6.1.4.1.30932.1.10.1.3.10 | not-accessible | This table contains a list of PDU line entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of input lines. Each row in the table represents a PDU line in the daisy chain. The table is indexed based on the corresponding Line Input ID and the source PDU MAC. | |
| cpiPduLineEntry | 1.3.6.1.4.1.30932.1.10.1.3.10.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduLineTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU. | |
| MAC cpiPduLineMac | 1.3.6.1.4.1.30932.1.10.1.3.10.1.1 | MacAddress | read-only | Get the MAC address of the PDU that owns the input line. |
| I32 cpiPduLineId | 1.3.6.1.4.1.30932.1.10.1.3.10.1.2 | Integer32 | read-only | Get the ID of the input line on the PDU. |
| I32 cpiPduLineCurrent | 1.3.6.1.4.1.30932.1.10.1.3.10.1.3 | Integer32 | read-only | Get current draw in 1/100 amp of the line on the PDU. Convert the value by dividing by 100. |
| U32 cpiBranchTableCount | 1.3.6.1.4.1.30932.1.10.1.3.100 | Unsigned32 | read-only | Get the number of PDU branches being monitored by this PDU. This is the number of entries in the cpiPduBranchTable. |
| cpiPduBranchTable | 1.3.6.1.4.1.30932.1.10.1.3.110 | not-accessible | This table contains a list of PDU branch entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of branches per PDU. Each row in the table represents a PDU branch in the daisy chain. The table is indexed based on the corresponding Branch ID and the source PDU MAC. | |
| cpiPduBranchEntry | 1.3.6.1.4.1.30932.1.10.1.3.110.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduBranchTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU. | |
| MAC cpiPduBranchMac | 1.3.6.1.4.1.30932.1.10.1.3.110.1.1 | MacAddress | read-only | Get the MAC address of the PDU that owns the branch. |
| I32 cpiPduBranchId | 1.3.6.1.4.1.30932.1.10.1.3.110.1.2 | Integer32 | read-only | Get the ID of the branch on the owning PDU. |
| I32 cpiPduBranchCurrent | 1.3.6.1.4.1.30932.1.10.1.3.110.1.3 | Integer32 | read-only | Get the current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100. |
| I32 cpiPduBranchMaxCurrent | 1.3.6.1.4.1.30932.1.10.1.3.110.1.4 | Integer32 | read-only | Get the maximum current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100. |
| I32 cpiPduBranchVoltage | 1.3.6.1.4.1.30932.1.10.1.3.110.1.5 | Integer32 | read-only | Get the voltage in 1/10 volts of the branch on the PDU. Convert the value by dividing by 10. |
| I32 cpiPduBranchPower | 1.3.6.1.4.1.30932.1.10.1.3.110.1.6 | Integer32 | read-only | Get the power in volt-amps for the branch. |
| I32 cpiPduBranchPowerFactor | 1.3.6.1.4.1.30932.1.10.1.3.110.1.7 | Integer32 | read-only | Get the power factor for the branch. |
| INT cpiPduBranchStatus | 1.3.6.1.4.1.30932.1.10.1.3.110.1.8 | INTEGER | read-only | Get the alarm status of the branch. |
| C64 cpiPduBranchEnergy | 1.3.6.1.4.1.30932.1.10.1.3.110.1.9 | Counter64 | read-only | Get the branch energy accumulated in decaVA-secs, divide by 360 to obtain VA-hr. |
| cpiPduBranchAlertTable | 1.3.6.1.4.1.30932.1.10.1.3.210 | not-accessible | This table contains a list of PDU branch alert entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of branches per PDU. Each row in the table represents a PDU branch in the daisy chain. The table is indexed based on the corresponding Branch ID and the source PDU MAC. | |
| cpiPduBranchAlertEntry | 1.3.6.1.4.1.30932.1.10.1.3.210.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduBranchAlertTable'. Each column represents an alert attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU. | |
| MAC cpiPduBranchAlertMac | 1.3.6.1.4.1.30932.1.10.1.3.210.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| I32 cpiPduBranchAlertBranchId | 1.3.6.1.4.1.30932.1.10.1.3.210.1.2 | Integer32 | read-only | Get the branch ID on the PDU. |
| I32 cpiPduBranchAlertWarnLoCurrent | 1.3.6.1.4.1.30932.1.10.1.3.210.1.3 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers a warning condition. Convert the value by dividing by 100. |
| I32 cpiPduBranchAlertWarnHiCurrent | 1.3.6.1.4.1.30932.1.10.1.3.210.1.4 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers a warning condition. Convert the value by dividing by 100. |
| I32 cpiPduBranchAlertLoCurrent | 1.3.6.1.4.1.30932.1.10.1.3.210.1.5 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
| I32 cpiPduBranchAlertHiCurrent | 1.3.6.1.4.1.30932.1.10.1.3.210.1.6 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
| I32 cpiPduBranchAlertCriticalCurrent | 1.3.6.1.4.1.30932.1.10.1.3.210.1.7 | Integer32 | read-write | Set or get the critical current draw in 1/100 amp of the branch on the PDU. Convert the value by dividing by 100. |
| I32 cpiPduBranchAlertWarnLoVolt | 1.3.6.1.4.1.30932.1.10.1.3.210.1.8 | Integer32 | read-write | Set or get the minimum voltage that the branch can reach up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
| I32 cpiPduBranchAlertWarnHiVolt | 1.3.6.1.4.1.30932.1.10.1.3.210.1.9 | Integer32 | read-write | Set or get the maximum voltage that the branch can reach up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
| I32 cpiPduBranchAlertLoVolt | 1.3.6.1.4.1.30932.1.10.1.3.210.1.10 | Integer32 | read-write | Set or get the minimum voltage that the branch can reach up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
| I32 cpiPduBranchAlertHiVolt | 1.3.6.1.4.1.30932.1.10.1.3.210.1.11 | Integer32 | read-write | Set or get the maximum voltage that the branch can reach up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10. |
| U32 cpiPduBranchAlertIndex | 1.3.6.1.4.1.30932.1.10.1.3.210.1.12 | Unsigned32 | read-only | Index for branch aler |
| U32 cpiPduBranchAlertEntryCpiPduBranchAlertIndex | 1.3.6.1.4.1.30932.1.10.1.3.210.1.13 | Unsigned32 | read-only | Index for branch alert. |
| outlet | 1.3.6.1.4.1.30932.1.10.1.4 | |||
| U32 cpiOutletTableCount | 1.3.6.1.4.1.30932.1.10.1.4.1 | Unsigned32 | read-only | Get the number of PDU outlets being monitored by this PDU. This is the number of entries in the cpiPduOutletTable. |
| cpiPduOutletTable | 1.3.6.1.4.1.30932.1.10.1.4.10 | not-accessible | This table contains a list of PDU outlet entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of outlets on each PDU. Each row in the table represents a PDU outlet in the daisy chain. The table is indexed based on the corresponding Outlet ID and the source PDU MAC. | |
| cpiPduOutletEntry | 1.3.6.1.4.1.30932.1.10.1.4.10.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduOutletTable'. Each column represents an outlet of a PDU. This table is indexed by the PDU Outlet identifier that is unique within the PDU. | |
| MAC cpiPduOutletMac | 1.3.6.1.4.1.30932.1.10.1.4.10.1.1 | MacAddress | read-only | Get the MAC address of the source PDU. |
| I32 cpiPduOutletId | 1.3.6.1.4.1.30932.1.10.1.4.10.1.2 | Integer32 | read-only | Get the ID of the outlet on the PDU. |
| I32 cpiPduOutletBranchId | 1.3.6.1.4.1.30932.1.10.1.4.10.1.3 | Integer32 | read-only | Get the ID of the branch the outlet is associated with on the PDU. |
| STR cpiPduOutletName | 1.3.6.1.4.1.30932.1.10.1.4.10.1.4 | DisplayString | read-write | Set or get the user supplied name of the outlet on the PDU. |
| STR cpiPduOutletDescription | 1.3.6.1.4.1.30932.1.10.1.4.10.1.5 | DisplayString | read-write | Set or get the user supplied description of the outlet on the PDU. |
| I32 cpiPduOutletCurrent | 1.3.6.1.4.1.30932.1.10.1.4.10.1.6 | Integer32 | read-only | Get the current draw in 1/100 amp of the outlet on the PDU. Convert the value by dividing by 100. |
| I32 cpiPduOutletVoltage | 1.3.6.1.4.1.30932.1.10.1.4.10.1.7 | Integer32 | read-only | Get the voltage in 1/10 volts of the outlet on the PDU. Convert the value by dividing by 10. |
| I32 cpiPduOutletPower | 1.3.6.1.4.1.30932.1.10.1.4.10.1.8 | Integer32 | read-only | The power in Volt-Amps of the outlet on the PDU. |
| INT cpiPduOutletStatus | 1.3.6.1.4.1.30932.1.10.1.4.10.1.9 | INTEGER | read-only | Get the alarm status of the outlet. |
| C64 cpiPduOutletEnergy | 1.3.6.1.4.1.30932.1.10.1.4.10.1.10 | Counter64 | read-only | Get the outlet energy accumulated in decaWatt-secs, divide by 360 to obtain Watt-hr. |
| INT cpiPduOutletControl | 1.3.6.1.4.1.30932.1.10.1.4.10.1.11 | INTEGER | read-write | Set or get power control to the outlet. |
| INT cpiPduOutletReset | 1.3.6.1.4.1.30932.1.10.1.4.10.1.12 | INTEGER | read-write | Set or get reset power to the outlet. |
| cpiPduOutletConfigTable | 1.3.6.1.4.1.30932.1.10.1.4.210 | not-accessible | This table contains a list of PDU outlet configuration entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of outlets per PDU. Each row in the table represents a PDU outlet in the daisy chain. The table is indexed based on the corresponding Outlet ID and the source PDU MAC. | |
| cpiPduOutletConfigEntry | 1.3.6.1.4.1.30932.1.10.1.4.210.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduOutletConfigTable'. Each column represents an configurable attribute of an outlet in the PDU. This table is indexed by the PDU Line identifier that is unique within the PDU. | |
| MAC cpiPduOutletConfigMac | 1.3.6.1.4.1.30932.1.10.1.4.210.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| I32 cpiPduOutletConfigOutletId | 1.3.6.1.4.1.30932.1.10.1.4.210.1.2 | Integer32 | read-only | Get the ID of the outlet on the PDU. |
| I32 cpiPduOutletConfigOnDelay | 1.3.6.1.4.1.30932.1.10.1.4.210.1.3 | Integer32 | read-write | Set or get the outlet power-on delay in seconds. |
| I32 cpiPduOutletConfigResetDelay | 1.3.6.1.4.1.30932.1.10.1.4.210.1.4 | Integer32 | read-write | Set or get the outlet reset delay in seconds. |
| cpiPduOutletAlertTable | 1.3.6.1.4.1.30932.1.10.1.4.310 | not-accessible | This table contains a list of PDU outlet alert entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of PDUs being monitored and the number of outlets per PDU. Each row in the table represents a PDU outlet in the daisy chain. The table is indexed based on the corresponding Outlet ID and the source PDU MAC. | |
| cpiPduOutletAlertEntry | 1.3.6.1.4.1.30932.1.10.1.4.310.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduOutletAlertTable'. Each column represents an alert attribute of a PDU. This table is indexed by the PDU Line identifier that is unique within the PDU. | |
| MAC cpiPduOutletAlertMac | 1.3.6.1.4.1.30932.1.10.1.4.310.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| STR cpiPduOutletAlertOutletId | 1.3.6.1.4.1.30932.1.10.1.4.310.1.2 | DisplayString | read-only | Get the outlet ID on the PDU. |
| I32 cpiPduOutletAlertWarnLoCurrent | 1.3.6.1.4.1.30932.1.10.1.4.310.1.3 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers a warning condition. Convert the value by dividing by 100. |
| I32 cpiPduOutletAlertWarnHiCurrent | 1.3.6.1.4.1.30932.1.10.1.4.310.1.4 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers a warning condition. Convert the value by dividing by 100. |
| I32 cpiPduOutletAlertLoCurrent | 1.3.6.1.4.1.30932.1.10.1.4.310.1.5 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU that triggers an alarm condition. Convert the value by dividing by 100. |
| I32 cpiPduOutletAlertHiCurrent | 1.3.6.1.4.1.30932.1.10.1.4.310.1.6 | Integer32 | read-write | Set or get the current draw in 1/100 amp of the branch on the PDU, that triggers an alarm condition. Convert the value by dividing by 100. |
| I32 cpiPduOutletAlertCriticalCurrent | 1.3.6.1.4.1.30932.1.10.1.4.310.1.7 | Integer32 | read-write | Set or get the critical current draw in 1/100 amp of the outlet on the PDU. Convert the value by dividing by 100. |
| sensors | 1.3.6.1.4.1.30932.1.10.1.5 | |||
| U32 cpiPduSensorCount | 1.3.6.1.4.1.30932.1.10.1.5.1 | Unsigned32 | read-only | Get the number of PDU sensors being monitored by this PDU. This is the number of entries in the cpiPduSensorTable. |
| cpiPduProbeTable | 1.3.6.1.4.1.30932.1.10.1.5.5 | not-accessible | This table contains a list of PDU probes that are being monitored by the PDU. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored and the number of probes attached to the PDUs in the daisy chain. Each row in the table represents a probe in the daisy chain. The table is index based on the corresponding Probe ID and the source PDU MAC. | |
| cpiPduProbeEntry | 1.3.6.1.4.1.30932.1.10.1.5.5.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduProbeTable'. Each column represents an attribute of a PDU probe. This table is indexed by the PDU identifier that is unique within the PDU and the probe ID. | |
| MAC cpiPduProbeMac | 1.3.6.1.4.1.30932.1.10.1.5.5.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| I32 cpiPduProbeId | 1.3.6.1.4.1.30932.1.10.1.5.5.1.2 | Integer32 | read-only | Get the probe ID on the PDU. |
| STR cpiPduProbeName | 1.3.6.1.4.1.30932.1.10.1.5.5.1.3 | DisplayString | read-write | Set or get the user defined name of the probe. |
| cpiPduSensorTable | 1.3.6.1.4.1.30932.1.10.1.5.10 | not-accessible | This table contains a list of PDU sensor entries that are being monitored by the PDU. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored and the number of sensors attached to the PDUs in the daisy chain. Each row in the table represents a sensor in the daisy chain. The table is index based on the corresponding Sensor ID and the source PDU MAC. | |
| cpiPduSensorEntry | 1.3.6.1.4.1.30932.1.10.1.5.10.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduSensorTable'. Each column represents an attribute of a PDU sensor. This table is indexed by the PDU identifier that is unique within the PDU and the sensor ID. | |
| MAC cpiPduSensorMac | 1.3.6.1.4.1.30932.1.10.1.5.10.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| I32 cpiPduSensorId | 1.3.6.1.4.1.30932.1.10.1.5.10.1.2 | Integer32 | read-only | Get the sensor ID on the PDU. |
| STR cpiPduSensorName | 1.3.6.1.4.1.30932.1.10.1.5.10.1.3 | DisplayString | read-only | Set or get the user defined name of the sensor. |
| INT cpiPduSensorType | 1.3.6.1.4.1.30932.1.10.1.5.10.1.4 | INTEGER | read-only | Get the type of sensor for the entry. |
| I32 cpiPduSensorValue | 1.3.6.1.4.1.30932.1.10.1.5.10.1.5 | Integer32 | read-only | Get the value of the sensor. For temperature the value is in degrees Fahrenheit and for humidity the value is percent humidity. |
| cpiPduSensorAlertTable | 1.3.6.1.4.1.30932.1.10.1.5.110 | not-accessible | This table contains a list of PDU sensor alert entries that are being monitored by the PDU. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored and the number of sensors attached to the PDUs in the daisy chain. Each row in the table represents a sensor in the daisy chain. The table is index based on the corresponding Sonsor ID and the source PDU MAC. | |
| cpiPduSensorAlertEntry | 1.3.6.1.4.1.30932.1.10.1.5.110.1 | not-accessible | This entry defines the columns to be populated in the 'cpiPduSensorAlertTable'. Each column represents an attribute of a PDU sensor alert. This table is indexed by the PDU identifier that is unique within the PDU. | |
| MAC cpiPduSensorAlertMac | 1.3.6.1.4.1.30932.1.10.1.5.110.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| I32 cpiPduSensorAlertSensorId | 1.3.6.1.4.1.30932.1.10.1.5.110.1.2 | Integer32 | read-only | Get the id of the sensor. |
| I32 cpiPduSensorAlertWarnMin | 1.3.6.1.4.1.30932.1.10.1.5.110.1.3 | Integer32 | read-write | Set or get the minimum warning value of the sensor. |
| I32 cpiPduSensorAlertWarnMax | 1.3.6.1.4.1.30932.1.10.1.5.110.1.4 | Integer32 | read-write | Set or get the maximum warning value of the sensor. |
| I32 cpiPduSensorAlertMin | 1.3.6.1.4.1.30932.1.10.1.5.110.1.5 | Integer32 | read-write | Set or get the minimum alarm value of the sensor. |
| I32 cpiPduSensorAlertMax | 1.3.6.1.4.1.30932.1.10.1.5.110.1.6 | Integer32 | read-write | Set or get the maximum alarm value of the sensor. |
| group | 1.3.6.1.4.1.30932.1.10.1.6 | |||
| U32 cpiPduGroupCount | 1.3.6.1.4.1.30932.1.10.1.6.1 | Unsigned32 | read-only | Get the number of supported groups by the PDU. Value from 0 to 16. |
| U32 cpiPduGroupOutletCount | 1.3.6.1.4.1.30932.1.10.1.6.2 | Unsigned32 | read-only | Get the number of outlets in the Group Outlet Table. |
| cpiGroupTable | 1.3.6.1.4.1.30932.1.10.1.6.10 | not-accessible | This table contains a list of PDU group entries that are being monitored by the PDU. The table contains one, or many rows, depending upon the number of groups that have been configured. Each row in the table represents a group. | |
| cpiGroupEntry | 1.3.6.1.4.1.30932.1.10.1.6.10.1 | not-accessible | This entry defines the columns to be populated in the 'cpiGroupTable'. This table is indexed by the group identifier that is unique within the PDU. | |
| U32 cpiGroupEntryIndex | 1.3.6.1.4.1.30932.1.10.1.6.10.1.1 | Unsigned32 | read-only | This is the index that indicates the row of the 'cpiPduTable'. |
| STR cpiGroupName | 1.3.6.1.4.1.30932.1.10.1.6.10.1.2 | DisplayString | read-write | Name for GROUP 1 of receptacles. |
| cpiGroupOutletTable | 1.3.6.1.4.1.30932.1.10.1.6.20 | not-accessible | This table contains a list of PDU group entries. The table contains zero, one, or many rows, depending upon the number of groups that have been configured. Each row in the table represents a group. | |
| cpiGroupOutletEntry | 1.3.6.1.4.1.30932.1.10.1.6.20.1 | not-accessible | This entry defines the columns to be populated in the 'cpiGroupTable'. This table is indexed by the group identifier that is unique within the PDU. | |
| U32 cpiGroupOutletEntryIndex | 1.3.6.1.4.1.30932.1.10.1.6.20.1.1 | Unsigned32 | read-only | This is the index that indicates the row of the 'cpiGroupOutletTable'. |
| U32 cpiGroupOutletGroupID | 1.3.6.1.4.1.30932.1.10.1.6.20.1.2 | Unsigned32 | read-only | Name for GROUP 1 of receptacles. |
| MAC cpiGroupOutletPDUMac | 1.3.6.1.4.1.30932.1.10.1.6.20.1.3 | MacAddress | read-write | MAC of PDU the outlet is on. |
| I32 cpiGroupOutletOutletId | 1.3.6.1.4.1.30932.1.10.1.6.20.1.4 | Integer32 | read-write | The ID of the outlet on the PDU. |
| easData | 1.3.6.1.4.1.30932.1.10.1.7 | |||
| U32 cpiEasCount | 1.3.6.1.4.1.30932.1.10.1.7.1 | Unsigned32 | read-only | Get the number of locks connected to the PDU. This includes the PDUs on the daisy chain. |
| cpiEasConfigTable | 1.3.6.1.4.1.30932.1.10.1.7.90 | not-accessible | This table contains a list of electronic locks that are connected to the PDU and allows for the configuration of the various settings associated with the EAS (electronic access system). The table contains zero, one, or many rows, depending upon the number of PDUs being monitored and the number of locks attached to the PDUs in the daisy chain. Each row in the table represents a lock in the daisy chain. The table is index based on the corresponding lock ID and the source PDU MAC. | |
| cpiEasConfigEntry | 1.3.6.1.4.1.30932.1.10.1.7.90.1 | not-accessible | This entry defines the columns to be populated in the 'cpiEasTable'. Each column represents an attribute of a PDU lock. This table is indexed by the PDU identifier that is unique within the PDU and the lock ID. | |
| MAC cpiEasConfigLockMac | 1.3.6.1.4.1.30932.1.10.1.7.90.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| INT cpiEasConfigEnabled | 1.3.6.1.4.1.30932.1.10.1.7.90.1.2 | INTEGER | read-only | Indicates whether the Electronic Access System (EAS) is available on the PDU. |
| INT cpiEasFrontLockEnabled | 1.3.6.1.4.1.30932.1.10.1.7.90.1.3 | INTEGER | read-write | Enables the front lock on the EAS. |
| INT cpiEasRearLockEnabled | 1.3.6.1.4.1.30932.1.10.1.7.90.1.4 | INTEGER | read-write | Enables the rear lock on the EAS. |
| INT cpiEasLockHoldOpenTime | 1.3.6.1.4.1.30932.1.10.1.7.90.1.5 | INTEGER | read-write | The length of time in seconds to hold open the lock after a successful card scan. |
| INT cpiEasDoorOpenAlarmTime | 1.3.6.1.4.1.30932.1.10.1.7.90.1.6 | INTEGER | read-write | The length of time in minutes before alerting that the door is open. |
| cpiEasTable | 1.3.6.1.4.1.30932.1.10.1.7.100 | not-accessible | This table contains a list of electronic locks that are connected to the PDU The table contains zero, one, or many rows, depending upon the number of PDUs being monitored and the number of locks attached to the PDUs in the daisy chain. Each row in the table represents a lock in the daisy chain. The table is index based on the corresponding lock ID and the source PDU MAC. | |
| cpiEasEntry | 1.3.6.1.4.1.30932.1.10.1.7.100.1 | not-accessible | This entry defines the columns to be populated in the 'cpiEasTable'. Each column represents an attribute of a PDU lock. This table is indexed by the PDU identifier that is unique within the PDU and the lock ID. | |
| MAC cpiPduLockMac | 1.3.6.1.4.1.30932.1.10.1.7.100.1.1 | MacAddress | read-only | Get the MAC address of the PDU. |
| INT cpiPduLockId | 1.3.6.1.4.1.30932.1.10.1.7.100.1.2 | INTEGER | read-only | Get the lock ID on the PDU. |
| INT cpiPduEasStatus | 1.3.6.1.4.1.30932.1.10.1.7.100.1.3 | INTEGER | read-only | Indicates if the Electronic Access Control system is ready, inactive, or in an error state. If the status is Inactive, then the lock is not enabled on the PDU. If the status is Error, then the cpiEasError field will have an error code to help diagnose the issue. If the status is Ready, then the lock at the door is enabled and ready. |
| INT cpiPduDoorStatus | 1.3.6.1.4.1.30932.1.10.1.7.100.1.4 | INTEGER | read-only | Indicates if the door sensor is closed or open. |
| INT cpiPduLockStatus | 1.3.6.1.4.1.30932.1.10.1.7.100.1.5 | INTEGER | read-only | Indicates if the lock is closed or open. |
| INT cpiPduForceStatus | 1.3.6.1.4.1.30932.1.10.1.7.100.1.6 | INTEGER | read-only | Indicates if the cabinet was forced open by a command from the webUI or SNMP interfaces. |
| INT cpiPduTamperStatus | 1.3.6.1.4.1.30932.1.10.1.7.100.1.7 | INTEGER | read-only | Indicates if the cabinet is currently unlocked/opened without an authorization scan. |
| U32 cpiEasError | 1.3.6.1.4.1.30932.1.10.1.7.100.1.8 | Unsigned32 | read-only | Gets the error code associated for the electronic lock system. The possible error codes are: 196608 (0x00030000 ) - No error, the lock is working and ready. 167968771 (0x0a030003 ) - The lock is not enabled. Enable the lock through the cpiEasConfigTable. 167837698 (0x0a010002 ) - The lock is not responding. Ensure that the lock is connected to the PDU, and is recieving power. Try to disable and re-enable the lock in the cpiEasConfigTable. |
| STR cpiEasLockVer | 1.3.6.1.4.1.30932.1.10.1.7.100.1.9 | DisplayString | read-only | Gets the version of the electronic lock control. |
| STR cpiEasLockSerialNumber | 1.3.6.1.4.1.30932.1.10.1.7.100.1.10 | DisplayString | read-only | Get the serial number of the electronic lock control. |
| INT cpiPduLockCtrl | 1.3.6.1.4.1.30932.1.10.1.7.100.1.11 | INTEGER | read-write | Tells the system to open the locks on the cabinet. |
| traps | 1.3.6.1.4.1.30932.1.10.1.500 | |||
| trapInformation | 1.3.6.1.4.1.30932.1.10.1.500.0 | |||
| STR trapInfoUserName | 1.3.6.1.4.1.30932.1.10.1.500.0.1 | DisplayString | not-accessible | The user Id associated with the action. |
| STR trapInfoCardId | 1.3.6.1.4.1.30932.1.10.1.500.0.2 | DisplayString | not-accessible | The card Id associated with the action. |
| STR trapInfoConfigName | 1.3.6.1.4.1.30932.1.10.1.500.0.3 | DisplayString | not-accessible | The configuration value that was changed. |
| INT trapInfoInterface | 1.3.6.1.4.1.30932.1.10.1.500.0.4 | INTEGER | not-accessible | An identifier for the affected interface. |
| OID trapInfoVarId | 1.3.6.1.4.1.30932.1.10.1.500.0.5 | OBJECT IDENTIFIER | not-accessible | An identifier for the value that was changed. |
| INT trapInfoBootType | 1.3.6.1.4.1.30932.1.10.1.500.0.6 | INTEGER | not-accessible | Indicates that type of boot up occurring. A Cold boot is done from a complete power off. A Warm boot was not a loss in power, but just a reboot of the control module. |
| I32 trapInfoProgress | 1.3.6.1.4.1.30932.1.10.1.500.0.7 | Integer32 | not-accessible | Indicates the percent complete of an operation. |
| INT trapInfoResult | 1.3.6.1.4.1.30932.1.10.1.500.0.8 | INTEGER | not-accessible | Indicates the result of an operation. |
| INT trapInfoErrorCode | 1.3.6.1.4.1.30932.1.10.1.500.0.9 | INTEGER | not-accessible | Indicates the error code of an operation. See the operation for details. Firmware Update Operation Error Codes: 151060481 - Error: Insufficient space available on the PDU to complete the operation. 151060482 - Error: Too many packets were lost in the transfer process. Please try the operation again. 151060483 - Error: The firmware file is corrupted and can not be used. 151060484 - Error: There was a failure in writing the firmware data out to internal memory. 151060485 - Error: The firmware file could not be opened and processed correctly. 151060489 - Error: A unknown failure occured while performing a firmware upgrade. 151060490 - Info: A firmware update is in progress. No issue currently. 151191558 - Info: A firmware upgrade has completed and does not need to reboot. 151191559 - Info: A firmware upgrade has compelted and will reboot. 151191560 - Info: A firmware upgrade has compelted and it was not needed. PDU will not reboot. |
| STR trapInfoGroupName | 1.3.6.1.4.1.30932.1.10.1.500.0.10 | DisplayString | not-accessible | The user group Id associated with the action. |
| systemNotifications | 1.3.6.1.4.1.30932.1.10.1.500.1 | |||
| NTF systemConfigChangeAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.1 | Notification that a configuration value was changed on the PDU. | ||
| NTF systemBootAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.2 | Notification that a PDU is booting up. | ||
| NTF systemFWUpdateStartAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.3 | Notification that a firmware update has been initiated. | ||
| NTF systemFWUpdateStatusAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.4 | Notification that about the progress of the firmware update. | ||
| NTF systemFWUpdateCompleteAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.5 | Notification that about the progress of the firmware update. | ||
| NTF systemSecureArrayFailoverAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.6 | Notification that the SecureArray is being managed by the identified PDU. | ||
| NTF systemSecureArrayDisconnectAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.7 | Notification that the specified PDU disconnected from the SecureArray. | ||
| NTF systemSecureArrayConnectAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.8 | Notification that the specified PDU connected to the SecureArray. | ||
| NTF systemConfigCertAlert | 1.3.6.1.4.1.30932.1.10.1.500.1.9 | Notification that the HTTPS certificate was changed on the PDU. | ||
| userNotifications | 1.3.6.1.4.1.30932.1.10.1.500.2 | |||
| NTF userLoginAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.1 | Notification that a user logged onto the PDU. | ||
| NTF userLoginFailAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.2 | Notification that a user failed to log onto the PDU. | ||
| NTF userAddAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.3 | Notification that a user was added to the PDU. | ||
| NTF userDeleteAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.4 | Notification that a user was deleted from the PDU. | ||
| NTF userModifiedAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.5 | Notification that a user was modified on the PDU. | ||
| NTF userGroupAddAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.6 | Notification that a user group was added to the PDU. | ||
| NTF userGroupDeleteAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.7 | Notification that a user group was deleted from the PDU. | ||
| NTF userGroupModifyAlert | 1.3.6.1.4.1.30932.1.10.1.500.2.8 | Notification that a user group was modified on the PDU. | ||
| inletNotifications | 1.3.6.1.4.1.30932.1.10.1.500.3 | |||
| branchNotifications | 1.3.6.1.4.1.30932.1.10.1.500.4 | |||
| outletNotifications | 1.3.6.1.4.1.30932.1.10.1.500.5 | |||
| NTF outletStateChangeAlert | 1.3.6.1.4.1.30932.1.10.1.500.5.1 | The outlet state has changed. | ||
| environNotification | 1.3.6.1.4.1.30932.1.10.1.500.6 | |||
| NTF environMaxTempAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.1 | The temperature sensor reached the Maximum limit. | ||
| NTF environMinTempAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.2 | The temperature sensor reached the minimum limit. | ||
| NTF environMaxHumidAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.3 | The humidity sensor reached the maximum limit. | ||
| NTF environMinHumidAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.4 | The humidity sensor reached the maximum limit. | ||
| NTF environMaxWarnTempAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.5 | The temperature sensor reached the Maximum limit. | ||
| NTF environMinWarnTempAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.6 | The temperature sensor reached the minimum limit. | ||
| NTF environMaxWarnHumidAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.7 | The humidity sensor reached the maximum limit. | ||
| NTF environMinWarnHumidAlert | 1.3.6.1.4.1.30932.1.10.1.500.6.8 | The humidity sensor reached the maximum limit. | ||
| easNotification | 1.3.6.1.4.1.30932.1.10.1.500.7 | |||
| NTF easScanPassAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.1 | A card was scanned and the associated user was authenticated and authorized to access the cabinet. | ||
| NTF easScanFailAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.2 | A card was scanned but was not authenticated or authorized to access the cabinet. | ||
| NTF easDoorOpenAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.3 | Notification that a door was opened. | ||
| NTF easDoorCloseAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.4 | Notification that a door was closed. | ||
| NTF easLockOpenAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.5 | Notification that a lock was opened. | ||
| NTF easLockCloseAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.6 | Notification that a lock was closed. | ||
| NTF easDoorExtOpenAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.7 | Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. | ||
| NTF easDoorExtOpenClearAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.8 | Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. | ||
| NTF easForceUnlockAlert | 1.3.6.1.4.1.30932.1.10.1.500.7.9 | Notification that a door was open for longer that the time set in cpiEasDoorOpenAlarmTime setting. | ||
| mibconformance | 1.3.6.1.4.1.30932.1.10.1.600 |
RFC description
Chatsworth eConnect unified MIB for power distribution units providing system information and monitoring.
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.