CPI-UNITY-MIB :: alarmsMinMap

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › alarmsMinMap

alarmsMinMap

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::alarmsMinMap

OID (numeric): 1.3.6.1.4.1.30932.1.1.3.10.2

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: Min threshold alarmed state bitmap: bit0=currA, bit1=currB, bit2=currC ... bit6=voltA, bit7=voltB, bit8=voltC ... bit12=temperature1, bit13=temperature2, bit14=humidity1, bit15=humidity2

What is alarmsMinMap?

This read-only Integer32 is a bitmap where each bit flags whether a specific measured channel has dropped below its minimum (critical low) threshold, with bit assignments given directly in the description: bit0-2 for the three current phases (currA/B/C), bit6-8 for the three voltage phases (voltA/B/C), bit12-13 for the two temperature probes, and bit14-15 for the two humidity probes. An admin reads this single value instead of polling every individual sensor to instantly see which class of measurement has breached its lower critical limit, then drills into the specific probe or phase. For example, if alarmsMinMap has bit7 set, the admin knows voltB has sagged under its minimum threshold, which could indicate a failing input feed on that phase.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.3.10.2
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::alarmsMinMap

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.3.10.2.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::alarmsMinMap.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> alarmsMinMap.1

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::alarmsMinMap OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.3metricsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.3.10alarmsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.3.10.2alarmsMinMapCPI-UNITY-MIB