CPI-UNITY-MIB :: xy1WarnLoVolt

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › xy1WarnLoVolt

xy1WarnLoVolt

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::xy1WarnLoVolt

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.27.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Warning Low voltage in volts that XY1 can sag before triggering notifications, 0=ignore.

What is xy1WarnLoVolt?

This read-write integer, expressed directly in volts (0-3120) with 0 meaning the limit is disabled, sets the voltage that the X-Y phase-pair of circuit 1 can sag to before the PDU triggers a warning notification, ahead of the harder xy1MinVolt brownout limit. This lets an administrator catch a gradually weakening feed on circuit 1's X-Y leg early, before it drops far enough to hit the stricter minimum-voltage alarm. For instance, setting xy1WarnLoVolt to 200 volts warns when X-Y sags below 200V, ahead of a 190V xy1MinVolt alarm.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.27.1
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::xy1WarnLoVolt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.27.1.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::xy1WarnLoVolt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.27.1.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::xy1WarnLoVolt OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.27warnLoVoltageLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.27.1xy1WarnLoVoltCPI-UNITY-MIB