All MIBs › CPI-UNITY-MIB › outlet19Current
outlet19Current
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet19Current
OID (numeric): 1.3.6.1.4.1.30932.1.1.3.5.19
Node type: OBJECT-TYPE
Type: Integer32
Access: read-only
Description: Outlet19 current draw in 1/100 Amps.
What is outlet19Current?
This is a read-only Integer32 value from 0 to 2000 giving the live current draw on Outlet19 in units of 1/100 Amp, as stated directly in the object's description. An administrator watches this per-outlet reading to see exactly how much load a rack PDU downstream from this one plugged into Outlet19 is pulling, so a spike can be caught before it trips a shared breaker. For example, a raw reading of 390 on outlet19Current means Outlet19 is drawing 3.90 Amps at that moment, letting the admin confirm it is within the PDU's rated per-outlet limit.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.3.5.19 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet19Current
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.3.5.19.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet19Current.1
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet19Current OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.3 | metrics | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.3.5 | receptacleCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.3.5.19 | outlet19Current | CPI-UNITY-MIB |