All MIBs › CPI-UNITY-MIB › outlet16WarnHiCurr
outlet16WarnHiCurr
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet16WarnHiCurr
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.30.16
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Outlet16 warning high current in 1/100 Amps.
What is outlet16WarnHiCurr?
This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets an early warning current level for outlet 16, set below its harder outlet16MaxCurr ceiling. Reaching this level lets an administrator see the device on outlet 16 trending toward an overload and act, for example by moving a load to another outlet, before the stricter maximum is tripped. For instance, setting outlet16WarnHiCurr to 450 (4.50A) would raise an early warning on outlet 16 before its draw reaches a 5.00A outlet16MaxCurr limit.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.30.16 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet16WarnHiCurr
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.30.16.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet16WarnHiCurr.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.30.16.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet16WarnHiCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.30 | receptacleWarnHiCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.30.16 | outlet16WarnHiCurr | CPI-UNITY-MIB |