outlet1WarnLoCurr

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::outlet1WarnLoCurr

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.31.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Outlet1 warning low current in 1/100 Amps.

What is outlet1WarnLoCurr?

This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets an early warning level for unexpectedly low current draw on outlet 1, set above its harder outlet1MinCurr floor. This gives an administrator advance notice that the device on outlet 1 is drawing less power than usual, which can be an early sign of a partial fault before the load disappears entirely. For example, setting outlet1WarnLoCurr to 40 (0.40A) would warn on outlet 1 once its draw dips under 0.4 amps, ahead of any 0.2A outlet1MinCurr alarm.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.1
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet1WarnLoCurr

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.1.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet1WarnLoCurr.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.31.1.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet1WarnLoCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.31receptacleWarnLoCurrentCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.31.1outlet1WarnLoCurrCPI-UNITY-MIB