All MIBs › CPI-UNITY-MIB › outlet13WarnLoCurr
outlet13WarnLoCurr
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet13WarnLoCurr
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.31.13
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Outlet13 warning low current in 1/100 Amps.
What is outlet13WarnLoCurr?
This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets an early warning level for unexpectedly low current draw on outlet 13, set above its harder outlet13MinCurr floor. This gives an administrator advance notice that the device on outlet 13 is drawing less power than usual, which can be an early sign of a partial fault before the load disappears entirely. For example, setting outlet13WarnLoCurr to 40 (0.40A) would warn on outlet 13 once its draw dips under 0.4 amps, ahead of any 0.2A outlet13MinCurr alarm.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.13 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet13WarnLoCurr
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.13.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet13WarnLoCurr.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.31.13.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet13WarnLoCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.31 | receptacleWarnLoCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.31.13 | outlet13WarnLoCurr | CPI-UNITY-MIB |