All MIBs › CPI-UNITY-MIB › minTempProbe1
minTempProbe1
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::minTempProbe1
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.33.1
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Minimum temperature for Probe 1 in 1/100 of degrees Fahrenheit, 0=ignore.
What is minTempProbe1?
This read-write integer, in hundredths of a degree Fahrenheit (0-20000, i.e. up to 200.00F) with 0 meaning the limit is disabled, sets the lowest temperature reading allowed from temperature Probe 1 attached to this PDU. A reading below this floor from Probe 1 can indicate a cooling malfunction, an open door letting in cold air, or an HVAC fault affecting the equipment near that probe. For instance, setting minTempProbe1 to 3200 (32.00F) would alarm if Probe 1 ever reads at or below freezing.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.33.1 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::minTempProbe1
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.33.1.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::minTempProbe1.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.33.1.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::minTempProbe1 OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.33 | minTempLimits | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.33.1 | minTempProbe1 | CPI-UNITY-MIB |