All MIBs › CPI-UNITY-MIB › outlet3MaxCurr
outlet3MaxCurr
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet3MaxCurr
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.28.3
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Outlet3 maximum current in 1/100 Amps.
What is outlet3MaxCurr?
This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets the maximum current outlet 3 specifically is allowed to draw, independent of the phase-level MaxCurr limits covering the whole circuit. Because it is scoped to outlet 3 alone, it lets an administrator catch a single overloaded device plugged into that outlet even when the branch circuit as a whole is still within its own limits. For example, setting outlet3MaxCurr to 500 (5.00A) means the PDU flags outlet 3 the instant whatever is plugged into it draws more than 5 amps.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.28.3 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet3MaxCurr
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.28.3.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet3MaxCurr.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.28.3.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet3MaxCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.28 | receptacleMaxCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.28.3 | outlet3MaxCurr | CPI-UNITY-MIB |