All MIBs › CPI-UNITY-MIB › yz2MinVolt
yz2MinVolt
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::yz2MinVolt
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.25.5
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Minimum voltage that YZ2 can sag in volts, 0=ignore.
What is yz2MinVolt?
This read-write integer, expressed directly in volts (0-3120) with 0 meaning the limit is disabled, sets the lowest voltage the Y-Z phase-pair of circuit 2 can sag to before the PDU treats it as a brownout condition. Detecting a sag on Y-Z lets an administrator catch an unstable utility feed or failing upstream transformer affecting circuit 2 before connected equipment starts misbehaving from low voltage. For instance, setting yz2MinVolt to 190 volts flags circuit 2's Y-Z leg the moment it sags below 190V.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.25.5 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::yz2MinVolt
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.25.5.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::yz2MinVolt.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.25.5.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::yz2MinVolt OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.25 | minVoltageLimits | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.25.5 | yz2MinVolt | CPI-UNITY-MIB |