CPI-UNITY-MIB :: yz2WarnHiVolt

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › yz2WarnHiVolt

yz2WarnHiVolt

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::yz2WarnHiVolt

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.26.5

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Warning High voltage in volts that YZ2 can reach before triggering warning notifications, 0=ignore.

What is yz2WarnHiVolt?

This read-write integer, expressed directly in volts (0-3120) with 0 meaning the limit is disabled, sets the voltage that the Y-Z phase-pair of circuit 2 can reach before the PDU triggers a warning notification, distinct from the harder yz2MaxVolt overvoltage limit. This earlier warning lets staff investigate a rising voltage trend on circuit 2's Y-Z leg while it is still a minor deviation rather than a full overvoltage event. For example, setting yz2WarnHiVolt to 240 volts would send a warning notification on Y-Z well before it reaches a 250V yz2MaxVolt cutoff.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.26.5
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::yz2WarnHiVolt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.26.5.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::yz2WarnHiVolt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.26.5.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::yz2WarnHiVolt OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.26warnHiVoltageLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.26.5yz2WarnHiVoltCPI-UNITY-MIB