All MIBs › CPI-UNITY-MIB › outlet17MinCurr
outlet17MinCurr
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet17MinCurr
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.29.17
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Outlet17 minimum current in 1/100 Amps.
What is outlet17MinCurr?
This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets the minimum current outlet 17 is expected to draw when its connected device is operating normally. A reading below this floor on outlet 17 can mean the plugged-in device has powered itself off, been unplugged, or failed, a change that would otherwise be invisible unless someone physically checked the outlet. For example, setting outlet17MinCurr to 20 (0.20A) lets the PDU flag outlet 17 if its draw drops under 0.2 amps, suggesting the device it powers has gone idle or offline.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.29.17 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet17MinCurr
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.29.17.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet17MinCurr.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.29.17.1 i <value>
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet17MinCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.29 | receptacleMinCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.29.17 | outlet17MinCurr | CPI-UNITY-MIB |