CPI-UNITY-MIB :: warnLoHumidProbe1

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › warnLoHumidProbe1

warnLoHumidProbe1

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::warnLoHumidProbe1

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.39.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Warning Low humidity for Probe 1 in 1/100 of %, 0=ignore.

What is warnLoHumidProbe1?

This read-write integer, in hundredths of a percent (0-10000, i.e. up to 100.00%) with 0 meaning the limit is disabled, sets the humidity at which Probe 1 triggers an early low-humidity warning, set above the harder minHumidProbe1 alarm floor. This gives staff advance notice that air near Probe 1 is getting too dry, raising static-discharge risk, before it reaches the stricter minimum-humidity alarm. For instance, setting warnLoHumidProbe1 to 3000 (30.00%) would warn on Probe 1 before it drops to a 20.00% minHumidProbe1 alarm.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.39.1
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::warnLoHumidProbe1

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.39.1.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::warnLoHumidProbe1.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.39.1.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::warnLoHumidProbe1 OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.39warnLoHumidityLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.39.1warnLoHumidProbe1CPI-UNITY-MIB