CPI-UNITY-MIB :: warnLoTempProbe2

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › warnLoTempProbe2

warnLoTempProbe2

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::warnLoTempProbe2

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.35.2

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Warning Low temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.

What is warnLoTempProbe2?

This read-write integer, in hundredths of a degree Fahrenheit (0-20000, i.e. up to 200.00F) with 0 meaning the limit is disabled, sets the temperature at which Probe 2 triggers an early low-temperature warning, set above the harder minTempProbe2 alarm floor. This gives staff advance notice that conditions near Probe 2 are getting unusually cold, which can signal an HVAC problem before it reaches the stricter minimum-temperature alarm. For instance, setting warnLoTempProbe2 to 4000 (40.00F) would warn on Probe 2 before it drops to a 32.00F minTempProbe2 alarm.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.35.2
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::warnLoTempProbe2

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.35.2.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::warnLoTempProbe2.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.35.2.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::warnLoTempProbe2 OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.35warnLoTempLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.35.2warnLoTempProbe2CPI-UNITY-MIB