CPI-UNITY-MIB :: maxHumidProbe1

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › maxHumidProbe1

maxHumidProbe1

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::maxHumidProbe1

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.36.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Maximum humidity for Probe 1 in 1/100 of %, 0=ignore.

What is maxHumidProbe1?

This read-write integer, in hundredths of a percent (0-10000, i.e. up to 100.00%) with 0 meaning the limit is disabled, sets the highest relative humidity reading allowed from humidity Probe 1 attached to this PDU. Excess humidity near Probe 1 raises the risk of condensation and corrosion on the equipment the PDU powers, so this ceiling lets an administrator catch that condition early. For example, setting maxHumidProbe1 to 8000 (80.00%) flags an alarm as soon as Probe 1 reads above 80 percent relative humidity.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.36.1
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::maxHumidProbe1

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.36.1.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::maxHumidProbe1.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.36.1.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::maxHumidProbe1 OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.36maxHumidityLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.36.1maxHumidProbe1CPI-UNITY-MIB