All MIBs › CPI-UNITY-MIB › outlet20WarnLoCurr
outlet20WarnLoCurr
Module: CPI-UNITY-MIB
OID (symbolic): CPI-UNITY-MIB::outlet20WarnLoCurr
OID (numeric): 1.3.6.1.4.1.30932.1.1.2.31.20
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Outlet20 warning low current in 1/100 Amps.
What is outlet20WarnLoCurr?
This read-write integer, in hundredths of an amp (0-2000, i.e. up to 20.00A), sets an early warning level for unexpectedly low current draw on outlet 20, set above its harder outlet20MinCurr floor. This gives an administrator advance notice that the device on outlet 20 is drawing less power than usual, which can be an early sign of a partial fault before the load disappears entirely. For example, setting outlet20WarnLoCurr to 40 (0.40A) would warn on outlet 20 once its draw dips under 0.4 amps, ahead of any 0.2A outlet20MinCurr alarm.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.20 snmpwalk -v2c -c public <target> CPI-UNITY-MIB::outlet20WarnLoCurr
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.31.20.1 snmpget -v2c -c public <target> CPI-UNITY-MIB::outlet20WarnLoCurr.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.31.20.1 i <value>
SNMPv3 example:
snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> outlet20WarnLoCurr.1
Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::outlet20WarnLoCurr OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.30932 | cpi | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1 | products | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1 | cpiPDU | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2 | configuration | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.31 | receptacleWarnLoCurrent | CPI-UNITY-MIB |
| 1.3.6.1.4.1.30932.1.1.2.31.20 | outlet20WarnLoCurr | CPI-UNITY-MIB |