CPI-UNITY-MIB :: cpiPduBranchAlertHiVolt

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › cpiPduBranchAlertHiVolt

cpiPduBranchAlertHiVolt

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::cpiPduBranchAlertHiVolt

OID (numeric): 1.3.6.1.4.1.30932.1.10.1.3.210.1.11

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Set or get the maximum voltage that the branch can reach up to in 1/10th volts, 0=ignore. Convert the value by dividing by 10.

What is cpiPduBranchAlertHiVolt?

This read-write Integer32 sets the maximum voltage, in 1/10 volt units, that a branch can reach before triggering a more severe alarm condition; a value of 0 disables this check. An admin sets this higher than the warning-high threshold so it only fires for a genuinely dangerous overvoltage condition that could damage connected equipment. For example, setting this to 1400 (140.0 volts) marks a more severe spike than the warning-high threshold would catch.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.10.1.3.210.1.11
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::cpiPduBranchAlertHiVolt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.10.1.3.210.1.11.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::cpiPduBranchAlertHiVolt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.10.1.3.210.1.11.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::cpiPduBranchAlertHiVolt OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10unityCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10.1econnectCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10.1.3branchCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10.1.3.210cpiPduBranchAlertTableCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10.1.3.210.1cpiPduBranchAlertEntryCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.10.1.3.210.1.11cpiPduBranchAlertHiVoltCPI-UNITY-MIB