CPI-UNITY-MIB :: warnHiTempProbe2

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › CPI-UNITY-MIB › warnHiTempProbe2

warnHiTempProbe2

Module: CPI-UNITY-MIB

OID (symbolic): CPI-UNITY-MIB::warnHiTempProbe2

OID (numeric): 1.3.6.1.4.1.30932.1.1.2.34.2

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Warning High temperature for Probe 2 in 1/100 of degrees Fahrenheit, 0=ignore.

What is warnHiTempProbe2?

This read-write integer, in hundredths of a degree Fahrenheit (0-20000, i.e. up to 200.00F) with 0 meaning the limit is disabled, sets the temperature at which Probe 2 triggers an early high-temperature warning, set below the harder maxTempProbe2 alarm ceiling. This lets staff notice a rack near Probe 2 starting to run hot and respond, for example by checking airflow, before the stricter maximum-temperature alarm fires. For example, setting warnHiTempProbe2 to 8500 (85.00F) would warn on Probe 2 before it reaches a 90.00F maxTempProbe2 alarm.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.34.2
snmpwalk -v2c -c public <target> CPI-UNITY-MIB::warnHiTempProbe2

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.30932.1.1.2.34.2.1
snmpget -v2c -c public <target> CPI-UNITY-MIB::warnHiTempProbe2.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.30932.1.1.2.34.2.1 i <value>

Start monitoring Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPI-UNITY-MIB::warnHiTempProbe2 OID value, configure state conditions and alerts, and monitor any Chatsworth Products (CPI) eConnect rack PDU/cabinet management unit from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.30932cpiCPI-UNITY-MIB
1.3.6.1.4.1.30932.1productsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1cpiPDUCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2configurationCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.34warnHiTempLimitsCPI-UNITY-MIB
1.3.6.1.4.1.30932.1.1.2.34.2warnHiTempProbe2CPI-UNITY-MIB