All MIBs › WIENER-CRATE-MIB
Organization: W-IE-NE-R Power Electronics GmbH
Last Updated: 2019-04-03
Category: Power and Environmental Monitoring
Description: Monitors W-IE-NE-R Power Electronics VME/NIM crate power supply voltage, current, temperature, and fault conditions.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is WIENER-CRATE-MIB?
WIENER-CRATE-MIB is a MIB from W-IE-NE-R Power Electronics for their VME/NIM crate power supply mainframes (widely used in nuclear/particle-physics instrumentation), providing management of crate control and diagnostics. It exposes system-level control and status objects covering main switch control, overall system status, reset operations, and low-level debug memory access, alongside its documented focus on voltage, current, temperature and fault monitoring for crate power channels. It is squarely a hardware-status monitoring MIB: sysStatus reports overall crate health, sysMainSwitch and sysVmeSysReset/sysHardwareReset provide power/reset control, sysOperatingTime tracks device uptime, and the broader crate module (per its short description) tracks output voltage, current, temperature, and fault conditions of the power supply channels. It is a self-contained vendor module (part of the "communication.can" branch, implying CAN-bus based communication) without heavy reliance on standard IETF MIBs. It is typically deployed in physics laboratory and industrial instrumentation racks where WIENER crate power supplies back NIM/VME electronics. Engineers can download the WIENER-CRATE-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in WIENER-CRATE-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- W-IE-NE-R VME/NIM crate power supply mainframe
Monitoring Examples
An administrator would poll sysStatus and sysOperatingTime to confirm the crate mainframe is running normally and to track uptime since last reset, and use sysMainSwitch to check whether the crate's main power is enabled. The sysConfigDoMeasurementCurrent object indicates whether current measurement is active for monitoring load draw on the crate, while sysDebugMemory8/16/32 provide low-level diagnostic memory reads useful for firmware troubleshooting. A sysStatus fault flag or an unexpected sysHardwareReset/sysFactoryDefaults event would reveal the crate has experienced a fault or been reset, potentially disrupting the connected instrumentation modules.
What Can Be Monitored
- crate operational status
- main power switch state
- system uptime
- current measurement configuration
- reset/fault events
- output voltage/current/temperature per channel
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-SMI
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| OBJECT-IDENTITY | |
| OBJECT-TYPE | |
| Opaque | |
| enterprises |
From SNMPv2-TC
| DisplayString | |
| MacAddress | |
| TEXTUAL-CONVENTION |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| wiener | 1.3.6.1.4.1.19947 | Introduction of the communication.can branch. | ||
| crate | 1.3.6.1.4.1.19947.1 | SNMP control for electronic crates. A crate is a complete electronic system and consists of the mechanical rack, a power supply, a fan tray and a backplane. All this things are necessary to provide an adequate housing for electronic modules (e.g. VME CPU's) | ||
| system | 1.3.6.1.4.1.19947.1.1 | A collection of objects which affect the complete crate | ||
| INT sysMainSwitch | 1.3.6.1.4.1.19947.1.1.1 | INTEGER | read-write | Read: An enumerated value which shows the current state of the crates main switch. Write: Try to switch the complete crate ON or OFF. Only the values ON or OFF are allowed. |
| BIT sysStatus | 1.3.6.1.4.1.19947.1.1.2 | Bits | read-only | A bit string which shows the status (health) of the complete crate. If a bit is set (1), the explanation is satisfied mainOn (0), system is switched on, individual outputs may be controlled by their specific ON/INHIBIT mainInhibit(1), external (hardware-)inhibit of the complete system localControlOnly (2), local control only (CANBUS write access denied) inputFailure (3), any input failure (e.g. power fail) outputFailure (4), any output failure, details in outputTable fantrayFailure (5), fantray failure sensorFailure (6), temperature of the external sensors too high vmeSysfail(7), VME SYSFAIL signal is active plugAndPlayIncompatible (8) wrong power supply and rack connected busReset (9) The sytem bus (e.g. VME or CPCI) reset signal is active. supplyDerating (10) The (first) system power supply has the DEG signal active. supplyFailure (11) The (first) system power supply has the FAL signal active. supplyDerating2 (12) The second system power supply has the DEG signal active. supplyFailure2 (13) The second system power supply has the FAL signal active. |
| INT sysVmeSysReset | 1.3.6.1.4.1.19947.1.1.3 | INTEGER | read-write | Read: Always 0. Write: Trigger the generation of the VME SYSRESET or CPIC RESET signal. This signal will be active for a time of 200 ms |
| I32 sysHardwareReset | 1.3.6.1.4.1.19947.1.1.4 | Integer32 | read-write | Triggered a Reset via Watchdog or ResetLine. |
| INT sysFactoryDefaults | 1.3.6.1.4.1.19947.1.1.5 | INTEGER | read-write | A set operation performs a complete factory reset of ALL data stored in the controller (e.g. community names, passwords, ...). |
| BIT sysConfigDoMeasurementCurrent | 1.3.6.1.4.1.19947.1.1.10 | Bits | read-write | CSet the analog inputs to measure voltage or current. |
| I32 sysOperatingTime | 1.3.6.1.4.1.19947.1.1.11 | Integer32 | read-write | The time in seconds for how long the controller was in action. |
| I32 sysDebugMemory8 | 1.3.6.1.4.1.19947.1.1.1024 | Integer32 | read-write | Debug 16-bit memory access. |
| I32 sysDebugMemory16 | 1.3.6.1.4.1.19947.1.1.1025 | Integer32 | read-write | Debug 16-bit memory access. |
| I32 sysDebugMemory32 | 1.3.6.1.4.1.19947.1.1.1026 | Integer32 | read-write | Debug 32-bit memory access. |
| OCT sysDebug | 1.3.6.1.4.1.19947.1.1.1027 | OCTET STRING | read-write | Debug communication with the MPOD. This is a direct map to the ancient functions which are accessible via USB (without SLIP/SNMP). |
| OCT sysDebugDisplay | 1.3.6.1.4.1.19947.1.1.1028 | OCTET STRING | read-write | Debug communication with the MPOD display. |
| OCT sysDebugBoot | 1.3.6.1.4.1.19947.1.1.1029 | OCTET STRING | read-write | Debug communication with the simple debug interface / bootloader. |
| input | 1.3.6.1.4.1.19947.1.2 | All objects which are associated with the power input of the crate | ||
| output | 1.3.6.1.4.1.19947.1.3 | All objects which are associated with the power output of the crate | ||
| I32 outputNumber | 1.3.6.1.4.1.19947.1.3.1 | Integer32 | read-only | The number of output channels of the crate. |
| outputTable | 1.3.6.1.4.1.19947.1.3.2 | not-accessible | A list of output entries. | |
| outputEntry | 1.3.6.1.4.1.19947.1.3.2.1 | not-accessible | A table row | |
| INT outputIndex | 1.3.6.1.4.1.19947.1.3.2.1.1 | INTEGER | not-accessible | A unique number for each power output channel. Its value ranges between 1 and total number of output channels. This value is equivalent to the output channel number at the type label of the crate or power supply, but because the SMI index starts at 1, index 1 corresponds to U0. |
| STR outputName | 1.3.6.1.4.1.19947.1.3.2.1.2 | DisplayString | read-only | A textual string containing a short name of the output. If the crate is equipped with an alphanumeric display, this string is shown to identify a output channel. |
| I32 outputGroup | 1.3.6.1.4.1.19947.1.3.2.1.3 | Integer32 | read-write | The group number (1...63) assigned to each channel. If commands shall be sent to all channels with a specific group number (e.g. with the groupsSwitch command defined below), additional bits can be added to the group number: HLgggggg g: Group number (1...63) L: Mask bit: 1: high voltage channels only, no low voltage channels H: Mask bit: 1: low voltage channels only, no high voltage channels Special groups: 0: all (LV+HV) channels 0x40: all, but no LV channels 0x80: all, but no HV channels |
| BIT outputStatus | 1.3.6.1.4.1.19947.1.3.2.1.4 | Bits | read-only | A bit string which shows the status (health and operating conditions) of one output channel. If a bit is set (1), the explanation is satisfied: outputOn (0), output channel is on outputInhibit(1), external (hardware-)inhibit of the output channel outputFailureMinSenseVoltage (2) Supervision limit hurt: Sense voltage is too low outputFailureMaxSenseVoltage (3), Supervision limit hurt: Sense voltage is too high outputFailureMaxTerminalVoltage (4), Supervision limit hurt: Terminal voltage is too high outputFailureMaxCurrent (5), Supervision limit hurt: Current is too high outputFailureMaxTemperature (6), Supervision limit hurt: Heat sink temperature is too high outputFailureMaxPower (7), Supervision limit hurt: Output power is too high outputFailureTimeout (9), Communication timeout between output channel and main control outputCurrentLimited (10), Current limiting is active (constant current mode) outputRampUp (11), Output voltage is increasing (e.g. after switch on) outputRampDown (12), Output voltage is decreasing (e.g. after switch off) outputEnableKill (13), EnableKill is active outputEmergencyOff (14), EmergencyOff event is active outputAdjusting (15), Fine adjustment is working outputConstantVoltage (16), Voltage control (constant voltage mode) outputLowCurrentRange (17), The channel is operating in the low current measurement range outputCurrentBoundsExceeded (18), Output current is out of bounds outputFailureCurrentLimit (19) Hardware current limit (EHS) / trip (EDS, EBS) was exceeded |
| FLO outputMeasurementSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.5 | Float | read-only | The measured voltage at the sense input lines. |
| FLO outputMeasurementTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.6 | Float | read-only | The measured voltage at the output terminals. |
| FLO outputMeasurementCurrent | 1.3.6.1.4.1.19947.1.3.2.1.7 | Float | read-only | The measured output current. |
| INT outputMeasurementTemperature | 1.3.6.1.4.1.19947.1.3.2.1.8 | INTEGER | read-only | The measured temperature of the power module. |
| INT outputSwitch | 1.3.6.1.4.1.19947.1.3.2.1.9 | INTEGER | read-write | Read: An enumerated value which shows the current state of the output channel. Write: Change the state of the channel. If the channel is On, and the write value is Off, then the channel will switch Off. If the channel is Off, and the write value is On, and if no other signals (mainInhibit, outputInhibit, outputEmergencyOff or outputFailureMaxCurrent) are active, then the channel will switch on. If the write value is resetEmergencyOff, then the channel will leave the state EmergencyOff. A write of clearEvents is necessary before the voltage can ramp up again. If the write value is setEmergencyOff, then the channel will have the state EmergencyOff, which means that the High Voltage will switch off without a ramp and reset of the outputVoltage to null volt. If the write value is clearEvents, then all failure messages of the outputStatus will be reset (all channel events, all module events and the state emergencyOff). |
| FLO outputVoltage | 1.3.6.1.4.1.19947.1.3.2.1.10 | Float | read-write | The nominal output voltage of the channel. |
| I32 outputAdjustVoltage | 1.3.6.1.4.1.19947.1.3.2.1.11 | Integer32 | read-write | A posibillity to make small changes of the output voltage. |
| FLO outputCurrent | 1.3.6.1.4.1.19947.1.3.2.1.12 | Float | read-write | The current limit of the channel. |
| FLO outputVoltageRiseRate | 1.3.6.1.4.1.19947.1.3.2.1.13 | Float | read-write | Voltage Fall Slew Rate [V/s]. The slew rate of the output voltage if it increases (after switch on or if the Voltage has been changed). |
| FLO outputVoltageFallRate | 1.3.6.1.4.1.19947.1.3.2.1.14 | Float | read-write | Voltage Rise Slew Rate [V/s]. The slew rate of the output voltage if it decreases (after switch off or if the Voltage has been changed). |
| I32 outputSupervisionBehavior | 1.3.6.1.4.1.19947.1.3.2.1.15 | Integer32 | read-write | A bit field packed into an integer which define the behavior of the output channel / power supply after failures. For each supervision value, a two-bit field exists. The enumeration of this value (..L+..H*2) is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate. iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. The position of the bit fields in the integer value are: Bit 0, 1: outputFailureMinSenseVoltage Bit 2, 3: outputFailureMaxSenseVoltage Bit 4, 5: outputFailureMaxTerminalVoltage Bit 6, 7: outputFailureMaxCurrent Bit 8, 9: outputFailureMaxTemperature Bit 10, 11: outputFailureMaxPower Bit 12, 13: outputFailureInhibit Bit 14, 15: outputFailureTimeout |
| FLO outputSupervisionMinSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.16 | Float | read-write | If the measured sense voltage is below this value, the power supply performs the function defined by SupervisionAction. |
| FLO outputSupervisionMaxSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.17 | Float | read-write | If the measured sense voltage is above this value, the power supply performs the function defined by SupervisionAction. |
| FLO outputSupervisionMaxTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.18 | Float | read-write | If the measured voltage at the power supply output terminals is above this value, the power supply performs the function defined by SupervisionAction. |
| FLO outputSupervisionMaxCurrent | 1.3.6.1.4.1.19947.1.3.2.1.19 | Float | read-write | If the measured current is above this value, the power supply performs the function defined by SupervisionAction. |
| I32 outputSupervisionMaxTemperature | 1.3.6.1.4.1.19947.1.3.2.1.20 | Integer32 | read-write | If the measured module temperature is above this value, the power supply performs the function defined by SupervisionAction. |
| FLO outputConfigMaxSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.21 | Float | read-write | The maximum possible value of the sense voltage |
| FLO outputConfigMaxTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.22 | Float | read-write | The maximum possible value of the terminal voltage |
| FLO outputConfigMaxCurrent | 1.3.6.1.4.1.19947.1.3.2.1.23 | Float | read-write | The maximum possible value of the output current |
| FLO outputSupervisionMaxPower | 1.3.6.1.4.1.19947.1.3.2.1.24 | Float | read-write | If the measured power (measured current * measured terminal voltage) is above this value, the power supply performs the function defined by SupervisionAction. |
| FLO outputCurrentRiseRate | 1.3.6.1.4.1.19947.1.3.2.1.25 | Float | read-write | Current Fall Slew Rate [A/s]. The slew rate of the output current if it increases (after switch on or if the Current has been changed). |
| FLO outputCurrentFallRate | 1.3.6.1.4.1.19947.1.3.2.1.26 | Float | read-write | Current Rise Slew Rate [A/s]. The slew rate of the output current if it decreases (after switch off or if the Current has been changed). |
| OUT outputTripTimeMaxCurrent | 1.3.6.1.4.1.19947.1.3.2.1.27 | OutputTripTime | read-write | Minimum time the outputSupervisionMaxCurrent threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior (bit field outputFailureMaxCurrent) or the new outputTripActionMaxCurrent. |
| FLO outputHardwareLimitVoltage | 1.3.6.1.4.1.19947.1.3.2.1.28 | Float | read-only | Hardware Voltage Limit [V]. Potentiometer to adjust the global hardware voltage limit (for all channels of a module). |
| FLO outputHardwareLimitCurrent | 1.3.6.1.4.1.19947.1.3.2.1.29 | Float | read-only | Hardware Current Limit [A]. Potentiometer to adjust the global hardware current limit (for all channels of a module). |
| FLO outputConfigGainSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.30 | Float | read-write | The gain value of the sense voltage |
| FLO outputConfigOffsetSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.31 | Float | read-write | The offset value of the sense voltage |
| FLO outputConfigGainTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.32 | Float | read-write | The gain value of the sense voltage |
| FLO outputConfigOffsetTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.33 | Float | read-write | The offset value of the sense voltage |
| FLO outputConfigGainCurrent | 1.3.6.1.4.1.19947.1.3.2.1.34 | Float | read-write | The gain value of the sense voltage |
| FLO outputConfigOffsetCurrent | 1.3.6.1.4.1.19947.1.3.2.1.35 | Float | read-write | The offset value of the sense voltage |
| I32 outputUserConfig | 1.3.6.1.4.1.19947.1.3.2.1.37 | Integer32 | read-write | Definition of user-changeable items. A bit field packed into an integer which define the behavior of the output channel. Usable for WIENER LV devices only. The position of the bit fields in the integer value are: Bit 0: Voltage ramping at switch off: 0: Ramp down at switch off. 1: No ramp at switch off (immediate off) Bit 1, 2: Set different regulation modes, dependent on the cable inductance: 0: fast: short cables, up to 1 meter. 1: moderate: cables from 1 to 30 meter. 2: fast: identical to 0 (should not be used) 3: slow: cables longer than 30 meter. Bit 3: Internal sense line connection to the output (MPOD only): 0: The sense input at the sense connector is used for regulation. 1: The output voltage is used for regulation. Any signals at the sense connector are ignored. Bit 4: Enable External Inhibit input. 0: The external inhibit input is ignored. 1: The external inhibit input must be connected to a voltage source to allow switch on. Bit 5: Disable Global Inhibit inputs. 0: The global inhibit/interlock inputs of the system is active. 1: The global inhibit/interlock inputs of the system is ignored. Bit 6: Automatic Power On. 0: After switching the main system switch ON, the output is not switched on automatically. A separate outputSwitch command is required. 1: After switching the main system switch ON, the output is switched on automatically. If 'Disable Global Inhibit' (bit 5) is set, the output will be switched on regardless of the global inhibit/interlock signals. Community required for write access: guru. |
| INT outputRegulationMode | 1.3.6.1.4.1.19947.1.3.2.1.38 | INTEGER | read-write | Definition of the regulation mode. Deprecated, use outputUserConfig for this function in the future! It is possible to set different regulation modes, dependent on the cable inductance. fast: short cables, up to 1 meter. moderate: cables from 1 to 30 meter. slow: cables longer than 30 meter. Community required for write access: guru. |
| I32 outputConfigMaxTemperature | 1.3.6.1.4.1.19947.1.3.2.1.39 | Integer32 | read-write | The maximum possible value of outputSupervisionMaxTemperature. |
| FLO outputResistance | 1.3.6.1.4.1.19947.1.3.2.1.40 | Float | read-write | Item to specify an external resistor. For instance a wire resistor or an external resistor to protect the detectot which is supplied by a cascaded HV module. |
| OUT outputTripTimeMinSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.41 | OutputTripTime | read-write | Minimum time the outputSupervisionMinSenseVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionMinSenseVoltage. |
| OUT outputTripTimeMaxSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.42 | OutputTripTime | read-write | Minimum time the outputSupervisionMaxSenseVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionMaxSenseVoltage. |
| OUT outputTripTimeMaxTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.43 | OutputTripTime | read-write | Minimum time the outputSupervisionMaxTerminalVoltage threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionMaxTerminalVoltage. |
| OUT outputTripTimeMaxTemperature | 1.3.6.1.4.1.19947.1.3.2.1.44 | OutputTripTime | read-write | Minimum time the outputSupervisionMaxTemperature threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionMaxTemperature. |
| OUT outputTripTimeMaxPower | 1.3.6.1.4.1.19947.1.3.2.1.45 | OutputTripTime | read-write | Minimum time the outputSupervisionMaxPower threshold must be violated to activate the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionMaxPower. |
| OUT outputTripTimeTimeout | 1.3.6.1.4.1.19947.1.3.2.1.46 | OutputTripTime | read-write | Maximum time the communication between module and controller can paused before activation the trip action [ms]. The trip action is defined in outputSupervisionBehavior or the new outputTripActionTimeout. |
| OUT outputTripActionMinSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.47 | OutputTripAction | read-write | Trip action if outputSuperisionMinSenseVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 0..1 of outputSupervisionBehavior. |
| OUT outputTripActionMaxSenseVoltage | 1.3.6.1.4.1.19947.1.3.2.1.48 | OutputTripAction | read-write | Trip action if outputSuperisionMaxSenseVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 2..3 of outputSupervisionBehavior. |
| OUT outputTripActionMaxTerminalVoltage | 1.3.6.1.4.1.19947.1.3.2.1.49 | OutputTripAction | read-write | Trip action if outputSuperisionMaxTerminalVoltage threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 4..5 of outputSupervisionBehavior. |
| OUT outputTripActionMaxCurrent | 1.3.6.1.4.1.19947.1.3.2.1.50 | OutputTripAction | read-write | Trip action if outputSuperisionMaxCurrent threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate. iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 6..7 of outputSupervisionBehavior. |
| OUT outputTripActionMaxTemperature | 1.3.6.1.4.1.19947.1.3.2.1.51 | OutputTripAction | read-write | Trip action if outputSuperisionMaxTemperature threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 8..9 of outputSupervisionBehavior. |
| OUT outputTripActionMaxPower | 1.3.6.1.4.1.19947.1.3.2.1.52 | OutputTripAction | read-write | Trip action if outputSuperisionMaxPower threshold has been violated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 10..11 of outputSupervisionBehavior. |
| OUT outputTripActionExternalInhibit | 1.3.6.1.4.1.19947.1.3.2.1.53 | OutputTripAction | read-write | Trip action if the external inhibit input has been activated. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 12..13 of outputSupervisionBehavior. |
| OUT outputTripActionTimeout | 1.3.6.1.4.1.19947.1.3.2.1.54 | OutputTripAction | read-write | Trip action if the communication between module and controller has been paused longer than outputTripTimeTimeout. The enumerated value is: WIENER LV devices 0 ignore the failure 1 switch off this channel 2 switch off all channels with the same group number 3 switch off the complete crate iseg HV devices 0 ignore the failure 1 switch off this channel by ramp down the voltage 2 switch off this channel by a emergencyOff 3 switch off the whole board of the HV module by emergencyOff. This is a direct access of bits 14..15 of outputSupervisionBehavior. |
| OCT outputConfigDataS | 1.3.6.1.4.1.19947.1.3.2.1.1024 | OCTET STRING | read-write | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system software only and my not be accessed directly. snmpget: undefined behavior snmpset: OCTET STRING format for reading data (8 octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit OCTET STRING format used for writing data, or returned from the SNMP client after read/write (8+n octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit data numberOfOctets octets |
| OCT outputConfigDataU | 1.3.6.1.4.1.19947.1.3.2.1.1025 | OCTET STRING | read-write | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system software only and my not be accessed directly. snmpget: undefined behavior snmpset: OCTET STRING format for reading data (8 octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit OCTET STRING format returned from the SNMP client, or used for writing data (8+n octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit data numberOfOctets octets |
| I32 groupsNumber | 1.3.6.1.4.1.19947.1.3.3 | Integer32 | read-only | The number of output groups of the crate. |
| groupsTable | 1.3.6.1.4.1.19947.1.3.4 | not-accessible | A list of output groups entries. | |
| groupsEntry | 1.3.6.1.4.1.19947.1.3.4.1 | not-accessible | A table row | |
| I32 groupsIndex | 1.3.6.1.4.1.19947.1.3.4.1.1 | Integer32 | not-accessible | A unique number for each power output group. Its value ranges between 1 and 1999. The special group 0 is predefined and gives access to all channels. |
| INT groupsSwitch | 1.3.6.1.4.1.19947.1.3.4.1.9 | INTEGER | read-write | Read: This function is not defined with groups of output channels. Write: Switch the state of all channels of a group. If any channel is On, and the write value is Off, then all channels will switch off. If any channel is Off, and the write value is On, and if no other signals (mainInhibit, outputInhibit, outputEmergencyOff or outputFailureMaxCurrent) are active, then all channels will switch on. If the write value is resetEmergencyOff, then all channels will leave the state EmergencyOff. A write of clearEvents is necessary before the voltage can ramp up again. If the write value is setEmergencyOff, then all channels will have the state EmergencyOff, which means that the High Voltage will switch off without a ramp and reset of the outputVoltage to null volt. If the write value is disableKILL, then all channels will switch to disableKill (outputStatus outputDisableKill). If the write value is enableKILL, then all channels will switch to enableKill (outputStatus outputEnableKill). If the write value is clearEvents, then all failure messages of the outputStatus will be cleared (all channel events, all module events and the state outputEmergencyOff will be reset). For a detailed description of the different group numbers available look at the outputGroup OID above. |
| I32 moduleNumber | 1.3.6.1.4.1.19947.1.3.5 | Integer32 | read-only | The number of HV/LV modules of the crate. |
| moduleTable | 1.3.6.1.4.1.19947.1.3.6 | not-accessible | A list of output module entries. | |
| moduleEntry | 1.3.6.1.4.1.19947.1.3.6.1 | not-accessible | A row in the table of HV/LV modules | |
| INT moduleIndex | 1.3.6.1.4.1.19947.1.3.6.1.1 | INTEGER | not-accessible | A unique number for each HV/LV module. Its value ranges between 1 and the total number of HV/LV modules. Note, index 1 corresponds to ma0. |
| OCT moduleDescription | 1.3.6.1.4.1.19947.1.3.6.1.2 | OCTET STRING | read-only | Vendor, FirmwareName, ChannelNumber, SerialNumber, FirmwareRelease Vendor WIENER or iseg FirmwareName: 'E16D0' EDS 16 channels per PCB, distributor module, range of Vmax from VO max to (VO max - 1kV) 'E16D1' EDS 16 channels per PCB, distributor module 'E08C0' EHS 8 channels per PCB, common GND module 'E08F0' EHS 8 channels per PCB, floating GND module 'E08F2' EHS 8 channels per PCB, floating GND module, 2 current measurement ranges 'E08C2' EHS 8 channels per PCB, common floating GND module, 2 current measurement ranges 'E08B0' EBS 8 bipolars channel per PCB, distributor module 'H101C0' HPS 1 channel HV high power supply ChannelNumber 1 to 64 SerialNumber 71xxxx FirmwareRelease x.xx |
| moduleAuxiliaryMeasurementVoltage | 1.3.6.1.4.1.19947.1.3.6.1.3 | The measured module auxiliary voltages. | ||
| FLO moduleAuxiliaryMeasurementVoltage0 | 1.3.6.1.4.1.19947.1.3.6.1.3.1 | Float | read-only | The measured module auxiliary voltage. |
| FLO moduleAuxiliaryMeasurementVoltage1 | 1.3.6.1.4.1.19947.1.3.6.1.3.2 | Float | read-only | The measured module auxiliary voltage. |
| FLO moduleHardwareLimitVoltage | 1.3.6.1.4.1.19947.1.3.6.1.4 | Float | read-only | The module hardware voltage limit. |
| FLO moduleHardwareLimitCurrent | 1.3.6.1.4.1.19947.1.3.6.1.5 | Float | read-only | The module hardware current limit. |
| FLO moduleRampSpeedVoltage | 1.3.6.1.4.1.19947.1.3.6.1.6 | Float | read-write | The module voltage ramp speed (iseg HV modules have the same ramp speed value for all channels). |
| FLO moduleRampSpeedCurrent | 1.3.6.1.4.1.19947.1.3.6.1.7 | Float | read-write | The module current ramp speed (iseg HV modules have the same ramp speed value for all channels). |
| BIT moduleStatus | 1.3.6.1.4.1.19947.1.3.6.1.8 | Bits | read-only | A bit string which shows the current module status. If a bit is set (1), the explanation is satisfied: moduleIsFineAdjustment (0), Module has reached state fine adjustment. moduleIsLiveInsertion (2), Module is in state live insertion. moduleNeedService (4), Hardware failure detected (consult iseg Spezialelektronik GmbH). moduleIsHardwareLimitVoltageGood (5), Hardware limit voltage in proper range, using for HV distributor modules with current mirror only. moduleIsInputError (6), Input error in connection with a module access. moduleIsNoSumError (8), All channels without any failure. moduleIsNoRamp (9), All channels stable, no is ramp active. moduleIsSafetyLoopGood (10), Safety loop is closed. moduleIsEventActive (11), Any event is active and mask is set. moduleIsGood (12), Module state is good. moduleIsSupplyGood (13), Power supply is good. moduleIsTemperatureGood (14), Module temperature is good. moduleIsKillEnable (15) Module state of kill enable. |
| BIT moduleEventStatus | 1.3.6.1.4.1.19947.1.3.6.1.9 | Bits | read-only | A bit string which shows the current module status. If a bit is set (1), the explanation is satisfied: moduleEventPowerFail (0), Event power fail generated by the MPOD controller in order to ramp down all HV's (ramp speed=1000V/s) moduleEventLiveInsertion (2), Event live insertion to prepare a hot plug of a module moduleEventService (4), Module event: Hardware failure detected (consult iseg Spezialelektronik GmbH). moduleHardwareLimitVoltageNotGood (5), Module Event: Hardware voltage limit is not in proper range, using for HV distributor modules with current mirror only. moduleEventInputError (6), Module event: There was an input error in connection with a module access moduleEventSafetyLoopNotGood (10), Module event: Safety loop is open. moduleEventSupplyNotGood (13), Module event: At least one of the supplies is not good. moduleEventTemperatureNotGood (14), Module event: Temperature was above the permitted threshold (for EDS/EHS temperature above 55 degr.C) |
| BIT moduleEventChannelStatus | 1.3.6.1.4.1.19947.1.3.6.1.10 | Bits | read-only | Bit field that reserves one bit for every channel. bit 0 HV channel 0 bit 1 HV channel 1 bit x HV channel x |
| INT moduleDoClear | 1.3.6.1.4.1.19947.1.3.6.1.11 | INTEGER | read-write | All events of the module will be cleared. |
| moduleAuxiliaryMeasurementTemperature | 1.3.6.1.4.1.19947.1.3.6.1.12 | The number of auxiliary temperature sensors in the module. | ||
| FLO moduleAuxiliaryMeasurementTemperature0 | 1.3.6.1.4.1.19947.1.3.6.1.12.1 | Float | read-only | The measured module temperature of sensor 1. |
| FLO moduleAuxiliaryMeasurementTemperature1 | 1.3.6.1.4.1.19947.1.3.6.1.12.2 | Float | read-only | The measured module temperature of sensor 2. |
| FLO moduleAuxiliaryMeasurementTemperature2 | 1.3.6.1.4.1.19947.1.3.6.1.12.3 | Float | read-only | The measured module temperature of sensor 3. |
| FLO moduleAuxiliaryMeasurementTemperature3 | 1.3.6.1.4.1.19947.1.3.6.1.12.4 | Float | read-only | The measured module temperature of sensor 4. |
| OCT moduleConfigDataS | 1.3.6.1.4.1.19947.1.3.6.1.1024 | OCTET STRING | read-write | Configuration Data raw access. This allows to read / write output channel specific system configuration data. This OID is intended for use by WIENER system software only and my not be accessed directly. snmpget: undefined behavior snmpset: OCTET STRING format for reading data (8 octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit OCTET STRING format returned from the SNMP client, or used for writing data (8+n octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit data numberOfOctets octets |
| OCT moduleConfigDataU | 1.3.6.1.4.1.19947.1.3.6.1.1025 | OCTET STRING | read-write | Configuration Data raw access. This allows to read / write output channel specific user configuration data. This OID is intended for use by WIENER system software only and my not be accessed directly. snmpget: undefined behavior snmpset: OCTET STRING format for reading data (8 octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit OCTET STRING format returned from the SNMP client, or used for writing data (8+n octets): offsetInOctets 4 octets / 32 bit numberOfOctets 4 octets / 32 bit data numberOfOctets octets |
| sensor | 1.3.6.1.4.1.19947.1.4 | All objects which are associated with temperature sensors in the crate | ||
| I32 sensorNumber | 1.3.6.1.4.1.19947.1.4.1 | Integer32 | read-only | The number of temperature sensors of the crate. |
| sensorTable | 1.3.6.1.4.1.19947.1.4.2 | not-accessible | A (conceptual table) of temperature sensor data. | |
| sensorEntry | 1.3.6.1.4.1.19947.1.4.2.1 | not-accessible | An entry (conceptual row) of the sensorTable. | |
| INT sensorIndex | 1.3.6.1.4.1.19947.1.4.2.1.1 | INTEGER | not-accessible | A unique number for each temperature sensor in the crate |
| I32 sensorTemperature | 1.3.6.1.4.1.19947.1.4.2.1.2 | Integer32 | read-only | The measured temperature of the sensor. Unused temperature probes have the special value -128 |
| I32 sensorWarningThreshold | 1.3.6.1.4.1.19947.1.4.2.1.3 | Integer32 | read-write | If the measured temperature of the sensor is higher than this value, the fan speed of the connected fan tray is increased. The value 127 has the special meaning: channel disabled. |
| I32 sensorFailureThreshold | 1.3.6.1.4.1.19947.1.4.2.1.4 | Integer32 | read-write | If the measured temperature of the sensor is higher than this value, the power supply switches off. The value 127 has the special meaning: channel disabled. |
| I32 sensorAlarmThreshold | 1.3.6.1.4.1.19947.1.4.2.1.6 | Integer32 | read-write | If the measured temperature of the sensor is much higher than this value, the fans rotate in full speed. The value 127 has the special meaning: channel disabled. |
| STR sensorName | 1.3.6.1.4.1.19947.1.4.2.1.7 | DisplayString | read-write | A textual string containing a short name of the sensor. If the crate is equipped with an alphanumeric display, this string is shown to identify a sensor channel. |
| OCT sensorID | 1.3.6.1.4.1.19947.1.4.2.1.8 | OCTET STRING | read-write | Shows the 1-Wire Id of the corresponding Sensor. |
| I32 sensorStatus | 1.3.6.1.4.1.19947.1.4.2.1.9 | Integer32 | read-only | A bit field packed into an integer which define the Status of the Sensors after failures. For each Status value, a two-bit field exists. Bits-Value 00 Temperature is ok 01 Temperature is over WarningThreshold 10 Temperature is over AlarmThreshold 11 Temperature is over FailureThreshold The position of the bit fields in the integer value are: Bit 0, 1: Sensor1 Bit 2, 3: Sensor2 Bit 4, 5: Sensor3 Bit 6, 7: Sensor4 Bit 8, 9: Sensor5 Bit 10, 11: Sensor6 Bit 12, 13: Sensor7 Bit 14, 15: Sensor8 |
| communication | 1.3.6.1.4.1.19947.1.5 | All objects which affect the remote control of the crate | ||
| snmp | 1.3.6.1.4.1.19947.1.5.1 | SNMP configuration. | ||
| snmpCommunityTable | 1.3.6.1.4.1.19947.1.5.1.1 | not-accessible | The SNMP community string table for different views. | |
| snmpCommunityEntry | 1.3.6.1.4.1.19947.1.5.1.1.1 | not-accessible | One table row. | |
| INT snmpAccessRight | 1.3.6.1.4.1.19947.1.5.1.1.1.1 | INTEGER | not-accessible | A unique number for each access right |
| OCT snmpCommunityName | 1.3.6.1.4.1.19947.1.5.1.1.1.2 | OCTET STRING | read-write | The SNMP community names for different views. The rights of the different communities are: public no write access private can switch power on/off, generate system reset admin can change supervision levels guru can change output voltage & current (this may destroy hardware if done wrong!) Setting a community name to a zero-length string completly disables the access to this view. If there is no higher- privileged community, the community name can only changed by direct access to the crate (not via network)! |
| I32 snmpPort | 1.3.6.1.4.1.19947.1.5.1.2 | Integer32 | read-write | The UDP port number of the SNMP protocol. A value of 0 disables all future SNMP communication! |
| I32 httpPort | 1.3.6.1.4.1.19947.1.5.1.3 | Integer32 | read-write | The TCP port number of the HTTP (web) protocol. A value of 0 disables all HTTP access. |
| OCT firmwareUpdate | 1.3.6.1.4.1.19947.1.5.1.10 | OCTET STRING | read-write | Send a update String |
| IP ipDynamicAddress | 1.3.6.1.4.1.19947.1.5.1.11 | IpAddress | read-only | Shows the Ip which is currently used |
| IP ipStaticAddress | 1.3.6.1.4.1.19947.1.5.1.12 | IpAddress | read-write | Shows the Ip which is setted by user |
| MAC macAddress | 1.3.6.1.4.1.19947.1.5.1.13 | MacAddress | read-write | Shows the MAC of the corresponding device |
| can | 1.3.6.1.4.1.19947.1.5.2 | CAN-Bus tunnel via SNMP. | ||
| I32 canBitRate | 1.3.6.1.4.1.19947.1.5.2.1 | Integer32 | read-write | Control of the CAN-Bus. The value defines the bit rate of the CAN-bus interface. A write disconnects the CAN interface from the ISEG modules and connects it to the SNMP communication. Both the receive and transmit fifos are cleared and the CAN interface is initialized with the selected bit rate. The special bit rate 0 disables the tunnel and switches back to normal operation. |
| OCT canReceive | 1.3.6.1.4.1.19947.1.5.2.2 | OCTET STRING | read-only | Control of the CAN-Bus Receive FIFO. A read access returns the total number of CAN messages stored in the receive fifo and the oldest message. This message is removed from the fifo. The OCTET STRING data is formatted according to the CANviaSNMP structure. |
| OCT canTransmit | 1.3.6.1.4.1.19947.1.5.2.3 | OCTET STRING | read-write | Control of the CAN-Bus Transmit FIFO. A read access returns the total number of CAN messages stored in the transmit fifo and a NULL message. A write inserts the CAN message into the transmit fifo. This message will be transmitted via the CAN interface later. The total number of CAN messages stored in the transmit fifo and the recent message are returned. The OCTET STRING data is formatted according to the CANviaSNMP structure. |
| OCT canReceiveHv | 1.3.6.1.4.1.19947.1.5.2.4 | OCTET STRING | read-only | Control of the internal HV CAN-Bus on the backplane Receive FIFO. A read access returns the total number of CAN messages stored in the receive fifo and the oldest message. This message is removed from the fifo. The OCTET STRING data is formatted according to the CANviaSNMP structure. |
| OCT canTransmitHv | 1.3.6.1.4.1.19947.1.5.2.5 | OCTET STRING | read-write | Control of the internal HV CAN-Bus on the backplane. A write access with: CANID=0x600 DLC=4 DATAID=0x1001 CONTROL will switch the HV modules into a special state. CONTROL=0x0001 - enable SNMP CAN access, stop the refresh cycle for the data points of the name space CONTROL=0x0002 - disable SNMP CAN access, activate the refresh cycle for the data points of the name space A write access unequal to CANID=0x600 will be transmitted to the HV CAN on the backplane. Such a message will be transmitted immediately via the CAN interface. The OCTET STRING data is formatted according to the CANviaSNMP structure. |
| I32 canBitRateHv | 1.3.6.1.4.1.19947.1.5.2.6 | Integer32 | read-write | Control of the bit rate of the HV CAN-Bus. The value defines the bit rate of the CAN-bus interface. Possible Values are 125000 and 250000. Changing this value requires MPODC slave firmware 1.10 or above. |
| powersupply | 1.3.6.1.4.1.19947.1.6 | All objects which are specific for the power supply of the crate | ||
| STR psSerialNumber | 1.3.6.1.4.1.19947.1.6.2 | DisplayString | read-only | The serial number of the power supply. |
| I32 psOperatingTime | 1.3.6.1.4.1.19947.1.6.3 | Integer32 | read-write | The time in seconds for how long the power supply was switched on. |
| I32 psAuxiliaryNumber | 1.3.6.1.4.1.19947.1.6.4 | Integer32 | read-only | The number of auxiliary channels of the power supply. |
| psAuxiliaryTable | 1.3.6.1.4.1.19947.1.6.5 | not-accessible | A list of psAuxiliary entries. | |
| psAuxiliaryEntry | 1.3.6.1.4.1.19947.1.6.5.1 | not-accessible | A table row | |
| INT psAuxiliaryIndex | 1.3.6.1.4.1.19947.1.6.5.1.1 | INTEGER | not-accessible | A unique number for each power supply auxiliary channel. Its value ranges between 1 and total number of output channels. SMI index starts at 1, so index 1 corresponds to U0. |
| FLO psAuxiliaryMeasurementVoltage | 1.3.6.1.4.1.19947.1.6.5.1.3 | Float | read-only | The measured power supply auxiliary output voltage. |
| FLO psAuxiliaryMeasurementCurrent | 1.3.6.1.4.1.19947.1.6.5.1.4 | Float | read-only | The measured power supply auxiliary output current. |
| OCT psDirectAccess | 1.3.6.1.4.1.19947.1.6.1024 | OCTET STRING | read-write | Direct data transfer to the UEP6000 power supply. A read access returns nothing, a write access returns the response of the power supply. |
| fantray | 1.3.6.1.4.1.19947.1.7 | All objects which are specific for the fan tray of the crate | ||
| STR fanSerialNumber | 1.3.6.1.4.1.19947.1.7.2 | DisplayString | read-write | The serial number of the fan tray. |
| I32 fanOperatingTime | 1.3.6.1.4.1.19947.1.7.3 | Integer32 | read-write | The time in seconds for how long the fan tray was switched on. |
| I32 fanAirTemperature | 1.3.6.1.4.1.19947.1.7.4 | Integer32 | read-only | The temperature of the fan tray inlet air. |
| I32 fanSwitchOffDelay | 1.3.6.1.4.1.19947.1.7.5 | Integer32 | read-write | The maximum time in seconds for which the fans will continue running after the power supply has been switched off. This feature is used to cool down the electronics after switching off. |
| I32 fanNominalSpeed | 1.3.6.1.4.1.19947.1.7.6 | Integer32 | read-write | The nominal fan rotation speed (RPM, Revolutions Per Minute) Value 0 does switch off the fans (only allowed if at least one rack temperature sensor is present). Values 1..1199 are not allowed |
| I32 fanNumberOfFans | 1.3.6.1.4.1.19947.1.7.7 | Integer32 | read-write | The number of installed fans |
| fanSpeedTable | 1.3.6.1.4.1.19947.1.7.8 | not-accessible | A list of fanSpeedEntries. | |
| fanSpeedEntry | 1.3.6.1.4.1.19947.1.7.8.1 | not-accessible | A table row | |
| I32 fanNumber | 1.3.6.1.4.1.19947.1.7.8.1.1 | Integer32 | not-accessible | A unique number for each fan. |
| I32 fanSpeed | 1.3.6.1.4.1.19947.1.7.8.1.2 | Integer32 | read-only | The measured fan rotation speed (RPM, Revolutions Per Minute) |
| I32 fanMaxSpeed | 1.3.6.1.4.1.19947.1.7.9 | Integer32 | read-write | The highest allowed rotationspeed of fan. |
| I32 fanMinSpeed | 1.3.6.1.4.1.19947.1.7.10 | Integer32 | read-write | The lowest allowed Rotationspeed of fan. |
| I32 fanConfigMaxSpeed | 1.3.6.1.4.1.19947.1.7.11 | Integer32 | read-write | Hardwarelimits. Can only set by WIENER. |
| I32 fanConfigMinSpeed | 1.3.6.1.4.1.19947.1.7.12 | Integer32 | read-write | Hardwarelimits Can only set by WIENER. |
| rack | 1.3.6.1.4.1.19947.1.8 | All objects which are specific for the crate (BIN) of the crate | ||
| signal | 1.3.6.1.4.1.19947.1.9 | All objects which are associated with analog/digtal input/output in the crate | ||
| I32 numberOfAnalogInputs | 1.3.6.1.4.1.19947.1.9.1 | Integer32 | read-only | The number of additional analog inputs of the crate. |
| analogInputTable | 1.3.6.1.4.1.19947.1.9.2 | not-accessible | A (conceptual table) of analog input data. | |
| analogInputEntry | 1.3.6.1.4.1.19947.1.9.2.1 | not-accessible | An entry (conceptual row) of the analogInputTable. | |
| I32 analogInputIndex | 1.3.6.1.4.1.19947.1.9.2.1.1 | Integer32 | not-accessible | A unique number for each analog input of the crate |
| FLO analogMeasurementVoltage | 1.3.6.1.4.1.19947.1.9.2.1.2 | Float | read-only | The measured voltage of the analog input. |
| FLO analogMeasurementCurrent | 1.3.6.1.4.1.19947.1.9.2.1.3 | Float | read-only | The measured current of the analog input. |
| BIT digitalInput | 1.3.6.1.4.1.19947.1.9.5 | Bits | read-only | The value of the digital inputs. |
| BIT digitalOutput | 1.3.6.1.4.1.19947.1.9.6 | Bits | read-only | The value of the digital outputs. |
RFC description
Wiener CRATE (Compact Reconfigurable Advanced Test Equipment) MIB; manages power supply, timing, and monitoring functions for Wiener test equipment.
Start monitoring W-IE-NE-R VME/NIM crate power supply mainframe (channel voltage/current/temperature/fault status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.