All MIBs › WIENER-CRATE-MIB › outputSwitch
outputSwitch
Module: WIENER-CRATE-MIB
OID (symbolic): WIENER-CRATE-MIB::outputSwitch
OID (numeric): 1.3.6.1.4.1.19947.1.3.2.1.9
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Read: An enumerated value which shows the current state of the output channel.
Write: Change the state of the channel. If the channel is On, and the write value is Off, then the channel will switch Off. If the channel is Off, and the write value is On, and if no other signals (mainInhibit, outputInhibit, outputEmergencyOff or outputFailureMaxCurrent) are active, then the channel will switch on.
If the write value is resetEmergencyOff, then the channel will leave the state EmergencyOff. A write of clearEvents is necessary before the voltage can ramp up again. If the write value is setEmergencyOff, then the channel will have the state EmergencyOff, which means that the High Voltage will switch off without a ramp and reset of the outputVoltage to null volt.
If the write value is clearEvents, then all failure messages of the outputStatus will be reset (all channel events, all module events and the state emergencyOff).
What is outputSwitch?
Reads the channel's current on/off/inhibited state and, on write, controls it -- turning it on or off, clearing latched events, or forcing/resetting an emergency-off -- provided no active inhibit or failure condition is blocking the change, per the source description.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.19947.1.3.2.1.9 snmpwalk -v2c -c public <target> WIENER-CRATE-MIB::outputSwitch
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.19947.1.3.2.1.9.1 snmpget -v2c -c public <target> WIENER-CRATE-MIB::outputSwitch.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.19947.1.3.2.1.9.1 i <value>
Start monitoring W-IE-NE-R VME/NIM crate power supply mainframe (channel voltage/current/temperature/fault status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the WIENER-CRATE-MIB::outputSwitch OID value, configure state conditions and alerts, and monitor any W-IE-NE-R VME/NIM crate power supply mainframe (channel voltage/current/temperature/fault status) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.19947 | wiener | WIENER-CRATE-MIB |
| 1.3.6.1.4.1.19947.1 | crate | WIENER-CRATE-MIB |
| 1.3.6.1.4.1.19947.1.3 | output | WIENER-CRATE-MIB |
| 1.3.6.1.4.1.19947.1.3.2 | outputTable | WIENER-CRATE-MIB |
| 1.3.6.1.4.1.19947.1.3.2.1 | outputEntry | WIENER-CRATE-MIB |
| 1.3.6.1.4.1.19947.1.3.2.1.9 | outputSwitch | WIENER-CRATE-MIB |