All MIBs › EPPC-MIB
Category: Domain: Power/UPS
Description: Proprietary UPS MIB providing management objects for three-phase power, battery, and module status monitoring on enterprise UPS systems.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is EPPC-MIB?
This is a proprietary UPS (uninterruptible power supply) MIB providing management objects for enterprise three-phase UPS systems, covering power, battery, and module status. Based on its object hierarchy (upsAgent, upsE, upsEIdentity, and associated traps), it exposes power-subsystem data such as UPS identity/agent information and status of UPS modules, consistent with typical UPS MIB structures covering input/output power, battery charge, and load. Its core purpose is monitoring the hardware status of the UPS itself, including battery health, module/phase status, and fault conditions communicated via upsETraps, making it directly relevant to power infrastructure uptime monitoring. No dependency on another standard MIB is indicated in the provided material, suggesting it is a vendor-specific, self-contained UPS MIB rather than an extension of the standard UPS-MIB (RFC 1628). It is deployed in data centers and facilities using three-phase UPS systems from this vendor to protect critical power infrastructure for racks of network and server equipment. Engineers can download the EPPC-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in EPPC-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- three-phase UPS systems
Monitoring Examples
An administrator would poll objects under upsEIdentity to confirm the UPS model/agent identity and firmware are as expected, and monitor status objects under upsE/upsAgent for battery and module health to catch a failing battery module before it causes an outage. Receiving a trap from upsETraps would alert the admin to an event such as a phase failure, battery low condition, or module fault requiring immediate attention on a three-phase UPS supporting critical infrastructure.
What Can Be Monitored
- UPS module status
- battery status
- power/phase status
- UPS fault/event traps
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Counter | |
| IpAddress | |
| enterprises |
From SNMPv2-TC
| DisplayString |
From UPS-MIB
| NonNegativeInteger | |
| PositiveInteger |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| ppc | 1.3.6.1.4.1.935 | |||
| device | 1.3.6.1.4.1.935.10 | |||
| upsAgent | 1.3.6.1.4.1.935.10.1 | |||
| upsE | 1.3.6.1.4.1.935.10.1.1 | |||
| upsEIdentity | 1.3.6.1.4.1.935.10.1.1.1 | |||
| STR upsEIdentityManufacturer | 1.3.6.1.4.1.935.10.1.1.1.1 | DisplayString | read-only | The name of the UPS manufacturer. |
| STR upsEIdentityModel | 1.3.6.1.4.1.935.10.1.1.1.2 | DisplayString | read-only | The UPS Model designation. |
| STR upsEIdentityUPSFirmwareVerison | 1.3.6.1.4.1.935.10.1.1.1.3 | DisplayString | read-only | The UPS firmware/software version(s). |
| STR upsEIndentityUPSSerialNumber | 1.3.6.1.4.1.935.10.1.1.1.4 | DisplayString | read-only | optional. Most UPS don't supply the value of UPS serial No. |
| STR upsEIdentityDescription | 1.3.6.1.4.1.935.10.1.1.1.5 | DisplayString | read-write | A string to identify the UPS. This object should be set by the administrator. |
| STR upsEIdentityAgentSoftwareVerison | 1.3.6.1.4.1.935.10.1.1.1.6 | DisplayString | read-only | The Network Management Card software/firmware version. This variable may or may not have the same value as upsEIdentGroupUPSSoftwareVersion in some implementations. |
| STR upsEIdentityAttachedDevices | 1.3.6.1.4.1.935.10.1.1.1.7 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator |
| upsESystemSummary | 1.3.6.1.4.1.935.10.1.1.2 | |||
| INT upsESystemStatus | 1.3.6.1.4.1.935.10.1.1.2.1 | INTEGER | read-only | The indication of UPS system status. |
| INT upsESystemTemperature | 1.3.6.1.4.1.935.10.1.1.2.2 | INTEGER | read-only | The temperature of UPS presented in 0.1 degree. |
| STR upsESystemWarningCode | 1.3.6.1.4.1.935.10.1.1.2.3 | DisplayString | read-only | The warning code of UPS. Please refer the warning table of 'Q6' for details. |
| STR upsESystemFaultCode | 1.3.6.1.4.1.935.10.1.1.2.4 | DisplayString | read-only | The fault code of UPS.Please refer the fault code of 'Q6' for details. |
| NUM upsESystemConfigInputVoltage | 1.3.6.1.4.1.935.10.1.1.2.5 | NonNegativeInteger | read-only | The magnitude of the nominal input voltage presented in 0.1 V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
| NUM upsESystemConfigInputFrequence | 1.3.6.1.4.1.935.10.1.1.2.6 | NonNegativeInteger | read-only | The nominal input frequency presented in 0.1 Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
| NUM upsESystemConfigOutputVoltage | 1.3.6.1.4.1.935.10.1.1.2.7 | NonNegativeInteger | read-only | The magnitude of the nominal output voltage presented in 0.1V. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2 |
| NUM upsESystemConfigOutputFrequency | 1.3.6.1.4.1.935.10.1.1.2.8 | NonNegativeInteger | read-only | The nominal output frequency presented in 0.1Hz. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
| NUM upsESystemConfigOutputVA | 1.3.6.1.4.1.935.10.1.1.2.9 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating presented in VA. |
| NUM upsESystemConfigOutputPower | 1.3.6.1.4.1.935.10.1.1.2.10 | NonNegativeInteger | read-only | The magnitude of the nominal true power rating presented in W . |
| NUM upsESystemConfigOutputLoadHighSetPoint | 1.3.6.1.4.1.935.10.1.1.2.11 | NonNegativeInteger | read-write | The maximum output load allowed before the load is too high for UPS operation |
| NUM upsESystemConfigOverTemperatureSetPoint | 1.3.6.1.4.1.935.10.1.1.2.12 | NonNegativeInteger | read-write | The maximum temperature allowed before the UPS operation temperature is too high, presented in 0.1 degree. |
| INT upsESystemInputSourceNum | 1.3.6.1.4.1.935.10.1.1.2.13 | INTEGER | read-only | The present external source of input power. |
| CTR upsESystemInputLineBads | 1.3.6.1.4.1.935.10.1.1.2.14 | Counter | read-only | The number of times the Input was out of tolerance in voltage or frequency. Its value should be initialized 0 after agent restarting. |
| NUM upsESystemInputNumPhases | 1.3.6.1.4.1.935.10.1.1.2.15 | PositiveInteger | read-only | The number of input phase utilized is this device, serves as the table index. This value indicate the device initialized feature. |
| upsESystemInputTable | 1.3.6.1.4.1.935.10.1.1.2.16 | not-accessible | A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase. | |
| upsESystemInputEntry | 1.3.6.1.4.1.935.10.1.1.2.16.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM upsESystemInputPhase | 1.3.6.1.4.1.935.10.1.1.2.16.1.1 | PositiveInteger | not-accessible | The number of the phase. Serves as index for input table |
| NUM upsESystemInputFrequency | 1.3.6.1.4.1.935.10.1.1.2.16.1.2 | NonNegativeInteger | read-only | The measured input frquency from the UPS meters in 0.1Hz. |
| NUM upsESystemInputVoltage | 1.3.6.1.4.1.935.10.1.1.2.16.1.3 | NonNegativeInteger | read-only | The measured input voltage from the UPS meters in 0.1 volts |
| NUM upsESystemInputCurrent | 1.3.6.1.4.1.935.10.1.1.2.16.1.4 | NonNegativeInteger | read-only | The measured input mandatory from the UPS meters in 0.1 amps. |
| NUM upsESystemInputWatts | 1.3.6.1.4.1.935.10.1.1.2.16.1.5 | NonNegativeInteger | read-only | The measured input real power in watts. |
| NUM upsESystemOutputNumPhase | 1.3.6.1.4.1.935.10.1.1.2.17 | PositiveInteger | read-only | The number of metered output phases, serves as the table index. This value indicate the device initialized feature. |
| upsESystemOutputTable | 1.3.6.1.4.1.935.10.1.1.2.18 | not-accessible | A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase. | |
| upsESystemOutputEntry | 1.3.6.1.4.1.935.10.1.1.2.18.1 | not-accessible | An entry containing information applicable to a particular line. | |
| NUM upsESystemOutputPhase | 1.3.6.1.4.1.935.10.1.1.2.18.1.1 | PositiveInteger | not-accessible | The number of the phase. Serves as index for output table |
| NUM upsESystemOutputFrequency | 1.3.6.1.4.1.935.10.1.1.2.18.1.2 | NonNegativeInteger | read-only | The measured output frequency from the UPS meters in 0.1Hz. |
| NUM upsESystemOutputVoltage | 1.3.6.1.4.1.935.10.1.1.2.18.1.3 | NonNegativeInteger | read-only | The measured output voltage from the UPS meters in 0.1 volts |
| NUM upsESystemOutputCurrent | 1.3.6.1.4.1.935.10.1.1.2.18.1.4 | NonNegativeInteger | read-only | The measured output mandatory from the UPS meters in 0.1 amps. |
| NUM upsESystemOutputWatts | 1.3.6.1.4.1.935.10.1.1.2.18.1.5 | NonNegativeInteger | read-only | The measured output real power in watts. |
| NUM upsESystemOutputVA | 1.3.6.1.4.1.935.10.1.1.2.18.1.6 | NonNegativeInteger | read-only | The measured output real complex power in VA. |
| NUM upsESystemOutputLoad | 1.3.6.1.4.1.935.10.1.1.2.18.1.7 | NonNegativeInteger | read-only | The UPS output load in percent of rated capacity. |
| NUM upsESystemBypassNumPhase | 1.3.6.1.4.1.935.10.1.1.2.19 | PositiveInteger | read-only | The number of bypass phases, serves as the table index. This value indicate the device initialized feature |
| upsESystemBypassTable | 1.3.6.1.4.1.935.10.1.1.2.20 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase. | |
| upsESystemBypassEntry | 1.3.6.1.4.1.935.10.1.1.2.20.1 | not-accessible | An entry containing information applicable to a particular line. | |
| NUM upsESystemBypassPhase | 1.3.6.1.4.1.935.10.1.1.2.20.1.1 | PositiveInteger | not-accessible | The number of the phase. Serves as index for bypass table |
| NUM upsESystemBypassFrequency | 1.3.6.1.4.1.935.10.1.1.2.20.1.2 | NonNegativeInteger | read-only | The measured bypass frequency from the UPS meters in 0.1 Hz. |
| NUM upsESystemBypassVoltage | 1.3.6.1.4.1.935.10.1.1.2.20.1.3 | NonNegativeInteger | read-only | The measured bypass voltage from the UPS meters in 0.1 volts |
| NUM upsESystemBypassCurrent | 1.3.6.1.4.1.935.10.1.1.2.20.1.4 | NonNegativeInteger | read-only | The measured bypass mandatory from the UPS meters in 0.1 amps |
| NUM upsESystemBypassWatts | 1.3.6.1.4.1.935.10.1.1.2.20.1.5 | NonNegativeInteger | read-only | The measured input real power in watts. |
| NUM upsESystemConfigBelowCapacityLimit | 1.3.6.1.4.1.935.10.1.1.2.21 | NonNegativeInteger | read-write | The UPS batteries capacity(%) limit for shutdown |
| NUM upsESystemConfigBelowRemainTimeLimit | 1.3.6.1.4.1.935.10.1.1.2.22 | NonNegativeInteger | read-write | The UPS batteries backup time(minute) limit for shutdown |
| upsEBatterySystem | 1.3.6.1.4.1.935.10.1.1.3 | |||
| INT upsEBatteryStatus | 1.3.6.1.4.1.935.10.1.1.3.1 | INTEGER | read-only | The status of UPS battery, a value of batteryLow indicates that the battery-low status bit has been set from device. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is mandatoryly absent and the UPS is unable to sustain the output) |
| NUM upsESecondsOnBattery | 1.3.6.1.4.1.935.10.1.1.3.2 | NonNegativeInteger | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. 0 shall be returned if the unit is not on battery power |
| NUM upsEBatteryEstimatedMinutesRemaining | 1.3.6.1.4.1.935.10.1.1.3.3 | PositiveInteger | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. |
| I32 upsEBatteryEstimatedChargeRemaining | 1.3.6.1.4.1.935.10.1.1.3.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge |
| NUM upsEPositiveBatteryVoltage | 1.3.6.1.4.1.935.10.1.1.3.5 | NonNegativeInteger | read-only | The magnitude of the present positive battery voltage in 0.1 Volt DC |
| NUM upsENegativeBatteryVoltage | 1.3.6.1.4.1.935.10.1.1.3.6 | NonNegativeInteger | read-only | The magnitude of the present negative battery voltage in 0.1 Volt DC |
| NUM upsEBatteryCellNumber | 1.3.6.1.4.1.935.10.1.1.3.7 | NonNegativeInteger | read-only | This object indicate the cell number of each set. |
| INT upsEBatteryTemperature | 1.3.6.1.4.1.935.10.1.1.3.8 | INTEGER | read-only | The ambient temperature at or near the UPS Battery casing in 0.1 degree. |
| STR upsEBatteryLastReplacedDate | 1.3.6.1.4.1.935.10.1.1.3.9 | DisplayString | read-only | The date when the Batteries in this UPS were last replaced. The format should be DD/MM/YYYY. |
| INT upsEBatteryABMStatus | 1.3.6.1.4.1.935.10.1.1.3.10 | INTEGER | read-only | The status of ABM. |
| NUM upsEChargerModulesNum | 1.3.6.1.4.1.935.10.1.1.3.11 | NonNegativeInteger | read-only | The number of charger modules inserted to UPS systems. served as the index of the upsEChargerModulesTable. The default value 0 indicate that the UPS system don't have separate charger module. |
| upsEChargerModulesTable | 1.3.6.1.4.1.935.10.1.1.3.12 | not-accessible | A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum. | |
| upsEChargerModulesEntry | 1.3.6.1.4.1.935.10.1.1.3.12.1 | not-accessible | An entry containing information applicable to a particular charger module. | |
| NUM chargerModulesNum | 1.3.6.1.4.1.935.10.1.1.3.12.1.1 | PositiveInteger | not-accessible | The number of charger modules. Serves as index for charger module table |
| NUM chargerModulesAddress | 1.3.6.1.4.1.935.10.1.1.3.12.1.2 | NonNegativeInteger | read-only | Charger Modules' address. |
| NUM positiveChargeVotlage | 1.3.6.1.4.1.935.10.1.1.3.12.1.3 | NonNegativeInteger | read-only | The measured positive charger voltage from the UPS meters in 0.1 volts |
| NUM negativeChargeVoltage | 1.3.6.1.4.1.935.10.1.1.3.12.1.4 | NonNegativeInteger | read-only | The measured nepositive charger voltage from the UPS meters in 0.1 volts |
| NUM positiveChargeCurrent | 1.3.6.1.4.1.935.10.1.1.3.12.1.5 | NonNegativeInteger | read-only | The measured positive charger mandatory from the UPS meters in in 0.1 amps. |
| NUM negativeChargeCurrent | 1.3.6.1.4.1.935.10.1.1.3.12.1.6 | NonNegativeInteger | read-only | The measured nepositive charger mandatory from the UPS meters in 0.1 amps. |
| INT chargerModulesTemperature | 1.3.6.1.4.1.935.10.1.1.3.12.1.7 | INTEGER | read-only | The measured charger temperature from the UPS meters in 0.1 degree. |
| INT chargerModulesMode | 1.3.6.1.4.1.935.10.1.1.3.12.1.8 | INTEGER | read-only | The working mode of charger modules. |
| upsEPowerConverterSystem | 1.3.6.1.4.1.935.10.1.1.4 | |||
| NUM upsEUPSModulesNum | 1.3.6.1.4.1.935.10.1.1.4.1 | NonNegativeInteger | read-only | The number of UPS modules inserted to UPS systems. served as the index of the upsEModulesTable. the default value 0 indicate that the UPS system do not have separate UPS module. |
| upsEModulesTable | 1.3.6.1.4.1.935.10.1.1.4.2 | not-accessible | A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum. | |
| upsEModulesEntry | 1.3.6.1.4.1.935.10.1.1.4.2.1 | not-accessible | An entry containing information applicable to a particular upsE module. | |
| NUM upsEModulesNum | 1.3.6.1.4.1.935.10.1.1.4.2.1.1 | PositiveInteger | not-accessible | The number of UPS modules. Serves as index for UPS module table |
| INT upsEModuleAddress | 1.3.6.1.4.1.935.10.1.1.4.2.1.2 | INTEGER | read-only | the address of UPS modules. |
| NUM upsEModulePositiveBusVolt | 1.3.6.1.4.1.935.10.1.1.4.2.1.3 | NonNegativeInteger | read-only | The measured positive upsE module voltage from the UPS meters in 0.1 volts |
| NUM upsEModuleNegativeBusVolt | 1.3.6.1.4.1.935.10.1.1.4.2.1.4 | NonNegativeInteger | read-only | The measured nepositive upsE module voltage from the UPS meters in 0.1 volts |
| INT upsEModuleTemperature | 1.3.6.1.4.1.935.10.1.1.4.2.1.5 | INTEGER | read-only | The measured upsE module temperature from the UPS meters in 0.1 degree. |
| INT upsEModuleWorkingMode | 1.3.6.1.4.1.935.10.1.1.4.2.1.6 | INTEGER | read-only | The working mode of UPS modules. |
| NUM upsEModuleOutputCurrentR | 1.3.6.1.4.1.935.10.1.1.4.2.1.7 | NonNegativeInteger | read-only | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| NUM upsEModuleOutputWattR | 1.3.6.1.4.1.935.10.1.1.4.2.1.8 | NonNegativeInteger | read-only | The measured upsE module output watts from the UPS meters in watts. |
| INT upsEModuleOutputLoadR | 1.3.6.1.4.1.935.10.1.1.4.2.1.9 | INTEGER | read-only | The output load of UPS modules in %. |
| STR upsEModuleWarningCode | 1.3.6.1.4.1.935.10.1.1.4.2.1.10 | DisplayString | read-only | The warning code of ups modules.Please refer the warning table of 'QU,XX' for details. |
| STR upsEModuleFaultCode | 1.3.6.1.4.1.935.10.1.1.4.2.1.11 | DisplayString | read-only | The fault code of ups modules.Please refer command 'QU,XX' for details. |
| STR upsEModuleTrapState | 1.3.6.1.4.1.935.10.1.1.4.2.1.12 | DisplayString | read-only | the values indicate the unrestored traps. For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEModuleTrapState should change to empty. |
| NUM upsEModuleConfigOutputVA | 1.3.6.1.4.1.935.10.1.1.4.2.1.13 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating presented in VA. |
| NUM upsEModuleOutputCurrentS | 1.3.6.1.4.1.935.10.1.1.4.2.1.14 | NonNegativeInteger | read-only | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| NUM upsEModuleOutputCurrentT | 1.3.6.1.4.1.935.10.1.1.4.2.1.15 | NonNegativeInteger | read-only | The measured upsE module output mandatory from the UPS meters in 0.1 A. |
| NUM upsEModuleOutputWattS | 1.3.6.1.4.1.935.10.1.1.4.2.1.16 | NonNegativeInteger | read-only | The measured upsE module output watts from the UPS meters in watts. |
| NUM upsEModuleOutputWattT | 1.3.6.1.4.1.935.10.1.1.4.2.1.17 | NonNegativeInteger | read-only | The measured upsE module output watts from the UPS meters in watts. |
| INT upsEModuleOutputLoadS | 1.3.6.1.4.1.935.10.1.1.4.2.1.18 | INTEGER | read-only | The output load of UPS modules in %. |
| INT upsEModuleOutputLoadT | 1.3.6.1.4.1.935.10.1.1.4.2.1.19 | INTEGER | read-only | The output load of UPS modules in %. |
| NUM upsEModuleOutputVAR | 1.3.6.1.4.1.935.10.1.1.4.2.1.20 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating presented in VA. |
| NUM upsEModuleOutputVAS | 1.3.6.1.4.1.935.10.1.1.4.2.1.21 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating presented in VA. |
| NUM upsEModuleOutputVAT | 1.3.6.1.4.1.935.10.1.1.4.2.1.22 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating presented in VA. |
| upsELoadSegment | 1.3.6.1.4.1.935.10.1.1.5 | |||
| INT upsELoadSegment1OffDelay | 1.3.6.1.4.1.935.10.1.1.5.1 | INTEGER | read-write | Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment. |
| INT upsELoadSegment1OnDelay | 1.3.6.1.4.1.935.10.1.1.5.2 | INTEGER | read-write | Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. |
| INT upsELoadSegment1AutoOffTimer | 1.3.6.1.4.1.935.10.1.1.5.3 | INTEGER | read-write | The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired. |
| INT upsELoadSegment1AutoOnTimer | 1.3.6.1.4.1.935.10.1.1.5.4 | INTEGER | read-write | The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery. |
| INT upsELoadSegment1State | 1.3.6.1.4.1.935.10.1.1.5.5 | INTEGER | read-only | Load segment output state. |
| INT upsELoadSegment2OffDelay | 1.3.6.1.4.1.935.10.1.1.5.6 | INTEGER | read-write | Setting this object will shutdown the UPS Load Segment output after the indicated number of seconds, or less. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. Read this object will get countdown value of the Load Segment. |
| INT upsELoadSegment2OnDelay | 1.3.6.1.4.1.935.10.1.1.5.7 | INTEGER | read-write | Setting this object will start the Load segment output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. |
| INT upsELoadSegment2AutoOffTimer | 1.3.6.1.4.1.935.10.1.1.5.8 | INTEGER | read-write | The load segment turns automatically off after the delay while the unit operates on battery, but the shutdown is cancelled if the utility return before the delay has expired. |
| INT upsELoadSegment2AutoOnTimer | 1.3.6.1.4.1.935.10.1.1.5.9 | INTEGER | read-write | The load segment is automatically turned on after a selected delay if it has been shutdown due to on battery. |
| INT upsELoadSegment2State | 1.3.6.1.4.1.935.10.1.1.5.10 | INTEGER | read-only | Load segment output state. |
| upsEEnvironment | 1.3.6.1.4.1.935.10.1.1.6 | |||
| upsEEnvironmentTemperature | 1.3.6.1.4.1.935.10.1.1.6.1 | |||
| INT upsEEnvironmentCurrentTemperature | 1.3.6.1.4.1.935.10.1.1.6.1.1 | INTEGER | read-only | The measurement of temperature sensor, in 0.1 degree |
| INT upsEEnvironmentTemperatureHighSetPoint | 1.3.6.1.4.1.935.10.1.1.6.1.2 | INTEGER | read-write | The set point for high temperature warning, in 0.1 degrees. This value must be greater than upsEEnvironmentTemperatureLowSetPoint, and the least significant digit must be zero. |
| INT upsEEnvironmentTemperatureHighStatus | 1.3.6.1.4.1.935.10.1.1.6.1.3 | INTEGER | read-write | To enable/disable high set point check with sensor temperature. |
| INT upsEEnvironmentTemperatureLowSetPoint | 1.3.6.1.4.1.935.10.1.1.6.1.4 | INTEGER | read-write | The set point for low temperature warning, in 0.1 degrees. This value must be less than upsEEnvironmentTemperatureHighSetPoint, and the least significant digit must be zero. |
| INT upsEEnvironmentTemperatureLowStatus | 1.3.6.1.4.1.935.10.1.1.6.1.5 | INTEGER | read-write | To enable/disable low set point check with sensor temperature. |
| INT upsEEnvironmentTemperatureOffset | 1.3.6.1.4.1.935.10.1.1.6.1.6 | INTEGER | read-write | The offset to calibrate temperature of EMD, in 0.1 degrees |
| upsEEnvironmentHumidity | 1.3.6.1.4.1.935.10.1.1.6.2 | |||
| INT upsEEnvironmentCurrentHumidity | 1.3.6.1.4.1.935.10.1.1.6.2.1 | INTEGER | read-only | The measurement of sensor humidity present in %. |
| INT upsEEnvironmentHumidityHighSetPoint | 1.3.6.1.4.1.935.10.1.1.6.2.2 | INTEGER | read-write | The set point for high humidity warning, in %. This value must be greater than upsEEnvironmentHumidityLowSetPoint. |
| INT upsEEnvironmentHumidityHighStatus | 1.3.6.1.4.1.935.10.1.1.6.2.3 | INTEGER | read-write | To enable/disable high set point check with emd humidity. |
| INT upsEEnvironmentHumidityLowSetPoint | 1.3.6.1.4.1.935.10.1.1.6.2.4 | INTEGER | read-write | The set point for low humidity warning, in %. This value must be less than upsEEnvironmentHumidityHighSetPoint. |
| INT upsEEnvironmentHumidityLowStatus | 1.3.6.1.4.1.935.10.1.1.6.2.5 | INTEGER | read-write | To enable/disable high set point check with emd humidity. |
| INT upsEEnvironmentHumidityOffset | 1.3.6.1.4.1.935.10.1.1.6.2.6 | INTEGER | read-write | The offset to calibrate humidity of EMD, in %. |
| NUM upsEEnvironmentContactsNum | 1.3.6.1.4.1.935.10.1.1.6.3 | NonNegativeInteger | read-only | The number of environment contacts, serves as the table index. |
| upsEEnvironmentContactTable | 1.3.6.1.4.1.935.10.1.1.6.4 | not-accessible | A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum | |
| upsEEnvironmentContactEntry | 1.3.6.1.4.1.935.10.1.1.6.4.1 | not-accessible | An entry containing information applicable to a particular contact | |
| NUM upsEEnvironmentContactIndex | 1.3.6.1.4.1.935.10.1.1.6.4.1.1 | PositiveInteger | not-accessible | The number of environment contacts. Serves as index for environment contact table |
| INT upsEEnvironmentContactType | 1.3.6.1.4.1.935.10.1.1.6.4.1.2 | INTEGER | read-write | operation type |
| INT upsEEnvironmentContactState | 1.3.6.1.4.1.935.10.1.1.6.4.1.3 | INTEGER | read-only | The mandatory status. |
| STR upsEEnvironmentContactDescription | 1.3.6.1.4.1.935.10.1.1.6.4.1.4 | DisplayString | read-write | Description of environment contact. |
| upsEBatteryTest | 1.3.6.1.4.1.935.10.1.1.7 | |||
| INT upsEBatteryTestStart | 1.3.6.1.4.1.935.10.1.1.7.1 | INTEGER | read-write | This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsEBatteryTestSettingTime. |
| NUM upsEBatteryTestSettingTime | 1.3.6.1.4.1.935.10.1.1.7.2 | NonNegativeInteger | read-write | The object specify the test time for battery test in seconds. |
| INT upsEBatteryTestResult | 1.3.6.1.4.1.935.10.1.1.7.3 | INTEGER | read-only | This object indicate the test result of battery. |
| STR upsEBatteryTestStartTime | 1.3.6.1.4.1.935.10.1.1.7.4 | DisplayString | read-only | The value of the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsETestBatteryTestResult is noTestsInitiated(6), upsETestStartTime has the value 01/01/1970 00:00:00. |
| STR upsEBatteryTestElapsedTime | 1.3.6.1.4.1.935.10.1.1.7.5 | DisplayString | read-only | The amount of time in format hh:mm:ss, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is idle(1), upsTestElapsedTime has the value 00:00:00. |
| upsEBatteryTestScheduleTable | 1.3.6.1.4.1.935.10.1.1.7.6 | not-accessible | This table describes the schedule for automatically battery test. | |
| upsEBatteryTestScheduleEntry | 1.3.6.1.4.1.935.10.1.1.7.6.1 | not-accessible | An entry containing information applicable to schedule test. | |
| NUM upsEBatteryTestScheduleIndex | 1.3.6.1.4.1.935.10.1.1.7.6.1.1 | PositiveInteger | not-accessible | The index of battery test scheduled. |
| INT upsEBatteryTestScheduleDay | 1.3.6.1.4.1.935.10.1.1.7.6.1.2 | INTEGER | read-write | The weekday or specaial day on which the UPS should start battery test. |
| STR upsEBatteryTestScheduleTime | 1.3.6.1.4.1.935.10.1.1.7.6.1.3 | DisplayString | read-write | The time that the battery test will be initiated in hh:mm format. |
| INT upsEBatteryTestScheduleType | 1.3.6.1.4.1.935.10.1.1.7.6.1.5 | INTEGER | read-write | The type of battery test. |
| NUM upsEBatteryTestScheduleTestWithTime | 1.3.6.1.4.1.935.10.1.1.7.6.1.6 | NonNegativeInteger | read-write | The battery time of setting time test in seconds. |
| STR upsEBatteryTestScheduleSpecialDay | 1.3.6.1.4.1.935.10.1.1.7.6.1.7 | DisplayString | read-write | The special day that the battery test will be initiated in dd/mm/yyyy format. |
| upsEControl | 1.3.6.1.4.1.935.10.1.1.8 | |||
| NUM upsEControlOutputOffDelay | 1.3.6.1.4.1.935.10.1.1.8.1 | NonNegativeInteger | read-write | Setting this value to other than zero will cause the UPS output to turn off after the number of seconds. |
| NUM upsEControlOutputOnDelay | 1.3.6.1.4.1.935.10.1.1.8.2 | NonNegativeInteger | read-write | Setting this value to other than zero will cause the UPS output to turn on after the number of seconds. |
| INT upsEControlOutputOnOffControl | 1.3.6.1.4.1.935.10.1.1.8.3 | INTEGER | read-write | upsEOutputOff ( 1 ) indicates the shutdown sequence, upsEOutputOffCancel ( 2 ) indicates cancel the shutdown sequence, upsESleep( 3 ) indicates shutdown UPS first, then switch on. |
| upsEShutdownEventsTable | 1.3.6.1.4.1.935.10.1.1.8.4 | not-accessible | This table describes the parametes for shutdown process when shutdown event occurs | |
| upsEShutdownEventsEntry | 1.3.6.1.4.1.935.10.1.1.8.4.1 | not-accessible | An entry containing information applicable to a particular shutdown event line | |
| INT upsEShutdownEvent | 1.3.6.1.4.1.935.10.1.1.8.4.1.1 | INTEGER | not-accessible | The shutdown event identification |
| INT upsEShutdownEventAction | 1.3.6.1.4.1.935.10.1.1.8.4.1.2 | INTEGER | read-write | Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured. |
| NUM upsEShutdownwarningPeriodTime | 1.3.6.1.4.1.935.10.1.1.8.4.1.3 | NonNegativeInteger | read-write | The Delay in seconds after the occurance of the curresponding shutdown event, and warning message should be popped in this period. |
| NUM upsEShutdownWarningPeriodInterval | 1.3.6.1.4.1.935.10.1.1.8.4.1.4 | NonNegativeInteger | read-write | The frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds. |
| upsEControlWeeklyScheduleTable | 1.3.6.1.4.1.935.10.1.1.8.5 | not-accessible | The table to schedule shutting down the ups by weekly | |
| upsEControlWeeklyScheduleEntry | 1.3.6.1.4.1.935.10.1.1.8.5.1 | not-accessible | An entry containing information applicable to a particular line | |
| NUM upsEControlWeeklyScheduleIndex | 1.3.6.1.4.1.935.10.1.1.8.5.1.1 | PositiveInteger | not-accessible | the index of schedule events. |
| INT upsEWeeklyScheduleShutdownDay | 1.3.6.1.4.1.935.10.1.1.8.5.1.2 | INTEGER | read-write | the weekday on which upsE shoud shutdown |
| STR upsEWeeklyScheduleShutdownTime | 1.3.6.1.4.1.935.10.1.1.8.5.1.3 | DisplayString | read-write | The time that the process of shutting down the UPS will be initiated in hh:mm format. |
| INT upsEWeeklyScheduleRestartDay | 1.3.6.1.4.1.935.10.1.1.8.5.1.4 | INTEGER | read-write | the weekday on which the UPS should restart. |
| STR upsEWeeklyScheduleRestartTime | 1.3.6.1.4.1.935.10.1.1.8.5.1.5 | DisplayString | read-write | The time the UPS will restart in hh:mm format. |
| upsEControlSpecialDayScheduleTable | 1.3.6.1.4.1.935.10.1.1.8.6 | not-accessible | The table to schedule shutting down the ups. | |
| upsEControlSpecialDayScheduleEntry | 1.3.6.1.4.1.935.10.1.1.8.6.1 | not-accessible | An entry containing information applicable to a particular line. | |
| NUM upsEControlSpecialDayScheduleIndex | 1.3.6.1.4.1.935.10.1.1.8.6.1.1 | PositiveInteger | not-accessible | The index of special day schedule. |
| STR upsESpecialDayScheduleShutdownDay | 1.3.6.1.4.1.935.10.1.1.8.6.1.2 | DisplayString | read-write | The special day on which UPS should shutdown with the format of DD/MM/YYYY. |
| STR upsESpecialDayScheduleShutdownTime | 1.3.6.1.4.1.935.10.1.1.8.6.1.3 | DisplayString | read-write | The time that the process of shutting down the UPS will be initiated in hh:mm format. |
| STR upsESpecialDayScheduleRestartDay | 1.3.6.1.4.1.935.10.1.1.8.6.1.4 | DisplayString | read-write | The special day on which the UPS should restart with the format of DD/MM/YYYY. |
| STR upsESpecialDayScheduleRestartTime | 1.3.6.1.4.1.935.10.1.1.8.6.1.5 | DisplayString | read-write | The time the UPS will restart in hh:mm format. |
| INT upsESystemMasterOffDelay | 1.3.6.1.4.1.935.10.1.1.8.7 | INTEGER | read-only | The UPS output will shutdown after the indicated number of seconds, -1 indicate no action. |
| INT upsESystemMasterOnDelay | 1.3.6.1.4.1.935.10.1.1.8.8 | INTEGER | read-only | The UPS output will start on after the indicated number of seconds, -1 indicate no action. |
| upsETrapControl | 1.3.6.1.4.1.935.10.1.1.9 | |||
| upsETrapsReceiversTable | 1.3.6.1.4.1.935.10.1.1.9.1 | not-accessible | This table list the managers'IP to send traps to. | |
| upsETrapsReceiversEntry | 1.3.6.1.4.1.935.10.1.1.9.1.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM upsETrapsReceiversIndex | 1.3.6.1.4.1.935.10.1.1.9.1.1.1 | PositiveInteger | not-accessible | The index to a trap receiver entry |
| STR upsETrapsReceiverAddress | 1.3.6.1.4.1.935.10.1.1.9.1.1.2 | DisplayString | read-write | The IP address of the manager to send a trap to. |
| STR upsETrapReceiverCommunityString | 1.3.6.1.4.1.935.10.1.1.9.1.1.3 | DisplayString | read-write | The community name to use in the trap when sent to the manager. |
| INT upsETrapType | 1.3.6.1.4.1.935.10.1.1.9.1.1.4 | INTEGER | read-write | The type of trap to be received by the manager. |
| INT upsETrapsSeverityLevel | 1.3.6.1.4.1.935.10.1.1.9.1.1.5 | INTEGER | read-write | The severity level of traps to be received by this manager. |
| STR upsETrapReceiverDescription | 1.3.6.1.4.1.935.10.1.1.9.1.1.6 | DisplayString | read-write | Description of trap receivers |
| STR upsETrapState | 1.3.6.1.4.1.935.10.1.1.9.2 | DisplayString | read-only | the values indicate the unrestored traps. For example, after AC fail, the agent send the trap 1(AC Fail) and trap 7(battery on) to NMS. so the value of upsETrapState should be '1,7'. And then the AC restore, the value of upsETrapState should change to empty. |
| upsETraps | 1.3.6.1.4.1.935.10.1.2 | |||
| NTF upsEPowerFail | 1.3.6.1.4.1.935.10.1.2.0.1 | WARNING: Utility power not available. | ||
| NTF upsEPowerRestored | 1.3.6.1.4.1.935.10.1.2.0.2 | INFORMATION: Utility power has restored. | ||
| NTF upsELowBattery | 1.3.6.1.4.1.935.10.1.2.0.3 | SEVERE: The UPS batteries are low and will soon be exhausted. | ||
| NTF upsEReturnFromLowBattery | 1.3.6.1.4.1.935.10.1.2.0.4 | INFORMATION: The UPS has return from a low battery condition. | ||
| NTF upsEFailed | 1.3.6.1.4.1.935.10.1.2.0.5 | SEVERE: The UPS is not working fine. | ||
| NTF upsEOk | 1.3.6.1.4.1.935.10.1.2.0.6 | INFORMATION: The UPS is working fine. | ||
| NTF upsEOnBattery | 1.3.6.1.4.1.935.10.1.2.0.7 | WARNING: The UPS has switched to battery backup power. | ||
| NTF upsENotOnBattery | 1.3.6.1.4.1.935.10.1.2.0.8 | INFORMATION: The UPS is not on battery power. | ||
| NTF upsETestInProgress | 1.3.6.1.4.1.935.10.1.2.0.9 | INFORMATION: The testing is going on ups. | ||
| NTF upsETestOver | 1.3.6.1.4.1.935.10.1.2.0.10 | INFORMATION: The testing of UPS is completed. | ||
| NTF upsEBypassOn | 1.3.6.1.4.1.935.10.1.2.0.11 | INFORMATION: The UPS has enabled bypass. | ||
| NTF upsEOnline | 1.3.6.1.4.1.935.10.1.2.0.12 | INFORMATION: The UPS is not on Bypass and return to normal status. | ||
| NTF upsECommunicationLost | 1.3.6.1.4.1.935.10.1.2.0.13 | SEVERE: Communication to the UPS has been lost. | ||
| NTF upsECommunicationEstablished | 1.3.6.1.4.1.935.10.1.2.0.14 | INFORMATION: Communication with the UPS has been established. | ||
| NTF upsEGoingShutdown | 1.3.6.1.4.1.935.10.1.2.0.15 | WARNING: The UPS is going to shutdown output. | ||
| NTF upsEShutdownCancelled | 1.3.6.1.4.1.935.10.1.2.0.16 | INFORMATION: The UPS is not going to shutdown output. | ||
| NTF upsEOutlet1GoingShutdown | 1.3.6.1.4.1.935.10.1.2.0.17 | WARNING: The UPS is going to shutdown outlet1. | ||
| NTF upsEOutlet1ShutdownCancelled | 1.3.6.1.4.1.935.10.1.2.0.18 | INFORMATION: The UPS is not going to shutdown outlet1. | ||
| NTF upsEOutlet2GoingShutdown | 1.3.6.1.4.1.935.10.1.2.0.19 | WARNING: The UPS is going to shutdown outlet2. | ||
| NTF upsEOutlet2ShutdownCancelled | 1.3.6.1.4.1.935.10.1.2.0.20 | INFORMATION: The UPS is not going to shutdown outlet2. | ||
| NTF upsESleeping | 1.3.6.1.4.1.935.10.1.2.0.21 | INFORMATION: UPS has entered sleep mode and power to load has been cut off. | ||
| NTF upsEWokeUp | 1.3.6.1.4.1.935.10.1.2.0.22 | INFORMATION: The UPS woke up from sleep mode and power to load has been restored. | ||
| NTF upsEOverTemperature | 1.3.6.1.4.1.935.10.1.2.0.23 | WARNING: The UPS temperature is over the setting limit. | ||
| NTF upsENotOverTemperature | 1.3.6.1.4.1.935.10.1.2.0.24 | INFORMATION: The UPS temperature is not over the setting limit. | ||
| NTF upsEOverLoad | 1.3.6.1.4.1.935.10.1.2.0.25 | WARNING: The UPS load is over the setting limit. | ||
| NTF upsENotOverLoad | 1.3.6.1.4.1.935.10.1.2.0.26 | INFORMATION: The UPS load is not over the setting limit. | ||
| NTF upsEModuleInserted | 1.3.6.1.4.1.935.10.1.2.0.27 | WARNING: UPS module or charger module plug-in. | ||
| NTF upsEModuleRemoved | 1.3.6.1.4.1.935.10.1.2.0.28 | WARNING: UPS module or charger module unplugs. | ||
| NTF sensorTemperatureTooHigh | 1.3.6.1.4.1.935.10.1.2.0.29 | WARNING: Sensor Temperature over high Set point. | ||
| NTF sensorTemperatureNotHigh | 1.3.6.1.4.1.935.10.1.2.0.30 | INFORMATION: Sensor Temperature not over high Set point. | ||
| NTF sensorTemperatureTooLow | 1.3.6.1.4.1.935.10.1.2.0.31 | WARNING: Sensor Temperature under low Set point. | ||
| NTF sensorTemperatureNotLow | 1.3.6.1.4.1.935.10.1.2.0.32 | INFORMATION: Sensor Temperature not under low Set point. | ||
| NTF sensorHumidityTooHigh | 1.3.6.1.4.1.935.10.1.2.0.33 | WARNING: Sensor Humidity over high Set point. | ||
| NTF sensorHumidityNotHigh | 1.3.6.1.4.1.935.10.1.2.0.34 | INFORMATION: Sensor Humidity not over high Set point. | ||
| NTF sensorHumidityTooLow | 1.3.6.1.4.1.935.10.1.2.0.35 | WARNING: Sensor Humidity under low Set point. | ||
| NTF sensorHumidityNotLow | 1.3.6.1.4.1.935.10.1.2.0.36 | INFORMATION: Sensor Humidity not under low Set point. | ||
| NTF contactAlarm1Active | 1.3.6.1.4.1.935.10.1.2.0.37 | WARNING: Contact Alarm-1 activated. | ||
| NTF concactAlarm1Normal | 1.3.6.1.4.1.935.10.1.2.0.38 | INFORMATION: Contact Alarm-1 not active. | ||
| NTF contactAlarm2Active | 1.3.6.1.4.1.935.10.1.2.0.39 | WARNING: Contact Alarm-2 activated. | ||
| NTF contactAlarm2Normal | 1.3.6.1.4.1.935.10.1.2.0.40 | INFORMATION: Contact Alarm-2 not active. | ||
| NTF upsEInternalwarning | 1.3.6.1.4.1.935.10.1.2.0.41 | WARNING: Internal warning. | ||
| NTF upsEReturnFromInternalwarning | 1.3.6.1.4.1.935.10.1.2.0.42 | INFORMATION: Return from Internal warning. | ||
| NTF upsEEPOActive | 1.3.6.1.4.1.935.10.1.2.0.43 | WARNING: EPO Active. | ||
| NTF upsEReturnFromEPOActive | 1.3.6.1.4.1.935.10.1.2.0.44 | INFORMATION: Return from EPO Active. | ||
| NTF upsEModuleUnlock | 1.3.6.1.4.1.935.10.1.2.0.45 | WARNING: Module Unlock. | ||
| NTF upsEReturnFromModuleUnlock | 1.3.6.1.4.1.935.10.1.2.0.46 | INFORMATION: Return from Module Unlock. | ||
| NTF upsEMain1Neutralloss | 1.3.6.1.4.1.935.10.1.2.0.47 | WARNING: Main 1 Neutral loss. | ||
| NTF upsEReturnFromMain1Neutralloss | 1.3.6.1.4.1.935.10.1.2.0.48 | INFORMATION: Return from Main 1 Neutral loss. | ||
| NTF upsEMain1phaseerror | 1.3.6.1.4.1.935.10.1.2.0.49 | WARNING: Main 1 phase error. | ||
| NTF upsEReturnFromMain1phaseerror | 1.3.6.1.4.1.935.10.1.2.0.50 | INFORMATION: Return from Main 1 phase error. | ||
| NTF upsESitefault | 1.3.6.1.4.1.935.10.1.2.0.51 | WARNING: Site fault. | ||
| NTF upsEReturnFromSitefault | 1.3.6.1.4.1.935.10.1.2.0.52 | INFORMATION: Return from Site fault. | ||
| NTF upsEBypassAbnormal | 1.3.6.1.4.1.935.10.1.2.0.53 | WARNING: Bypass Abnormal. | ||
| NTF upsEReturnFromBypassAbnormal | 1.3.6.1.4.1.935.10.1.2.0.54 | INFORMATION: Return from Bypass Abnormal. | ||
| NTF upsEBypassPhaseError | 1.3.6.1.4.1.935.10.1.2.0.55 | WARNING: Bypass Phase Error. | ||
| NTF upsEReturnFromBypassPhaseError | 1.3.6.1.4.1.935.10.1.2.0.56 | INFORMATION: Return from Bypass Phase Error. | ||
| NTF upsEBatteryOpen | 1.3.6.1.4.1.935.10.1.2.0.57 | WARNING: Battery Open. | ||
| NTF upsEReturnFromBatteryOpen | 1.3.6.1.4.1.935.10.1.2.0.58 | INFORMATION: Return from Battery Open. | ||
| NTF upsEBatteryOverCharge | 1.3.6.1.4.1.935.10.1.2.0.59 | WARNING: Battery Over Charge. | ||
| NTF upsEReturnFromBatteryOverCharge | 1.3.6.1.4.1.935.10.1.2.0.60 | INFORMATION: Return from Battery Over Charge. | ||
| NTF upsEBatteryReverse | 1.3.6.1.4.1.935.10.1.2.0.61 | WARNING: Battery Reverse. | ||
| NTF upsEReturnFromBatteryReverse | 1.3.6.1.4.1.935.10.1.2.0.62 | INFORMATION: Return from Battery Reverse. | ||
| NTF upsEOverloadforewarning | 1.3.6.1.4.1.935.10.1.2.0.63 | WARNING: Overload forewarning. | ||
| NTF upsEReturnFromOverloadforewarning | 1.3.6.1.4.1.935.10.1.2.0.64 | INFORMATION: Return from Overload forewarning. | ||
| NTF upsEOverloadWarning | 1.3.6.1.4.1.935.10.1.2.0.65 | WARNING: Overload Warning. | ||
| NTF upsEReturnFromOverloadWarning | 1.3.6.1.4.1.935.10.1.2.0.66 | INFORMATION: Return from Overload Warning. | ||
| NTF upsEFanLock | 1.3.6.1.4.1.935.10.1.2.0.67 | WARNING: Fan Lock. | ||
| NTF upsEReturnFromFanLock | 1.3.6.1.4.1.935.10.1.2.0.68 | INFORMATION: Return from Fan Lock. | ||
| NTF upsEMaintaincoverisopen | 1.3.6.1.4.1.935.10.1.2.0.69 | WARNING: Maintain cover is open. | ||
| NTF upsEReturnFromMaintaincoverisopen | 1.3.6.1.4.1.935.10.1.2.0.70 | INFORMATION: Return from Maintain cover is open. | ||
| NTF upsEChargerfault | 1.3.6.1.4.1.935.10.1.2.0.71 | WARNING: Charger fault. | ||
| NTF upsEReturnFromChargerfault | 1.3.6.1.4.1.935.10.1.2.0.72 | INFORMATION: Return from Charger fault. | ||
| NTF upsEModulelocationerror | 1.3.6.1.4.1.935.10.1.2.0.73 | WARNING: Module location error. | ||
| NTF upsEReturnFromModulelocationerror | 1.3.6.1.4.1.935.10.1.2.0.74 | INFORMATION: Return from Module location error. | ||
| NTF upsETurnonabnormal | 1.3.6.1.4.1.935.10.1.2.0.75 | WARNING: Turn on abnormal. | ||
| NTF upsEReturnFromTurnonabnormal | 1.3.6.1.4.1.935.10.1.2.0.76 | INFORMATION: Return from Turn on abnormal. | ||
| NTF upsERedundancyloss | 1.3.6.1.4.1.935.10.1.2.0.77 | WARNING: Redundancy loss. | ||
| NTF upsEReturnFromRedundancyloss | 1.3.6.1.4.1.935.10.1.2.0.78 | INFORMATION: Return from Redundancy loss. | ||
| NTF upsEHotSwapActived | 1.3.6.1.4.1.935.10.1.2.0.79 | WARNING: Hot Swap Active. | ||
| NTF upsEReturnFromHotSwapActived | 1.3.6.1.4.1.935.10.1.2.0.80 | INFORMATION: Return from Hot Swap Active. | ||
| NTF upsEBatteryInform | 1.3.6.1.4.1.935.10.1.2.0.81 | WARNING: Battery Inform. | ||
| NTF upsEReturnFromBatteryInform | 1.3.6.1.4.1.935.10.1.2.0.82 | INFORMATION: Return from Battery Inform. | ||
| NTF upsEInspectionInform | 1.3.6.1.4.1.935.10.1.2.0.83 | WARNING: Inspection Inform. | ||
| NTF upsEReturnFromInspectionInform | 1.3.6.1.4.1.935.10.1.2.0.84 | INFORMATION: Return from Inspection Inform. | ||
| NTF upsEGuaranteeInform | 1.3.6.1.4.1.935.10.1.2.0.85 | WARNING: Guarantee Inform. | ||
| NTF upsEReturnFromGuaranteeInform | 1.3.6.1.4.1.935.10.1.2.0.86 | INFORMATION: Return from Guarantee Inform. | ||
| NTF upsETemperatureLow | 1.3.6.1.4.1.935.10.1.2.0.87 | WARNING: Temperature Low. | ||
| NTF upsEReturnFromTemperatureLow | 1.3.6.1.4.1.935.10.1.2.0.88 | INFORMATION: Return from Temperature Low. | ||
| NTF upsETemperatureHigh | 1.3.6.1.4.1.935.10.1.2.0.89 | WARNING: Temperature High. | ||
| NTF upsEReturnFromTemperatureHigh | 1.3.6.1.4.1.935.10.1.2.0.90 | INFORMATION: Return from Temperature High. | ||
| NTF upsEBatteryOverTemperature | 1.3.6.1.4.1.935.10.1.2.0.91 | WARNING: Battery Over Temperature. | ||
| NTF upsEReturnFromBatteryOverTemperature | 1.3.6.1.4.1.935.10.1.2.0.92 | INFORMATION: Return from Battery Over Temperature. | ||
| NTF upsEFanMaintainInform | 1.3.6.1.4.1.935.10.1.2.0.93 | WARNING: Fan Maintain Inform. | ||
| NTF upsEReturnFromFanMaintainInform | 1.3.6.1.4.1.935.10.1.2.0.94 | INFORMATION: Return from Fan Maintain Inform. | ||
| NTF upsEBusCapacitanceMaintainInform | 1.3.6.1.4.1.935.10.1.2.0.95 | WARNING: Bus Capacitance Maintain Inform. | ||
| NTF upsEReturnFromBusCapacitanceMaintainInform | 1.3.6.1.4.1.935.10.1.2.0.96 | INFORMATION: Return from Bus Capacitance Maintain Inform. | ||
| NTF upsESystemOverCapacity | 1.3.6.1.4.1.935.10.1.2.0.97 | WARNING: System Over Capacity. | ||
| NTF upsEReturnFromSystemOverCapacity | 1.3.6.1.4.1.935.10.1.2.0.98 | INFORMATION: Return from System Over Capacity. | ||
| NTF upsEBelowCapacityLimit | 1.3.6.1.4.1.935.10.1.2.0.123 | SEVERE: The UPS batteries capacity is lower than setting limit. | ||
| NTF upsENotBelowCapacityLimit | 1.3.6.1.4.1.935.10.1.2.0.124 | INFORMATION: The UPS batteries capacity is not lower than setting limit. | ||
| NTF upsEBelowRemainTimeLimit | 1.3.6.1.4.1.935.10.1.2.0.125 | SEVERE: The UPS batteries backup time is below the setting limit. | ||
| NTF upsENotBelowRemainTimeLimit | 1.3.6.1.4.1.935.10.1.2.0.126 | INFORMATION: The UPS batteries backup time is not below the setting limit. | ||
| NTF upsELoadSegment1Off | 1.3.6.1.4.1.935.10.1.2.0.127 | WARNING: Load segment 1 is off. | ||
| NTF upsELoadSegment1On | 1.3.6.1.4.1.935.10.1.2.0.128 | INFORMATION: Load segment 1 is on. | ||
| NTF upsELoadSegment2Off | 1.3.6.1.4.1.935.10.1.2.0.129 | WARNING: Load segment 2 is off. | ||
| NTF upsELoadSegment2On | 1.3.6.1.4.1.935.10.1.2.0.130 | INFORMATION: Load segment 2 is on. |
RFC description
UPS system MIB for managing uninterruptible power supplies, including battery, power converter, load segment, environmental monitoring, and battery testing.
Start monitoring Three-phase UPS system with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.