EPPC-MIB :: upsESystemTemperature

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › EPPC-MIB › upsESystemTemperature

upsESystemTemperature

Module: EPPC-MIB

OID (symbolic): EPPC-MIB::upsESystemTemperature

OID (numeric): 1.3.6.1.4.1.935.10.1.1.2.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The temperature of UPS presented in 0.1 degree.

What is upsESystemTemperature?

Read-only internal UPS temperature reported in tenths of a degree, so a value of 285 means 28.5 degrees. Trend this to catch a UPS that is overheating before it trips a thermal shutdown.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.10.1.1.2.2
snmpwalk -v2c -c public <target> EPPC-MIB::upsESystemTemperature

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.935.10.1.1.2.2.1
snmpget -v2c -c public <target> EPPC-MIB::upsESystemTemperature.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> upsESystemTemperature.1

Start monitoring Three-phase UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EPPC-MIB::upsESystemTemperature OID value, configure state conditions and alerts, and monitor any Three-phase UPS system from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.935ppcEPPC-MIB
1.3.6.1.4.1.935.10deviceEPPC-MIB
1.3.6.1.4.1.935.10.1upsAgentEPPC-MIB
1.3.6.1.4.1.935.10.1.1upsEEPPC-MIB
1.3.6.1.4.1.935.10.1.1.2upsESystemSummaryEPPC-MIB
1.3.6.1.4.1.935.10.1.1.2.2upsESystemTemperatureEPPC-MIB