All MIBs › EATON-EPDU-MIB
Organization: Eaton Corporation
Last Updated: 2014--0-9-
Category: Domain: Power/UPS, Vendor: Eaton
Description: Eaton ePDU MIB providing core management objects for Eaton rack power distribution units including power and current monitoring.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is EATON-EPDU-MIB?
EATON-EPDU-MIB is Eaton's core enterprise MIB for its ePDU (Enclosure/rack Power Distribution Unit) product line, providing management objects for monitoring and identifying rack-mounted PDUs used to distribute power to data-center equipment. It exposes unit identification and inventory data (product name, part number, serial number, firmware version, unit name) alongside input power/current monitoring objects and unit-level controls such as LCD display control and a device clock setting. Its primary monitoring value is power infrastructure health: tracking input current and power draw per PDU helps detect overload conditions or a failing circuit, while firmwareVersion and unit inventory data support fleet-wide firmware compliance audits, making this a key MIB for monitoring the health and load of rack power distribution hardware supporting other equipment. It is a self-contained enterprise MIB without heavy reliance on other standard MIBs, though it may be used alongside standard entity-inventory concepts. It is deployed on Eaton ePDU rack-mounted power distribution units in data center and server room environments. Network engineers evaluating or troubleshooting this functionality can download the EATON-EPDU-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in EATON-EPDU-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Eaton ePDU rack power distribution units
Monitoring Examples
A data center operator would poll unitTable/unitEntry (indexed by strappingIndex) for productName, partNumber, serialNumber, and firmwareVersion to inventory each ePDU across a fleet and confirm firmware compliance. Objects under "inputs" would be checked for input current/power readings to detect a PDU input circuit nearing its rated capacity, an early warning sign before a breaker trips, while unitsPresent confirms how many ePDU units the management interface currently sees. lcdControl and clockValue are typically checked or set during unit provisioning rather than as ongoing health indicators.
What Can Be Monitored
- input current/power per PDU
- unit presence/inventory count
- firmware version
- serial number/part number
- unit name
This MIB depends on
Related MIBs
Imported Objects
From EATON-OIDS
| pduAgent | OBJECT-IDENTITY |
From SNMPv2-CONF
| MODULE-COMPLIANCE | |
| NOTIFICATION-GROUP | |
| OBJECT-GROUP |
From SNMPv2-SMI
| Counter32 | |
| Integer32 | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| Unsigned32 |
From SNMPv2-TC
| DateAndTime | |
| DisplayString | |
| TEXTUAL-CONVENTION |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| eatonEpdu | 1.3.6.1.4.1.534.6.6.7 | The MIB module for Eaton ePDUs (Enclosure Power Distribution Units). | ||
| notifications | 1.3.6.1.4.1.534.6.6.7.0 | |||
| NTF notifyUserLogin | 1.3.6.1.4.1.534.6.6.7.0.1 | Sent whenever a user logs in. | ||
| NTF notifyUserLogout | 1.3.6.1.4.1.534.6.6.7.0.2 | Sent whenever a user logs out. | ||
| NTF notifyFailedLogin | 1.3.6.1.4.1.534.6.6.7.0.3 | Sent when someone attempts to log in and fails. On some models, may be sent after three failed login attempts. | ||
| NTF notifyBootUp | 1.3.6.1.4.1.534.6.6.7.0.4 | Sent whenever an ePDU finishes booting up (hard or soft reboot). | ||
| NTF notifyInputVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.11 | Sent whenever an input voltage threshold status changes. | ||
| NTF notifyInputCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.12 | Sent whenever an input current threshold status changes. | ||
| NTF notifyInputFrequencyStatus | 1.3.6.1.4.1.534.6.6.7.0.13 | Sent whenever the input frequency status changes. | ||
| NTF notifyGroupVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.21 | Sent whenever a group voltage threshold status changes. | ||
| NTF notifyGroupCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.22 | Sent whenever a group current threshold status changes. | ||
| NTF notifyGroupBreakerStatus | 1.3.6.1.4.1.534.6.6.7.0.23 | Sent whenever a group status changes to indicate whether the circuit breaker is on or off. | ||
| NTF notifyOutletVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.0.31 | Sent whenever an outlet voltage threshold status changes. | ||
| NTF notifyOutletCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.0.32 | Sent whenever an outlet current threshold status changes. | ||
| NTF notifyOutletControlStatus | 1.3.6.1.4.1.534.6.6.7.0.33 | Sent whenever an outlet state On / Off changes. | ||
| NTF notifyTemperatureThStatus | 1.3.6.1.4.1.534.6.6.7.0.41 | Sent whenever a temperature threshold status changes. | ||
| NTF notifyHumidityThStatus | 1.3.6.1.4.1.534.6.6.7.0.42 | Sent whenever a humidity threshold status changes. | ||
| NTF notifyContactState | 1.3.6.1.4.1.534.6.6.7.0.43 | Sent whenever a contact sensor state changes. | ||
| NTF notifyProbeStatus | 1.3.6.1.4.1.534.6.6.7.0.44 | Sent whenever the environment probe status changes. | ||
| NTF notifyCommunicationStatus | 1.3.6.1.4.1.534.6.6.7.0.51 | Sent whenever the PDU communication status changes. | ||
| NTF notifyInternalStatus | 1.3.6.1.4.1.534.6.6.7.0.52 | Sent whenever the PDU internal status changes. | ||
| NTF notifyTest | 1.3.6.1.4.1.534.6.6.7.0.53 | Sent whenever the trap test feature is used by the communication card. | ||
| NTF notifyStrappingStatus | 1.3.6.1.4.1.534.6.6.7.0.54 | Sent whenever the strapping communication status changes. | ||
| units | 1.3.6.1.4.1.534.6.6.7.1 | |||
| STR unitsPresent | 1.3.6.1.4.1.534.6.6.7.1.1 | DisplayString | read-only | Each unit is identified by a Strapping Index. This object returns a comma-delimited list of the Strapping Indexes of all units present in the strapping group. For example, if units 0, 1, 5, and 7 are present, this value will be '0,1,5,7'. For units that do not support strapping, a Strapping Index of '0' is assumed. |
| unitTable | 1.3.6.1.4.1.534.6.6.7.1.2 | not-accessible | A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object. | |
| unitEntry | 1.3.6.1.4.1.534.6.6.7.1.2.1 | not-accessible | An entry for a PDU. | |
| I32 strappingIndex | 1.3.6.1.4.1.534.6.6.7.1.2.1.1 | Integer32 | accessible-for-notify | For units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'. |
| OCT productName | 1.3.6.1.4.1.534.6.6.7.1.2.1.2 | OCTET STRING | read-only | Name of the product. |
| OCT partNumber | 1.3.6.1.4.1.534.6.6.7.1.2.1.3 | OCTET STRING | read-only | Part number of the unit. |
| OCT serialNumber | 1.3.6.1.4.1.534.6.6.7.1.2.1.4 | OCTET STRING | read-only | Serial number of the unit. |
| OCT firmwareVersion | 1.3.6.1.4.1.534.6.6.7.1.2.1.5 | OCTET STRING | read-only | Firmware version. |
| OCT unitName | 1.3.6.1.4.1.534.6.6.7.1.2.1.6 | OCTET STRING | read-write | Descriptive name for the unit. |
| INT lcdControl | 1.3.6.1.4.1.534.6.6.7.1.2.1.7 | INTEGER | read-write | Control the local LCD. |
| DAT clockValue | 1.3.6.1.4.1.534.6.6.7.1.2.1.8 | DateAndTime | read-write | Clock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only). |
| INT temperatureScale | 1.3.6.1.4.1.534.6.6.7.1.2.1.9 | INTEGER | read-write | Scale used to return temperature objects. |
| INT unitType | 1.3.6.1.4.1.534.6.6.7.1.2.1.10 | INTEGER | read-only | Technical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input and section/group monitoring, outlet switching. Managed (MA) - input, section/group, and outlet monitoring plug outlet switching. |
| I32 inputCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.20 | Integer32 | read-only | Number of inputs on this ePDU. |
| I32 groupCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.21 | Integer32 | read-only | Number of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups. |
| I32 outletCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.22 | Integer32 | read-only | Number of outlets on this ePDU. |
| I32 temperatureCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.23 | Integer32 | read-only | Max number of temperature measurements on this ePDU. |
| I32 humidityCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.24 | Integer32 | read-only | Max number of humidity measurements on this ePDU. |
| I32 contactCount | 1.3.6.1.4.1.534.6.6.7.1.2.1.25 | Integer32 | read-only | Max number of contact sensors on this ePDU. |
| INT communicationStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.30 | INTEGER | read-only | Status of the internal communication with the PDU. |
| INT internalStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.31 | INTEGER | read-only | Status of the internal failure inside the PDU. |
| INT strappingStatus | 1.3.6.1.4.1.534.6.6.7.1.2.1.32 | INTEGER | read-only | Status of the external communication with a strapping unit. |
| OCT userName | 1.3.6.1.4.1.534.6.6.7.1.2.1.40 | OCTET STRING | accessible-for-notify | Username used to log into the PDU. |
| INT commInterface | 1.3.6.1.4.1.534.6.6.7.1.2.1.41 | INTEGER | accessible-for-notify | Communications interface used to log into the PDU. |
| unitControlTable | 1.3.6.1.4.1.534.6.6.7.1.3 | not-accessible | A list of units that have controllable outlets. | |
| unitControlEntry | 1.3.6.1.4.1.534.6.6.7.1.3.1 | not-accessible | An entry for a PDU which has controllable outlets. | |
| I32 unitControlOffCmd | 1.3.6.1.4.1.534.6.6.7.1.3.1.2 | Integer32 | read-write | Unit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| I32 unitControlOnCmd | 1.3.6.1.4.1.534.6.6.7.1.3.1.3 | Integer32 | read-write | Unit-level outlet control command. Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds until the outlet Sequence On command is issued -1 : Cancel a pending unit-level On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| inputs | 1.3.6.1.4.1.534.6.6.7.3 | |||
| inputTable | 1.3.6.1.4.1.534.6.6.7.3.1 | not-accessible | List of inputs to the PDU. | |
| inputEntry | 1.3.6.1.4.1.534.6.6.7.3.1.1 | not-accessible | An entry for a particular input. | |
| I32 inputIndex | 1.3.6.1.4.1.534.6.6.7.3.1.1.1 | Integer32 | accessible-for-notify | A unique value for each input. Its value ranges from 1 to inputCount. |
| INT inputType | 1.3.6.1.4.1.534.6.6.7.3.1.1.2 | INTEGER | read-only | Type of input - single phase, split phase, three phase delta, or three phase wye. |
| I32 inputFrequency | 1.3.6.1.4.1.534.6.6.7.3.1.1.3 | Integer32 | read-only | Units are 0.1 Hz; divide by ten to get Hz. |
| INT inputFrequencyStatus | 1.3.6.1.4.1.534.6.6.7.3.1.1.4 | INTEGER | read-only | Status of the measured input frequency relative to the nominal frequency and the admitted tolerance. |
| I32 inputVoltageCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.5 | Integer32 | read-only | Number of input voltage measurements on this ePDU. |
| I32 inputCurrentCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.6 | Integer32 | read-only | Number of input current measurements on this ePDU. |
| I32 inputPowerCount | 1.3.6.1.4.1.534.6.6.7.3.1.1.7 | Integer32 | read-only | Number of rows in the inputPowerTable. |
| INT inputPlugType | 1.3.6.1.4.1.534.6.6.7.3.1.1.8 | INTEGER | read-only | Identifies which plug is on the input. |
| inputVoltageTable | 1.3.6.1.4.1.534.6.6.7.3.2 | not-accessible | A list of input voltage measurements. The number of entries is given by inputVoltageCount. | |
| inputVoltageEntry | 1.3.6.1.4.1.534.6.6.7.3.2.1 | not-accessible | An entry for a particular input voltage measurement. | |
| I32 inputVoltageIndex | 1.3.6.1.4.1.534.6.6.7.3.2.1.1 | Integer32 | accessible-for-notify | A unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount. |
| INT inputVoltageMeasType | 1.3.6.1.4.1.534.6.6.7.3.2.1.2 | INTEGER | read-only | Value indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
| I32 inputVoltage | 1.3.6.1.4.1.534.6.6.7.3.2.1.3 | Integer32 | read-only | An input voltage measurement value. Units are millivolts. |
| INT inputVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.3.2.1.4 | INTEGER | read-only | Status of the measured input voltage relative to the configured thresholds. |
| I32 inputVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.3.2.1.5 | Integer32 | read-write | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 inputVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.3.2.1.6 | Integer32 | read-write | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 inputVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.3.2.1.7 | Integer32 | read-write | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 inputVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.3.2.1.8 | Integer32 | read-write | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| inputCurrentTable | 1.3.6.1.4.1.534.6.6.7.3.3 | not-accessible | A list of input current measurements. The number of entries is given by inputCurrentCount. | |
| inputCurrentEntry | 1.3.6.1.4.1.534.6.6.7.3.3.1 | not-accessible | An entry for a particular input current measurement. | |
| I32 inputCurrentIndex | 1.3.6.1.4.1.534.6.6.7.3.3.1.1 | Integer32 | accessible-for-notify | A unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount. |
| INT inputCurrentMeasType | 1.3.6.1.4.1.534.6.6.7.3.3.1.2 | INTEGER | read-only | Which input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3. |
| I32 inputCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.3.3.1.3 | Integer32 | read-only | Rated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps. |
| I32 inputCurrent | 1.3.6.1.4.1.534.6.6.7.3.3.1.4 | Integer32 | read-only | An input current measurement value. Units are milliamps. |
| INT inputCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.3.3.1.5 | INTEGER | read-only | Status of the measured input current relative to the configured thresholds. |
| I32 inputCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.3.3.1.6 | Integer32 | read-write | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 inputCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.3.3.1.7 | Integer32 | read-write | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 inputCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.3.3.1.8 | Integer32 | read-write | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 inputCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.3.3.1.9 | Integer32 | read-write | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 inputCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.3.3.1.10 | Integer32 | read-only | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. |
| I32 inputCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.3.3.1.11 | Integer32 | read-only | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
| inputPowerTable | 1.3.6.1.4.1.534.6.6.7.3.4 | not-accessible | A list of input power measurements. The number of entries is given by inputPowerCount. | |
| inputPowerEntry | 1.3.6.1.4.1.534.6.6.7.3.4.1 | not-accessible | An entry for an input power measurement. | |
| I32 inputPowerIndex | 1.3.6.1.4.1.534.6.6.7.3.4.1.1 | Integer32 | not-accessible | A unique value for each input power measurement. Its value ranges from 1 to inputPowerCount. |
| INT inputPowerMeasType | 1.3.6.1.4.1.534.6.6.7.3.4.1.2 | INTEGER | read-only | Value indicates what is being measured in this table row. |
| I32 inputVA | 1.3.6.1.4.1.534.6.6.7.3.4.1.3 | Integer32 | read-only | An input VA value. Units are VA. A negative value indicates that this object is not available. |
| I32 inputWatts | 1.3.6.1.4.1.534.6.6.7.3.4.1.4 | Integer32 | read-only | An input Watts value. Units are Watts. A negative value indicates that this object is not available. |
| U32 inputWh | 1.3.6.1.4.1.534.6.6.7.3.4.1.5 | Unsigned32 | read-write | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. |
| UNI inputWhTimer | 1.3.6.1.4.1.534.6.6.7.3.4.1.6 | UnixTimeStamp | read-only | Timestamp of when input Watt-hours (inputWh) was last reset. |
| I32 inputPowerFactor | 1.3.6.1.4.1.534.6.6.7.3.4.1.7 | Integer32 | read-only | An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
| I32 inputVAR | 1.3.6.1.4.1.534.6.6.7.3.4.1.8 | Integer32 | read-only | An input VAR value. Units are VAR. A negative value indicates that this object is not available. |
| inputTotalPowerTable | 1.3.6.1.4.1.534.6.6.7.3.5 | not-accessible | A list of total input power measurements. | |
| inputTotalPowerEntry | 1.3.6.1.4.1.534.6.6.7.3.5.1 | not-accessible | An entry for a total input power measurement. | |
| I32 inputTotalVA | 1.3.6.1.4.1.534.6.6.7.3.5.1.3 | Integer32 | read-only | An input VA value. Units are VA. A negative value indicates that this object is not available. |
| I32 inputTotalWatts | 1.3.6.1.4.1.534.6.6.7.3.5.1.4 | Integer32 | read-only | An input Watts value. Units are Watts. A negative value indicates that this object is not available. |
| U32 inputTotalWh | 1.3.6.1.4.1.534.6.6.7.3.5.1.5 | Unsigned32 | read-write | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. |
| UNI inputTotalWhTimer | 1.3.6.1.4.1.534.6.6.7.3.5.1.6 | UnixTimeStamp | read-only | Timestamp of when input Watt-hours (inputWh) was last reset. |
| I32 inputTotalPowerFactor | 1.3.6.1.4.1.534.6.6.7.3.5.1.7 | Integer32 | read-only | An input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
| I32 inputTotalVAR | 1.3.6.1.4.1.534.6.6.7.3.5.1.8 | Integer32 | read-only | An input VAR value. Units are VAR. A negative value indicates that this object is not available. |
| groups | 1.3.6.1.4.1.534.6.6.7.5 | |||
| groupTable | 1.3.6.1.4.1.534.6.6.7.5.1 | not-accessible | A list of groups. The number of entries is given by groupCount. | |
| groupEntry | 1.3.6.1.4.1.534.6.6.7.5.1.1 | not-accessible | An entry for a particular group. | |
| I32 groupIndex | 1.3.6.1.4.1.534.6.6.7.5.1.1.1 | Integer32 | accessible-for-notify | A unique value for each group. Its value ranges from 1 to groupCount. |
| STR groupID | 1.3.6.1.4.1.534.6.6.7.5.1.1.2 | DisplayString | read-only | Alphanumeric designator for the group. This value may be written on the face of the unit. |
| OCT groupName | 1.3.6.1.4.1.534.6.6.7.5.1.1.3 | OCTET STRING | read-write | A descriptive name for the group. |
| INT groupType | 1.3.6.1.4.1.534.6.6.7.5.1.1.4 | INTEGER | read-only | The type of the group. |
| INT groupBreakerStatus | 1.3.6.1.4.1.534.6.6.7.5.1.1.5 | INTEGER | read-only | Only applicable to breaker-groups. Indicates whether a breaker is turned off or on. |
| I32 groupChildCount | 1.3.6.1.4.1.534.6.6.7.5.1.1.6 | Integer32 | read-only | Number of children for this group. |
| groupChildTable | 1.3.6.1.4.1.534.6.6.7.5.2 | not-accessible | A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group. | |
| groupChildEntry | 1.3.6.1.4.1.534.6.6.7.5.2.1 | not-accessible | An entry for a particular child. | |
| I32 groupChildIndex | 1.3.6.1.4.1.534.6.6.7.5.2.1.1 | Integer32 | not-accessible | A unique value for each child. Its value ranges from 1 to groupChildCount. |
| INT groupChildType | 1.3.6.1.4.1.534.6.6.7.5.2.1.2 | INTEGER | read-only | The type of the child. |
| OID groupChildOID | 1.3.6.1.4.1.534.6.6.7.5.2.1.3 | OBJECT IDENTIFIER | read-only | Object ID of a child object. |
| groupVoltageTable | 1.3.6.1.4.1.534.6.6.7.5.3 | not-accessible | A list of group voltage measurements. There can be only one voltage measurement for each group. | |
| groupVoltageEntry | 1.3.6.1.4.1.534.6.6.7.5.3.1 | not-accessible | An entry for a group voltage measurement. | |
| INT groupVoltageMeasType | 1.3.6.1.4.1.534.6.6.7.5.3.1.2 | INTEGER | read-only | Value indicates what voltage is being measured in this table row. |
| I32 groupVoltage | 1.3.6.1.4.1.534.6.6.7.5.3.1.3 | Integer32 | read-only | Units are millivolts. |
| INT groupVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.5.3.1.4 | INTEGER | read-only | Status of the measured group voltage relative to the configured thresholds. |
| I32 groupVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.5.3.1.5 | Integer32 | read-write | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 groupVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.5.3.1.6 | Integer32 | read-write | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 groupVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.5.3.1.7 | Integer32 | read-write | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 groupVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.5.3.1.8 | Integer32 | read-write | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| groupCurrentTable | 1.3.6.1.4.1.534.6.6.7.5.4 | not-accessible | A list of group current measurements. There can be only one current measurement for each group. | |
| groupCurrentEntry | 1.3.6.1.4.1.534.6.6.7.5.4.1 | not-accessible | An entry for a group current measurement. | |
| I32 groupCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.5.4.1.2 | Integer32 | read-only | Rated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). |
| I32 groupCurrent | 1.3.6.1.4.1.534.6.6.7.5.4.1.3 | Integer32 | read-only | A group current measurement value. Units are milliamps. |
| INT groupCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.5.4.1.4 | INTEGER | read-only | Status of the measured group current relative to the configured thresholds. |
| I32 groupCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.5.4.1.5 | Integer32 | read-write | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 groupCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.5.4.1.6 | Integer32 | read-write | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 groupCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.5.4.1.7 | Integer32 | read-write | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 groupCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.5.4.1.8 | Integer32 | read-write | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 groupCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.5.4.1.9 | Integer32 | read-only | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. |
| I32 groupCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.5.4.1.10 | Integer32 | read-only | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
| groupPowerTable | 1.3.6.1.4.1.534.6.6.7.5.5 | not-accessible | A list of group power measurements. There can be only one power measurement for each group. | |
| groupPowerEntry | 1.3.6.1.4.1.534.6.6.7.5.5.1 | not-accessible | An entry for a group power measurement. | |
| I32 groupVA | 1.3.6.1.4.1.534.6.6.7.5.5.1.2 | Integer32 | read-only | A group VA value. Units are VA. A negative value indicates that this object is not available. |
| I32 groupWatts | 1.3.6.1.4.1.534.6.6.7.5.5.1.3 | Integer32 | read-only | A group Watts value. Units are Watts. A negative value indicates that this object is not available. |
| U32 groupWh | 1.3.6.1.4.1.534.6.6.7.5.5.1.4 | Unsigned32 | read-write | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. |
| UNI groupWhTimer | 1.3.6.1.4.1.534.6.6.7.5.5.1.5 | UnixTimeStamp | read-only | Timestamp of when group Watt-hours (groupWh) was last reset. |
| I32 groupPowerFactor | 1.3.6.1.4.1.534.6.6.7.5.5.1.6 | Integer32 | read-only | A group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
| I32 groupVAR | 1.3.6.1.4.1.534.6.6.7.5.5.1.7 | Integer32 | read-only | A group VAR value. Units are VAR. A negative value indicates that this object is not available. |
| groupControlTable | 1.3.6.1.4.1.534.6.6.7.5.6 | not-accessible | A list of controllable groups. | |
| groupControlEntry | 1.3.6.1.4.1.534.6.6.7.5.6.1 | not-accessible | An entry for a controllable group. | |
| INT groupControlStatus | 1.3.6.1.4.1.534.6.6.7.5.6.1.2 | INTEGER | read-only | Current state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states. |
| I32 groupControlOffCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.3 | Integer32 | read-write | Group-level outlet control command. Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| I32 groupControl0nCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.4 | Integer32 | read-write | Group-level outlet control command. Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| I32 groupControlRebootCmd | 1.3.6.1.4.1.534.6.6.7.5.6.1.5 | Integer32 | read-write | Group-level outlet control command. For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending group-level Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| outlets | 1.3.6.1.4.1.534.6.6.7.6 | |||
| outletTable | 1.3.6.1.4.1.534.6.6.7.6.1 | not-accessible | A list of outlets. The number of entries is given by outletCount. | |
| outletEntry | 1.3.6.1.4.1.534.6.6.7.6.1.1 | not-accessible | An entry for a particular outlet. | |
| I32 outletIndex | 1.3.6.1.4.1.534.6.6.7.6.1.1.1 | Integer32 | accessible-for-notify | A unique value for each outlet. its value ranges from 1 to outletCount. |
| STR outletID | 1.3.6.1.4.1.534.6.6.7.6.1.1.2 | DisplayString | read-only | Alphanumeric designator for the outlet. |
| OCT outletName | 1.3.6.1.4.1.534.6.6.7.6.1.1.3 | OCTET STRING | read-write | A descriptive name for the outlet. |
| I32 outletParentCount | 1.3.6.1.4.1.534.6.6.7.6.1.1.4 | Integer32 | read-only | Number of parents for this outlet. |
| INT outletType | 1.3.6.1.4.1.534.6.6.7.6.1.1.5 | INTEGER | read-only | The physical type of outlet. |
| outletParentTable | 1.3.6.1.4.1.534.6.6.7.6.2 | not-accessible | A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child. | |
| outletParentEntry | 1.3.6.1.4.1.534.6.6.7.6.2.1 | not-accessible | An entry for a particular parent. | |
| I32 outletParentIndex | 1.3.6.1.4.1.534.6.6.7.6.2.1.1 | Integer32 | not-accessible | A unique value for each parent. Its value ranges from 1 to outletParentCount. |
| INT outletParentType | 1.3.6.1.4.1.534.6.6.7.6.2.1.2 | INTEGER | read-only | The type of the parent. |
| OID outletParentOID | 1.3.6.1.4.1.534.6.6.7.6.2.1.3 | OBJECT IDENTIFIER | read-only | Object ID of a parent object. |
| outletVoltageTable | 1.3.6.1.4.1.534.6.6.7.6.3 | not-accessible | A list of outlet voltage measurements. | |
| outletVoltageEntry | 1.3.6.1.4.1.534.6.6.7.6.3.1 | not-accessible | An entry for an outlet voltage measurement. | |
| I32 outletVoltage | 1.3.6.1.4.1.534.6.6.7.6.3.1.2 | Integer32 | read-only | Units are millivolts. |
| INT outletVoltageThStatus | 1.3.6.1.4.1.534.6.6.7.6.3.1.3 | INTEGER | read-only | Status of the measured outlet voltage relative to the configured thresholds. |
| I32 outletVoltageThLowerWarning | 1.3.6.1.4.1.534.6.6.7.6.3.1.4 | Integer32 | read-write | Lower warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 outletVoltageThLowerCritical | 1.3.6.1.4.1.534.6.6.7.6.3.1.5 | Integer32 | read-write | Lower critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 outletVoltageThUpperWarning | 1.3.6.1.4.1.534.6.6.7.6.3.1.6 | Integer32 | read-write | Upper warning threshold. Units are millivolts. A negative value indicates that this object is not available. |
| I32 outletVoltageThUpperCritical | 1.3.6.1.4.1.534.6.6.7.6.3.1.7 | Integer32 | read-write | Upper critical threshold. Units are millivolts. A negative value indicates that this object is not available. |
| outletCurrentTable | 1.3.6.1.4.1.534.6.6.7.6.4 | not-accessible | A list of outlet current measurements. | |
| outletCurrentEntry | 1.3.6.1.4.1.534.6.6.7.6.4.1 | not-accessible | An entry for an outlet current measurement. | |
| I32 outletCurrentCapacity | 1.3.6.1.4.1.534.6.6.7.6.4.1.2 | Integer32 | read-only | Rated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown. |
| I32 outletCurrent | 1.3.6.1.4.1.534.6.6.7.6.4.1.3 | Integer32 | read-only | An outlet current measurement value. Units are milliamps. |
| INT outletCurrentThStatus | 1.3.6.1.4.1.534.6.6.7.6.4.1.4 | INTEGER | read-only | Status of the measured outlet current relative to the configured thresholds. |
| I32 outletCurrentThLowerWarning | 1.3.6.1.4.1.534.6.6.7.6.4.1.5 | Integer32 | read-write | Lower warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 outletCurrentThLowerCritical | 1.3.6.1.4.1.534.6.6.7.6.4.1.6 | Integer32 | read-write | Lower critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 outletCurrentThUpperWarning | 1.3.6.1.4.1.534.6.6.7.6.4.1.7 | Integer32 | read-write | Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 outletCurrentThUpperCritical | 1.3.6.1.4.1.534.6.6.7.6.4.1.8 | Integer32 | read-write | Upper critical threshold. Units are milliamps. A negative value indicates that this object is not available. |
| I32 outletCurrentCrestFactor | 1.3.6.1.4.1.534.6.6.7.6.4.1.9 | Integer32 | read-only | Current crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. |
| I32 outletCurrentPercentLoad | 1.3.6.1.4.1.534.6.6.7.6.4.1.10 | Integer32 | read-only | Current percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
| outletPowerTable | 1.3.6.1.4.1.534.6.6.7.6.5 | not-accessible | A list of outlet power measurements. | |
| outletPowerEntry | 1.3.6.1.4.1.534.6.6.7.6.5.1 | not-accessible | An entry for an outlet power measurement. | |
| I32 outletVA | 1.3.6.1.4.1.534.6.6.7.6.5.1.2 | Integer32 | read-only | An outlet VA value. Units are VA. A negative value indicates that this object is not available. |
| I32 outletWatts | 1.3.6.1.4.1.534.6.6.7.6.5.1.3 | Integer32 | read-only | An outlet Watts value. Units are Watts. A negative value indicates that this object is not available. |
| U32 outletWh | 1.3.6.1.4.1.534.6.6.7.6.5.1.4 | Unsigned32 | read-write | Units are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. |
| UNI outletWhTimer | 1.3.6.1.4.1.534.6.6.7.6.5.1.5 | UnixTimeStamp | read-only | Timestamp of when outlet Watt-hours (outletWh) was last reset. |
| I32 outletPowerFactor | 1.3.6.1.4.1.534.6.6.7.6.5.1.6 | Integer32 | read-only | An outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
| I32 outletVAR | 1.3.6.1.4.1.534.6.6.7.6.5.1.7 | Integer32 | read-only | An outlet VAR value. Units are VAR. A negative value indicates that this object is not available. |
| outletControlTable | 1.3.6.1.4.1.534.6.6.7.6.6 | not-accessible | A list of controllable outlets. | |
| outletControlEntry | 1.3.6.1.4.1.534.6.6.7.6.6.1 | not-accessible | An entry for a controllable outlet. | |
| INT outletControlStatus | 1.3.6.1.4.1.534.6.6.7.6.6.1.2 | INTEGER | read-only | Current state of a controlled outlet. |
| I32 outletControlOffCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.3 | Integer32 | read-write | Outlet control command. Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet Off command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| I32 outletControlOnCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.4 | Integer32 | read-write | Outlet control command. Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet On command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| I32 outletControlRebootCmd | 1.3.6.1.4.1.534.6.6.7.6.6.1.5 | Integer32 | read-write | Outlet control command. For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn back On. For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime seconds from when the command is issued. 0-n : Time in seconds until the Reboot command is issued -1 : Cancel a pending outlet Reboot command When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command. Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control commands. These will respond with an error if a command value of > 0 is written to this object. |
| INT outletControlPowerOnState | 1.3.6.1.4.1.534.6.6.7.6.6.1.6 | INTEGER | read-write | Determines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was lost. If the state was ON, should sequence back ON in line with outletControlSequenceTime. |
| I32 outletControlSequenceDelay | 1.3.6.1.4.1.534.6.6.7.6.6.1.7 | Integer32 | read-write | Time delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence On commands. |
| I32 outletControlRebootOffTime | 1.3.6.1.4.1.534.6.6.7.6.6.1.8 | Integer32 | read-write | Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command. |
| INT outletControlSwitchable | 1.3.6.1.4.1.534.6.6.7.6.6.1.9 | INTEGER | read-write | Determines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled. |
| I32 outletControlShutoffDelay | 1.3.6.1.4.1.534.6.6.7.6.6.1.10 | Integer32 | read-write | Time delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd. |
| environmental | 1.3.6.1.4.1.534.6.6.7.7 | |||
| temperatureTable | 1.3.6.1.4.1.534.6.6.7.7.1 | not-accessible | A list of temperature probe measurements. The number of entries is given by temperatureCount. | |
| temperatureEntry | 1.3.6.1.4.1.534.6.6.7.7.1.1 | not-accessible | An entry for a temperature measurement. | |
| I32 temperatureIndex | 1.3.6.1.4.1.534.6.6.7.7.1.1.1 | Integer32 | accessible-for-notify | A unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount. |
| OCT temperatureName | 1.3.6.1.4.1.534.6.6.7.7.1.1.2 | OCTET STRING | read-write | A descriptive name for the temperature probe. |
| INT temperatureProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.1.1.3 | INTEGER | read-only | Indicates whether a probe is connected or not. |
| I32 temperatureValue | 1.3.6.1.4.1.534.6.6.7.7.1.1.4 | Integer32 | read-only | Units are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. |
| INT temperatureThStatus | 1.3.6.1.4.1.534.6.6.7.7.1.1.5 | INTEGER | read-only | Status of the measured temperature relative to the configured thresholds. |
| I32 temperatureThLowerWarning | 1.3.6.1.4.1.534.6.6.7.7.1.1.6 | Integer32 | read-write | Lower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| I32 temperatureThLowerCritical | 1.3.6.1.4.1.534.6.6.7.7.1.1.7 | Integer32 | read-write | Lower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| I32 temperatureThUpperWarning | 1.3.6.1.4.1.534.6.6.7.7.1.1.8 | Integer32 | read-write | Upper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| I32 temperatureThUpperCritical | 1.3.6.1.4.1.534.6.6.7.7.1.1.9 | Integer32 | read-write | Upper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. |
| humidityTable | 1.3.6.1.4.1.534.6.6.7.7.2 | not-accessible | A list of humidity probe measurements. The number of entries is given by humidityCount. | |
| humidityEntry | 1.3.6.1.4.1.534.6.6.7.7.2.1 | not-accessible | An entry for a humidity measurement. | |
| I32 humidityIndex | 1.3.6.1.4.1.534.6.6.7.7.2.1.1 | Integer32 | accessible-for-notify | A unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount. |
| OCT humidityName | 1.3.6.1.4.1.534.6.6.7.7.2.1.2 | OCTET STRING | read-write | A descriptive name for the humidity probe. |
| INT humidityProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.2.1.3 | INTEGER | read-only | Indicates whether a probe is connected or not. |
| I32 humidityValue | 1.3.6.1.4.1.534.6.6.7.7.2.1.4 | Integer32 | read-only | Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH. |
| INT humidityThStatus | 1.3.6.1.4.1.534.6.6.7.7.2.1.5 | INTEGER | read-only | Status of the measured humidity relative to the configured thresholds. |
| I32 humidityThLowerWarning | 1.3.6.1.4.1.534.6.6.7.7.2.1.6 | Integer32 | read-write | Lower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| I32 humidityThLowerCritical | 1.3.6.1.4.1.534.6.6.7.7.2.1.7 | Integer32 | read-write | Lower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| I32 humidityThUpperWarning | 1.3.6.1.4.1.534.6.6.7.7.2.1.8 | Integer32 | read-write | Upper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| I32 humidityThUpperCritical | 1.3.6.1.4.1.534.6.6.7.7.2.1.9 | Integer32 | read-write | Upper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. |
| contactTable | 1.3.6.1.4.1.534.6.6.7.7.3 | not-accessible | A list of contact sensors. The number of entries is given by contactCount. | |
| contactEntry | 1.3.6.1.4.1.534.6.6.7.7.3.1 | not-accessible | An entry for a contact sensor | |
| I32 contactIndex | 1.3.6.1.4.1.534.6.6.7.7.3.1.1 | Integer32 | accessible-for-notify | A unique value for each contact sensor. Its value ranges from 1 to contactCount. |
| OCT contactName | 1.3.6.1.4.1.534.6.6.7.7.3.1.2 | OCTET STRING | read-write | A descriptive name for the contact sensor. |
| INT contactProbeStatus | 1.3.6.1.4.1.534.6.6.7.7.3.1.3 | INTEGER | read-only | Indicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. |
| INT contactState | 1.3.6.1.4.1.534.6.6.7.7.3.1.4 | INTEGER | read-only | The state of the contact sensor. |
| eatonEpduCompliances | 1.3.6.1.4.1.534.6.6.7.25.1 | The requirements for conforming to the ePDU MIB. | ||
| objectGroups | 1.3.6.1.4.1.534.6.6.7.25.5 | |||
| epduRequiredGroup | 1.3.6.1.4.1.534.6.6.7.25.5.1 | Minimal objects are required to conform to this MIB. | ||
| epduOptionalGroup | 1.3.6.1.4.1.534.6.6.7.25.5.2 | Most objects in this MIB are optional. | ||
| epduNotifyGroup | 1.3.6.1.4.1.534.6.6.7.25.5.3 | These notifications will be supported depending on the features of the ePDU. Check the web interface for options to turn these notifications on/off. If an option is not listed, then the ePDU likely does not support that notification. |
RFC description
Eaton vendor-private MIB for ePDU (intelligent Power Distribution Unit) power monitoring, metering, and outlet control.