All MIBs › GEPARALLELUPS-MIB
Organization: GE Digital Energy
Last Updated: 2010-07-05
Category: Domain: Power/UPS, Hardware and Environment, Vendor: GE
Description: GE Digital Energy MIB for parallel-configured UPS systems monitoring combined power output and redundancy status.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is GEPARALLELUPS-MIB?
GEPARALLELUPS-MIB is a vendor MIB from GE Digital Energy for uninterruptible power supply systems configured in parallel (redundant) arrangements. It exposes UPS identity data (manufacturer, model, serial number, software/firmware and communications protocol versions) plus discovery information about which UPS units are present via geDiscoveredUPSsMask. It is fundamentally a hardware status and power-health monitoring MIB: administrators use upsIdentOperatingTime to track uptime/runtime and rely on the identity objects to confirm firmware and agent versions are current across all paralleled units, which is critical for detecting a failed or unsynchronized member of the redundant group. It commonly parallels the conventions of the standard UPS-MIB (RFC 1628) even though it is implemented as a GE-specific module. It is deployed in data center or critical-facility power protection setups where multiple UPS units are combined in parallel for capacity or redundancy. Engineers can download the GEPARALLELUPS-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in GEPARALLELUPS-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- GE Digital Energy parallel/redundant UPS system
Monitoring Examples
An operator would read geDiscoveredUPSsMask to enumerate which UPS units in the parallel bank are currently detected, then query each unit's upsIdentModel, upsIdentUPSSerialNumber, and upsIdentUPSSoftwareVersion to confirm consistent hardware and firmware across the array. upsIdentOperatingTime shows how long each UPS has been running, and a value that resets unexpectedly could indicate an unplanned reboot or failover event. upsIdentAttachedDevices and upsIdentAgentSoftwareVersion help verify the SNMP management agent is healthy and correctly reporting the load attached to the UPS.
What Can Be Monitored
- discovered UPS units in the parallel array
- UPS model and serial number
- UPS and agent firmware/software version
- UPS operating time/uptime
- attached device count
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-SMI
| Counter32 | |
| Gauge32 | |
| Integer32 | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-IDENTITY | |
| OBJECT-TYPE | |
| Unsigned32 | |
| enterprises |
From SNMPv2-TC
| AutonomousType | |
| DisplayString | |
| TEXTUAL-CONVENTION | |
| TestAndIncr | |
| TimeInterval | |
| TimeStamp |
How to Use in IPNetwork Monitor
Example using upsInputLineBads OID:
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| imv | 1.3.6.1.4.1.818 | The MIB module to describe GE Digital Energy Uninterruptible Power Supplies. | ||
| geHardware | 1.3.6.1.4.1.818.1 | |||
| geUPS | 1.3.6.1.4.1.818.1.1 | |||
| I32 geDiscoveredUPSsMask | 1.3.6.1.4.1.818.1.1.1 | Integer32 | read-only | Reading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp branches 11-18 as follows: 1 FirstUPS alive 2 SecondUPS alive 4 ThirdUPS alive 8 FourthUPS alive 16 FifthUPS alive 32 SixthUPS alive 64 SeventhUPS alive 128 EigthUPS alive Since the management software should always monitor the GenericUPS branch (10), this value has no meaning for single upses (which provide values on that snmp branch), and should be set to zero in that case. |
| STR geRequestPacket | 1.3.6.1.4.1.818.1.1.2 | DisplayString | read-write | Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a remote place. |
| STR geReplyPacket | 1.3.6.1.4.1.818.1.1.3 | DisplayString | read-only | Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased. |
| geGenericUPS | 1.3.6.1.4.1.818.1.1.10 | |||
| upsIdent | 1.3.6.1.4.1.818.1.1.10.1 | |||
| STR upsIdentManufacturer | 1.3.6.1.4.1.818.1.1.10.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModel | 1.3.6.1.4.1.818.1.1.10.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersion | 1.3.6.1.4.1.818.1.1.10.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersion | 1.3.6.1.4.1.818.1.1.10.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentName | 1.3.6.1.4.1.818.1.1.10.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevices | 1.3.6.1.4.1.818.1.1.10.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumber | 1.3.6.1.4.1.818.1.1.10.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersion | 1.3.6.1.4.1.818.1.1.10.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTime | 1.3.6.1.4.1.818.1.1.10.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBattery | 1.3.6.1.4.1.818.1.1.10.2 | |||
| INT upsBatteryStatus | 1.3.6.1.4.1.818.1.1.10.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBattery | 1.3.6.1.4.1.818.1.1.10.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemaining | 1.3.6.1.4.1.818.1.1.10.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemaining | 1.3.6.1.4.1.818.1.1.10.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltage | 1.3.6.1.4.1.818.1.1.10.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrent | 1.3.6.1.4.1.818.1.1.10.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperature | 1.3.6.1.4.1.818.1.1.10.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipple | 1.3.6.1.4.1.818.1.1.10.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInput | 1.3.6.1.4.1.818.1.1.10.3 | |||
| C32 upsInputLineBadsEx | 1.3.6.1.4.1.818.1.1.10.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLines | 1.3.6.1.4.1.818.1.1.10.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputTable | 1.3.6.1.4.1.818.1.1.10.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputEntry | 1.3.6.1.4.1.818.1.1.10.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndex | 1.3.6.1.4.1.818.1.1.10.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequency | 1.3.6.1.4.1.818.1.1.10.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltage | 1.3.6.1.4.1.818.1.1.10.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrent | 1.3.6.1.4.1.818.1.1.10.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePower | 1.3.6.1.4.1.818.1.1.10.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMin | 1.3.6.1.4.1.818.1.1.10.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMax | 1.3.6.1.4.1.818.1.1.10.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutput | 1.3.6.1.4.1.818.1.1.10.4 | |||
| INT upsOutputSource | 1.3.6.1.4.1.818.1.1.10.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequency | 1.3.6.1.4.1.818.1.1.10.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLines | 1.3.6.1.4.1.818.1.1.10.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputTable | 1.3.6.1.4.1.818.1.1.10.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputEntry | 1.3.6.1.4.1.818.1.1.10.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndex | 1.3.6.1.4.1.818.1.1.10.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltage | 1.3.6.1.4.1.818.1.1.10.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrent | 1.3.6.1.4.1.818.1.1.10.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPower | 1.3.6.1.4.1.818.1.1.10.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoad | 1.3.6.1.4.1.818.1.1.10.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactor | 1.3.6.1.4.1.818.1.1.10.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrent | 1.3.6.1.4.1.818.1.1.10.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrent | 1.3.6.1.4.1.818.1.1.10.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypass | 1.3.6.1.4.1.818.1.1.10.5 | |||
| NUM upsBypassFrequency | 1.3.6.1.4.1.818.1.1.10.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLines | 1.3.6.1.4.1.818.1.1.10.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassTable | 1.3.6.1.4.1.818.1.1.10.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassEntry | 1.3.6.1.4.1.818.1.1.10.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndex | 1.3.6.1.4.1.818.1.1.10.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltage | 1.3.6.1.4.1.818.1.1.10.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrent | 1.3.6.1.4.1.818.1.1.10.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPower | 1.3.6.1.4.1.818.1.1.10.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarm | 1.3.6.1.4.1.818.1.1.10.6 | |||
| G32 upsAlarmsPresent | 1.3.6.1.4.1.818.1.1.10.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmTable | 1.3.6.1.4.1.818.1.1.10.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmEntry | 1.3.6.1.4.1.818.1.1.10.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmId | 1.3.6.1.4.1.818.1.1.10.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescr | 1.3.6.1.4.1.818.1.1.10.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTime | 1.3.6.1.4.1.818.1.1.10.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarms | 1.3.6.1.4.1.818.1.1.10.6.3 | |||
| upsAlarmBatteryBad | 1.3.6.1.4.1.818.1.1.10.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBattery | 1.3.6.1.4.1.818.1.1.10.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBattery | 1.3.6.1.4.1.818.1.1.10.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBattery | 1.3.6.1.4.1.818.1.1.10.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBad | 1.3.6.1.4.1.818.1.1.10.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBad | 1.3.6.1.4.1.818.1.1.10.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBad | 1.3.6.1.4.1.818.1.1.10.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverload | 1.3.6.1.4.1.818.1.1.10.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypass | 1.3.6.1.4.1.818.1.1.10.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBad | 1.3.6.1.4.1.818.1.1.10.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequested | 1.3.6.1.4.1.818.1.1.10.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequested | 1.3.6.1.4.1.818.1.1.10.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailed | 1.3.6.1.4.1.818.1.1.10.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOff | 1.3.6.1.4.1.818.1.1.10.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOff | 1.3.6.1.4.1.818.1.1.10.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailure | 1.3.6.1.4.1.818.1.1.10.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailure | 1.3.6.1.4.1.818.1.1.10.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFault | 1.3.6.1.4.1.818.1.1.10.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailed | 1.3.6.1.4.1.818.1.1.10.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLost | 1.3.6.1.4.1.818.1.1.10.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPower | 1.3.6.1.4.1.818.1.1.10.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPending | 1.3.6.1.4.1.818.1.1.10.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminent | 1.3.6.1.4.1.818.1.1.10.6.3.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgress | 1.3.6.1.4.1.818.1.1.10.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOff | 1.3.6.1.4.1.818.1.1.10.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailure | 1.3.6.1.4.1.818.1.1.10.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailure | 1.3.6.1.4.1.818.1.1.10.6.3.27 | A CRC problem on the Highspeed Bus JA is detected. | ||
| upsAlarmConnectivityBusFailure | 1.3.6.1.4.1.818.1.1.10.6.3.28 | A problem on the Connectivity Bus communication is detected | ||
| upsAlarmHighSpeedBusJBCRCFailure | 1.3.6.1.4.1.818.1.1.10.6.3.29 | A CRC problem on the Highspeed Bus JB is detected. | ||
| upsAlarmCurrentSharing | 1.3.6.1.4.1.818.1.1.10.6.3.30 | The System detects an high current sharing on the parallel system | ||
| upsAlarmDCRipple | 1.3.6.1.4.1.818.1.1.10.6.3.31 | The System detects an high ripple voltage on one DC link | ||
| U32 upsAlarmMaskA | 1.3.6.1.4.1.818.1.1.10.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTest | 1.3.6.1.4.1.818.1.1.10.7 | |||
| OID upsTestId | 1.3.6.1.4.1.818.1.1.10.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLock | 1.3.6.1.4.1.818.1.1.10.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummary | 1.3.6.1.4.1.818.1.1.10.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetail | 1.3.6.1.4.1.818.1.1.10.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTime | 1.3.6.1.4.1.818.1.1.10.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTime | 1.3.6.1.4.1.818.1.1.10.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTests | 1.3.6.1.4.1.818.1.1.10.7.7 | |||
| upsTestNoTestsInitiated | 1.3.6.1.4.1.818.1.1.10.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgress | 1.3.6.1.4.1.818.1.1.10.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTest | 1.3.6.1.4.1.818.1.1.10.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTest | 1.3.6.1.4.1.818.1.1.10.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibration | 1.3.6.1.4.1.818.1.1.10.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControl | 1.3.6.1.4.1.818.1.1.10.8 | |||
| INT upsShutdownType | 1.3.6.1.4.1.818.1.1.10.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelay | 1.3.6.1.4.1.818.1.1.10.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelay | 1.3.6.1.4.1.818.1.1.10.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDuration | 1.3.6.1.4.1.818.1.1.10.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestart | 1.3.6.1.4.1.818.1.1.10.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNum | 1.3.6.1.4.1.818.1.1.10.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleTable | 1.3.6.1.4.1.818.1.1.10.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleEntry | 1.3.6.1.4.1.818.1.1.10.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndex | 1.3.6.1.4.1.818.1.1.10.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOff | 1.3.6.1.4.1.818.1.1.10.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSMode | 1.3.6.1.4.1.818.1.1.10.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOff | 1.3.6.1.4.1.818.1.1.10.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethod | 1.3.6.1.4.1.818.1.1.10.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOff | 1.3.6.1.4.1.818.1.1.10.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOff | 1.3.6.1.4.1.818.1.1.10.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSource | 1.3.6.1.4.1.818.1.1.10.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfig | 1.3.6.1.4.1.818.1.1.10.9 | |||
| NUM upsConfigInputVoltage | 1.3.6.1.4.1.818.1.1.10.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreq | 1.3.6.1.4.1.818.1.1.10.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltage | 1.3.6.1.4.1.818.1.1.10.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreq | 1.3.6.1.4.1.818.1.1.10.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVA | 1.3.6.1.4.1.818.1.1.10.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPower | 1.3.6.1.4.1.818.1.1.10.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTime | 1.3.6.1.4.1.818.1.1.10.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatus | 1.3.6.1.4.1.818.1.1.10.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPoint | 1.3.6.1.4.1.818.1.1.10.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPoint | 1.3.6.1.4.1.818.1.1.10.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacity | 1.3.6.1.4.1.818.1.1.10.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrent | 1.3.6.1.4.1.818.1.1.10.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdown | 1.3.6.1.4.1.818.1.1.10.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelay | 1.3.6.1.4.1.818.1.1.10.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSet | 1.3.6.1.4.1.818.1.1.10.10 | |||
| NUM upsEventGetNext | 1.3.6.1.4.1.818.1.1.10.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPrevious | 1.3.6.1.4.1.818.1.1.10.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStamp | 1.3.6.1.4.1.818.1.1.10.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStamp | 1.3.6.1.4.1.818.1.1.10.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSize | 1.3.6.1.4.1.818.1.1.10.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventTable | 1.3.6.1.4.1.818.1.1.10.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventEntry | 1.3.6.1.4.1.818.1.1.10.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndex | 1.3.6.1.4.1.818.1.1.10.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCode | 1.3.6.1.4.1.818.1.1.10.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatus | 1.3.6.1.4.1.818.1.1.10.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTime | 1.3.6.1.4.1.818.1.1.10.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersRead | 1.3.6.1.4.1.818.1.1.10.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWrite | 1.3.6.1.4.1.818.1.1.10.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the first value of the table with the lowest index number. |
| NUM upsParametersStartAddress | 1.3.6.1.4.1.818.1.1.10.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSize | 1.3.6.1.4.1.818.1.1.10.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterTable | 1.3.6.1.4.1.818.1.1.10.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterEntry | 1.3.6.1.4.1.818.1.1.10.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndex | 1.3.6.1.4.1.818.1.1.10.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValue | 1.3.6.1.4.1.818.1.1.10.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatus | 1.3.6.1.4.1.818.1.1.10.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfail | 1.3.6.1.4.1.818.1.1.10.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfail | 1.3.6.1.4.1.818.1.1.10.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2 | 1.3.6.1.4.1.818.1.1.10.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5 | 1.3.6.1.4.1.818.1.1.10.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10 | 1.3.6.1.4.1.818.1.1.10.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200 | 1.3.6.1.4.1.818.1.1.10.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRel | 1.3.6.1.4.1.818.1.1.10.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimegen | 1.3.6.1.4.1.818.1.1.10.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPgenERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermission | 1.3.6.1.4.1.818.1.1.10.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCode | 1.3.6.1.4.1.818.1.1.10.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLock | 1.3.6.1.4.1.818.1.1.10.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLock | 1.3.6.1.4.1.818.1.1.10.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTraps | 1.3.6.1.4.1.818.1.1.10.11 | |||
| NTF upsTrapAlarmBatteryBad | 1.3.6.1.4.1.818.1.1.10.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBattery | 1.3.6.1.4.1.818.1.1.10.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBattery | 1.3.6.1.4.1.818.1.1.10.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBattery | 1.3.6.1.4.1.818.1.1.10.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBad | 1.3.6.1.4.1.818.1.1.10.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBad | 1.3.6.1.4.1.818.1.1.10.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBad | 1.3.6.1.4.1.818.1.1.10.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverload | 1.3.6.1.4.1.818.1.1.10.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypass | 1.3.6.1.4.1.818.1.1.10.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBad | 1.3.6.1.4.1.818.1.1.10.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequested | 1.3.6.1.4.1.818.1.1.10.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequested | 1.3.6.1.4.1.818.1.1.10.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailed | 1.3.6.1.4.1.818.1.1.10.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOff | 1.3.6.1.4.1.818.1.1.10.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOff | 1.3.6.1.4.1.818.1.1.10.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailure | 1.3.6.1.4.1.818.1.1.10.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailure | 1.3.6.1.4.1.818.1.1.10.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFault | 1.3.6.1.4.1.818.1.1.10.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailed | 1.3.6.1.4.1.818.1.1.10.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLost | 1.3.6.1.4.1.818.1.1.10.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPower | 1.3.6.1.4.1.818.1.1.10.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPending | 1.3.6.1.4.1.818.1.1.10.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminent | 1.3.6.1.4.1.818.1.1.10.11.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgress | 1.3.6.1.4.1.818.1.1.10.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOff | 1.3.6.1.4.1.818.1.1.10.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailure | 1.3.6.1.4.1.818.1.1.10.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailure | 1.3.6.1.4.1.818.1.1.10.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailure | 1.3.6.1.4.1.818.1.1.10.11.28 | A problem on the Connectivity Bus is detected. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailure | 1.3.6.1.4.1.818.1.1.10.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailure | 1.3.6.1.4.1.818.1.1.10.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailure | 1.3.6.1.4.1.818.1.1.10.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestored | 1.3.6.1.4.1.818.1.1.10.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestored | 1.3.6.1.4.1.818.1.1.10.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestored | 1.3.6.1.4.1.818.1.1.10.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestored | 1.3.6.1.4.1.818.1.1.10.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestored | 1.3.6.1.4.1.818.1.1.10.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestored | 1.3.6.1.4.1.818.1.1.10.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestored | 1.3.6.1.4.1.818.1.1.10.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestored | 1.3.6.1.4.1.818.1.1.10.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestored | 1.3.6.1.4.1.818.1.1.10.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestored | 1.3.6.1.4.1.818.1.1.10.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestored | 1.3.6.1.4.1.818.1.1.10.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestored | 1.3.6.1.4.1.818.1.1.10.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestored | 1.3.6.1.4.1.818.1.1.10.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOn | 1.3.6.1.4.1.818.1.1.10.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOn | 1.3.6.1.4.1.818.1.1.10.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestored | 1.3.6.1.4.1.818.1.1.10.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestored | 1.3.6.1.4.1.818.1.1.10.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestored | 1.3.6.1.4.1.818.1.1.10.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestored | 1.3.6.1.4.1.818.1.1.10.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestored | 1.3.6.1.4.1.818.1.1.10.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestored | 1.3.6.1.4.1.818.1.1.10.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestored | 1.3.6.1.4.1.818.1.1.10.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestored | 1.3.6.1.4.1.818.1.1.10.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestored | 1.3.6.1.4.1.818.1.1.10.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOn | 1.3.6.1.4.1.818.1.1.10.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestored | 1.3.6.1.4.1.818.1.1.10.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestored | 1.3.6.1.4.1.818.1.1.10.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestored | 1.3.6.1.4.1.818.1.1.10.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestored | 1.3.6.1.4.1.818.1.1.10.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestored | 1.3.6.1.4.1.818.1.1.10.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestored | 1.3.6.1.4.1.818.1.1.10.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLow | 1.3.6.1.4.1.818.1.1.10.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHigh | 1.3.6.1.4.1.818.1.1.10.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestored | 1.3.6.1.4.1.818.1.1.10.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestored | 1.3.6.1.4.1.818.1.1.10.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnostic | 1.3.6.1.4.1.818.1.1.10.12 | |||
| I32 upsDiagnosticBusJACommunicationStatus | 1.3.6.1.4.1.818.1.1.10.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatus | 1.3.6.1.4.1.818.1.1.10.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetime | 1.3.6.1.4.1.818.1.1.10.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetime | 1.3.6.1.4.1.818.1.1.10.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetime | 1.3.6.1.4.1.818.1.1.10.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetime | 1.3.6.1.4.1.818.1.1.10.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheck | 1.3.6.1.4.1.818.1.1.10.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geFirstUPS | 1.3.6.1.4.1.818.1.1.11 | |||
| upsIdentfirst | 1.3.6.1.4.1.818.1.1.11.1 | |||
| STR upsIdentManufacturerfirst | 1.3.6.1.4.1.818.1.1.11.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelfirst | 1.3.6.1.4.1.818.1.1.11.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionfirst | 1.3.6.1.4.1.818.1.1.11.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionfirst | 1.3.6.1.4.1.818.1.1.11.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamefirst | 1.3.6.1.4.1.818.1.1.11.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicesfirst | 1.3.6.1.4.1.818.1.1.11.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumberfirst | 1.3.6.1.4.1.818.1.1.11.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionfirst | 1.3.6.1.4.1.818.1.1.11.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimefirst | 1.3.6.1.4.1.818.1.1.11.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatteryfirst | 1.3.6.1.4.1.818.1.1.11.2 | |||
| INT upsBatteryStatusfirst | 1.3.6.1.4.1.818.1.1.11.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBatteryfirst | 1.3.6.1.4.1.818.1.1.11.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingfirst | 1.3.6.1.4.1.818.1.1.11.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingfirst | 1.3.6.1.4.1.818.1.1.11.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagefirst | 1.3.6.1.4.1.818.1.1.11.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentfirst | 1.3.6.1.4.1.818.1.1.11.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturefirst | 1.3.6.1.4.1.818.1.1.11.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplefirst | 1.3.6.1.4.1.818.1.1.11.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputfirst | 1.3.6.1.4.1.818.1.1.11.3 | |||
| C32 upsInputLineBadsfirst | 1.3.6.1.4.1.818.1.1.11.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinesfirst | 1.3.6.1.4.1.818.1.1.11.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputFirstTable | 1.3.6.1.4.1.818.1.1.11.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputFirstEntry | 1.3.6.1.4.1.818.1.1.11.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencyfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagefirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowerfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxfirst | 1.3.6.1.4.1.818.1.1.11.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputfirst | 1.3.6.1.4.1.818.1.1.11.4 | |||
| INT upsOutputSourcefirst | 1.3.6.1.4.1.818.1.1.11.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencyfirst | 1.3.6.1.4.1.818.1.1.11.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinesfirst | 1.3.6.1.4.1.818.1.1.11.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputFirstTable | 1.3.6.1.4.1.818.1.1.11.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputFirstEntry | 1.3.6.1.4.1.818.1.1.11.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagefirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowerfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentfirst | 1.3.6.1.4.1.818.1.1.11.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypassfirst | 1.3.6.1.4.1.818.1.1.11.5 | |||
| NUM upsBypassFrequencyfirst | 1.3.6.1.4.1.818.1.1.11.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinesfirst | 1.3.6.1.4.1.818.1.1.11.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassFirstTable | 1.3.6.1.4.1.818.1.1.11.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassFirstEntry | 1.3.6.1.4.1.818.1.1.11.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagefirst | 1.3.6.1.4.1.818.1.1.11.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentfirst | 1.3.6.1.4.1.818.1.1.11.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowerfirst | 1.3.6.1.4.1.818.1.1.11.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmfirst | 1.3.6.1.4.1.818.1.1.11.6 | |||
| G32 upsAlarmsPresentfirst | 1.3.6.1.4.1.818.1.1.11.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmFirstTable | 1.3.6.1.4.1.818.1.1.11.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmFirstEntry | 1.3.6.1.4.1.818.1.1.11.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdfirst | 1.3.6.1.4.1.818.1.1.11.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrfirst | 1.3.6.1.4.1.818.1.1.11.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimefirst | 1.3.6.1.4.1.818.1.1.11.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmsfirst | 1.3.6.1.4.1.818.1.1.11.6.3 | |||
| upsAlarmBatteryBadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatteryfirst | 1.3.6.1.4.1.818.1.1.11.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatteryfirst | 1.3.6.1.4.1.818.1.1.11.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatteryfirst | 1.3.6.1.4.1.818.1.1.11.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypassfirst | 1.3.6.1.4.1.818.1.1.11.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadfirst | 1.3.6.1.4.1.818.1.1.11.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedfirst | 1.3.6.1.4.1.818.1.1.11.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedfirst | 1.3.6.1.4.1.818.1.1.11.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedfirst | 1.3.6.1.4.1.818.1.1.11.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOfffirst | 1.3.6.1.4.1.818.1.1.11.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOfffirst | 1.3.6.1.4.1.818.1.1.11.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultfirst | 1.3.6.1.4.1.818.1.1.11.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedfirst | 1.3.6.1.4.1.818.1.1.11.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostfirst | 1.3.6.1.4.1.818.1.1.11.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowerfirst | 1.3.6.1.4.1.818.1.1.11.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingfirst | 1.3.6.1.4.1.818.1.1.11.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentfirst | 1.3.6.1.4.1.818.1.1.11.6.3.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgressfirst | 1.3.6.1.4.1.818.1.1.11.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOfffirst | 1.3.6.1.4.1.818.1.1.11.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.27 | A CRC failure on High Speed Bus JA is detected. | ||
| upsAlarmConnectivityBusFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailurefirst | 1.3.6.1.4.1.818.1.1.11.6.3.29 | A CRC failure on High Speed Bus JB is detected. | ||
| upsAlarmCurrentSharingfirst | 1.3.6.1.4.1.818.1.1.11.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplefirst | 1.3.6.1.4.1.818.1.1.11.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAfirst | 1.3.6.1.4.1.818.1.1.11.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestfirst | 1.3.6.1.4.1.818.1.1.11.7 | |||
| OID upsTestIdfirst | 1.3.6.1.4.1.818.1.1.11.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockfirst | 1.3.6.1.4.1.818.1.1.11.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummaryfirst | 1.3.6.1.4.1.818.1.1.11.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailfirst | 1.3.6.1.4.1.818.1.1.11.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimefirst | 1.3.6.1.4.1.818.1.1.11.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimefirst | 1.3.6.1.4.1.818.1.1.11.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestsfirst | 1.3.6.1.4.1.818.1.1.11.7.7 | |||
| upsTestNoTestsInitiatedfirst | 1.3.6.1.4.1.818.1.1.11.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgressfirst | 1.3.6.1.4.1.818.1.1.11.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestfirst | 1.3.6.1.4.1.818.1.1.11.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestfirst | 1.3.6.1.4.1.818.1.1.11.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationfirst | 1.3.6.1.4.1.818.1.1.11.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlfirst | 1.3.6.1.4.1.818.1.1.11.8 | |||
| INT upsShutdownTypefirst | 1.3.6.1.4.1.818.1.1.11.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelayfirst | 1.3.6.1.4.1.818.1.1.11.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelayfirst | 1.3.6.1.4.1.818.1.1.11.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationfirst | 1.3.6.1.4.1.818.1.1.11.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartfirst | 1.3.6.1.4.1.818.1.1.11.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumfirst | 1.3.6.1.4.1.818.1.1.11.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleFirstTable | 1.3.6.1.4.1.818.1.1.11.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleFirstEntry | 1.3.6.1.4.1.818.1.1.11.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOfffirst | 1.3.6.1.4.1.818.1.1.11.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModefirst | 1.3.6.1.4.1.818.1.1.11.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOfffirst | 1.3.6.1.4.1.818.1.1.11.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodfirst | 1.3.6.1.4.1.818.1.1.11.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOfffirst | 1.3.6.1.4.1.818.1.1.11.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOfffirst | 1.3.6.1.4.1.818.1.1.11.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcefirst | 1.3.6.1.4.1.818.1.1.11.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigfirst | 1.3.6.1.4.1.818.1.1.11.9 | |||
| NUM upsConfigInputVoltagefirst | 1.3.6.1.4.1.818.1.1.11.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqfirst | 1.3.6.1.4.1.818.1.1.11.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagefirst | 1.3.6.1.4.1.818.1.1.11.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqfirst | 1.3.6.1.4.1.818.1.1.11.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAfirst | 1.3.6.1.4.1.818.1.1.11.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowerfirst | 1.3.6.1.4.1.818.1.1.11.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimefirst | 1.3.6.1.4.1.818.1.1.11.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatusfirst | 1.3.6.1.4.1.818.1.1.11.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointfirst | 1.3.6.1.4.1.818.1.1.11.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointfirst | 1.3.6.1.4.1.818.1.1.11.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacityfirst | 1.3.6.1.4.1.818.1.1.11.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentfirst | 1.3.6.1.4.1.818.1.1.11.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownfirst | 1.3.6.1.4.1.818.1.1.11.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelayfirst | 1.3.6.1.4.1.818.1.1.11.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetfirst | 1.3.6.1.4.1.818.1.1.11.10 | |||
| NUM upsEventGetNextfirst | 1.3.6.1.4.1.818.1.1.11.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviousfirst | 1.3.6.1.4.1.818.1.1.11.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampfirst | 1.3.6.1.4.1.818.1.1.11.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampfirst | 1.3.6.1.4.1.818.1.1.11.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizefirst | 1.3.6.1.4.1.818.1.1.11.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventFirstTable | 1.3.6.1.4.1.818.1.1.11.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventFirstEntry | 1.3.6.1.4.1.818.1.1.11.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodefirst | 1.3.6.1.4.1.818.1.1.11.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatusfirst | 1.3.6.1.4.1.818.1.1.11.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimefirst | 1.3.6.1.4.1.818.1.1.11.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadfirst | 1.3.6.1.4.1.818.1.1.11.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritefirst | 1.3.6.1.4.1.818.1.1.11.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the first value of the table with the lowest index number. |
| NUM upsParametersStartAddressfirst | 1.3.6.1.4.1.818.1.1.11.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizefirst | 1.3.6.1.4.1.818.1.1.11.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterFirstTable | 1.3.6.1.4.1.818.1.1.11.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterFirstEntry | 1.3.6.1.4.1.818.1.1.11.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexfirst | 1.3.6.1.4.1.818.1.1.11.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuefirst | 1.3.6.1.4.1.818.1.1.11.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatusfirst | 1.3.6.1.4.1.818.1.1.11.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailfirst | 1.3.6.1.4.1.818.1.1.11.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailfirst | 1.3.6.1.4.1.818.1.1.11.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2first | 1.3.6.1.4.1.818.1.1.11.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5first | 1.3.6.1.4.1.818.1.1.11.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10first | 1.3.6.1.4.1.818.1.1.11.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200first | 1.3.6.1.4.1.818.1.1.11.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelfirst | 1.3.6.1.4.1.818.1.1.11.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimefirst | 1.3.6.1.4.1.818.1.1.11.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfirstERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionfirst | 1.3.6.1.4.1.818.1.1.11.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodefirst | 1.3.6.1.4.1.818.1.1.11.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockfirst | 1.3.6.1.4.1.818.1.1.11.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockfirst | 1.3.6.1.4.1.818.1.1.11.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapsfirst | 1.3.6.1.4.1.818.1.1.11.11 | |||
| NTF upsTrapAlarmBatteryBadfirst | 1.3.6.1.4.1.818.1.1.11.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatteryfirst | 1.3.6.1.4.1.818.1.1.11.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatteryfirst | 1.3.6.1.4.1.818.1.1.11.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatteryfirst | 1.3.6.1.4.1.818.1.1.11.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadfirst | 1.3.6.1.4.1.818.1.1.11.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadfirst | 1.3.6.1.4.1.818.1.1.11.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadfirst | 1.3.6.1.4.1.818.1.1.11.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadfirst | 1.3.6.1.4.1.818.1.1.11.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypassfirst | 1.3.6.1.4.1.818.1.1.11.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadfirst | 1.3.6.1.4.1.818.1.1.11.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedfirst | 1.3.6.1.4.1.818.1.1.11.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedfirst | 1.3.6.1.4.1.818.1.1.11.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedfirst | 1.3.6.1.4.1.818.1.1.11.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOfffirst | 1.3.6.1.4.1.818.1.1.11.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOfffirst | 1.3.6.1.4.1.818.1.1.11.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultfirst | 1.3.6.1.4.1.818.1.1.11.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedfirst | 1.3.6.1.4.1.818.1.1.11.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostfirst | 1.3.6.1.4.1.818.1.1.11.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowerfirst | 1.3.6.1.4.1.818.1.1.11.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingfirst | 1.3.6.1.4.1.818.1.1.11.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentfirst | 1.3.6.1.4.1.818.1.1.11.11.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgressfirst | 1.3.6.1.4.1.818.1.1.11.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOfffirst | 1.3.6.1.4.1.818.1.1.11.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.27 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.28 | A problem on the Connectivity Bus communication is detected | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailurefirst | 1.3.6.1.4.1.818.1.1.11.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnfirst | 1.3.6.1.4.1.818.1.1.11.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnfirst | 1.3.6.1.4.1.818.1.1.11.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnfirst | 1.3.6.1.4.1.818.1.1.11.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowfirst | 1.3.6.1.4.1.818.1.1.11.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighfirst | 1.3.6.1.4.1.818.1.1.11.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredfirst | 1.3.6.1.4.1.818.1.1.11.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticfirst | 1.3.6.1.4.1.818.1.1.11.12 | |||
| I32 upsDiagnosticBusJACommunicationStatusfirst | 1.3.6.1.4.1.818.1.1.11.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatusfirst | 1.3.6.1.4.1.818.1.1.11.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimefirst | 1.3.6.1.4.1.818.1.1.11.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimefirst | 1.3.6.1.4.1.818.1.1.11.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimefirst | 1.3.6.1.4.1.818.1.1.11.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimefirst | 1.3.6.1.4.1.818.1.1.11.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckfirst | 1.3.6.1.4.1.818.1.1.11.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geSecondUPS | 1.3.6.1.4.1.818.1.1.12 | |||
| upsIdentsecond | 1.3.6.1.4.1.818.1.1.12.1 | |||
| STR upsIdentManufacturersecond | 1.3.6.1.4.1.818.1.1.12.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelsecond | 1.3.6.1.4.1.818.1.1.12.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionsecond | 1.3.6.1.4.1.818.1.1.12.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionsecond | 1.3.6.1.4.1.818.1.1.12.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamesecond | 1.3.6.1.4.1.818.1.1.12.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicessecond | 1.3.6.1.4.1.818.1.1.12.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumbersecond | 1.3.6.1.4.1.818.1.1.12.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionsecond | 1.3.6.1.4.1.818.1.1.12.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimesecond | 1.3.6.1.4.1.818.1.1.12.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatterysecond | 1.3.6.1.4.1.818.1.1.12.2 | |||
| INT upsBatteryStatussecond | 1.3.6.1.4.1.818.1.1.12.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBatterysecond | 1.3.6.1.4.1.818.1.1.12.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingsecond | 1.3.6.1.4.1.818.1.1.12.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingsecond | 1.3.6.1.4.1.818.1.1.12.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagesecond | 1.3.6.1.4.1.818.1.1.12.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentsecond | 1.3.6.1.4.1.818.1.1.12.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturesecond | 1.3.6.1.4.1.818.1.1.12.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplesecond | 1.3.6.1.4.1.818.1.1.12.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputsecond | 1.3.6.1.4.1.818.1.1.12.3 | |||
| C32 upsInputLineBadssecond | 1.3.6.1.4.1.818.1.1.12.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinessecond | 1.3.6.1.4.1.818.1.1.12.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputSecondTable | 1.3.6.1.4.1.818.1.1.12.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputSecondEntry | 1.3.6.1.4.1.818.1.1.12.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencysecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagesecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentsecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowersecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinsecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxsecond | 1.3.6.1.4.1.818.1.1.12.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputsecond | 1.3.6.1.4.1.818.1.1.12.4 | |||
| INT upsOutputSourcesecond | 1.3.6.1.4.1.818.1.1.12.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencysecond | 1.3.6.1.4.1.818.1.1.12.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinessecond | 1.3.6.1.4.1.818.1.1.12.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputSecondTable | 1.3.6.1.4.1.818.1.1.12.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputSecondEntry | 1.3.6.1.4.1.818.1.1.12.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagesecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowersecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentsecond | 1.3.6.1.4.1.818.1.1.12.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypasssecond | 1.3.6.1.4.1.818.1.1.12.5 | |||
| NUM upsBypassFrequencysecond | 1.3.6.1.4.1.818.1.1.12.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinessecond | 1.3.6.1.4.1.818.1.1.12.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassSecondTable | 1.3.6.1.4.1.818.1.1.12.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassSecondEntry | 1.3.6.1.4.1.818.1.1.12.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagesecond | 1.3.6.1.4.1.818.1.1.12.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentsecond | 1.3.6.1.4.1.818.1.1.12.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowersecond | 1.3.6.1.4.1.818.1.1.12.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmsecond | 1.3.6.1.4.1.818.1.1.12.6 | |||
| G32 upsAlarmsPresentsecond | 1.3.6.1.4.1.818.1.1.12.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmSecondTable | 1.3.6.1.4.1.818.1.1.12.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmSecondEntry | 1.3.6.1.4.1.818.1.1.12.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdsecond | 1.3.6.1.4.1.818.1.1.12.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrsecond | 1.3.6.1.4.1.818.1.1.12.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimesecond | 1.3.6.1.4.1.818.1.1.12.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmssecond | 1.3.6.1.4.1.818.1.1.12.6.3 | |||
| upsAlarmBatteryBadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatterysecond | 1.3.6.1.4.1.818.1.1.12.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatterysecond | 1.3.6.1.4.1.818.1.1.12.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatterysecond | 1.3.6.1.4.1.818.1.1.12.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypasssecond | 1.3.6.1.4.1.818.1.1.12.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadsecond | 1.3.6.1.4.1.818.1.1.12.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedsecond | 1.3.6.1.4.1.818.1.1.12.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedsecond | 1.3.6.1.4.1.818.1.1.12.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedsecond | 1.3.6.1.4.1.818.1.1.12.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOffsecond | 1.3.6.1.4.1.818.1.1.12.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOffsecond | 1.3.6.1.4.1.818.1.1.12.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultsecond | 1.3.6.1.4.1.818.1.1.12.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedsecond | 1.3.6.1.4.1.818.1.1.12.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostsecond | 1.3.6.1.4.1.818.1.1.12.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowersecond | 1.3.6.1.4.1.818.1.1.12.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingsecond | 1.3.6.1.4.1.818.1.1.12.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentsecond | 1.3.6.1.4.1.818.1.1.12.6.3.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgresssecond | 1.3.6.1.4.1.818.1.1.12.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOffsecond | 1.3.6.1.4.1.818.1.1.12.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.27 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmConnectivityBusFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailuresecond | 1.3.6.1.4.1.818.1.1.12.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingsecond | 1.3.6.1.4.1.818.1.1.12.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplesecond | 1.3.6.1.4.1.818.1.1.12.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAsecond | 1.3.6.1.4.1.818.1.1.12.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestsecond | 1.3.6.1.4.1.818.1.1.12.7 | |||
| OID upsTestIdsecond | 1.3.6.1.4.1.818.1.1.12.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLocksecond | 1.3.6.1.4.1.818.1.1.12.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummarysecond | 1.3.6.1.4.1.818.1.1.12.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailsecond | 1.3.6.1.4.1.818.1.1.12.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimesecond | 1.3.6.1.4.1.818.1.1.12.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimesecond | 1.3.6.1.4.1.818.1.1.12.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestssecond | 1.3.6.1.4.1.818.1.1.12.7.7 | |||
| upsTestNoTestsInitiatedsecond | 1.3.6.1.4.1.818.1.1.12.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgresssecond | 1.3.6.1.4.1.818.1.1.12.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestsecond | 1.3.6.1.4.1.818.1.1.12.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestsecond | 1.3.6.1.4.1.818.1.1.12.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationsecond | 1.3.6.1.4.1.818.1.1.12.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlsecond | 1.3.6.1.4.1.818.1.1.12.8 | |||
| INT upsShutdownTypesecond | 1.3.6.1.4.1.818.1.1.12.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelaysecond | 1.3.6.1.4.1.818.1.1.12.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelaysecond | 1.3.6.1.4.1.818.1.1.12.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationsecond | 1.3.6.1.4.1.818.1.1.12.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartsecond | 1.3.6.1.4.1.818.1.1.12.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumsecond | 1.3.6.1.4.1.818.1.1.12.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleSecondTable | 1.3.6.1.4.1.818.1.1.12.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleSecondEntry | 1.3.6.1.4.1.818.1.1.12.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOffsecond | 1.3.6.1.4.1.818.1.1.12.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModesecond | 1.3.6.1.4.1.818.1.1.12.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOffsecond | 1.3.6.1.4.1.818.1.1.12.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodsecond | 1.3.6.1.4.1.818.1.1.12.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOffsecond | 1.3.6.1.4.1.818.1.1.12.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOffsecond | 1.3.6.1.4.1.818.1.1.12.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcesecond | 1.3.6.1.4.1.818.1.1.12.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigsecond | 1.3.6.1.4.1.818.1.1.12.9 | |||
| NUM upsConfigInputVoltagesecond | 1.3.6.1.4.1.818.1.1.12.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqsecond | 1.3.6.1.4.1.818.1.1.12.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagesecond | 1.3.6.1.4.1.818.1.1.12.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqsecond | 1.3.6.1.4.1.818.1.1.12.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAsecond | 1.3.6.1.4.1.818.1.1.12.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowersecond | 1.3.6.1.4.1.818.1.1.12.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimesecond | 1.3.6.1.4.1.818.1.1.12.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatussecond | 1.3.6.1.4.1.818.1.1.12.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointsecond | 1.3.6.1.4.1.818.1.1.12.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointsecond | 1.3.6.1.4.1.818.1.1.12.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacitysecond | 1.3.6.1.4.1.818.1.1.12.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentsecond | 1.3.6.1.4.1.818.1.1.12.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownsecond | 1.3.6.1.4.1.818.1.1.12.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelaysecond | 1.3.6.1.4.1.818.1.1.12.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetsecond | 1.3.6.1.4.1.818.1.1.12.10 | |||
| NUM upsEventGetNextsecond | 1.3.6.1.4.1.818.1.1.12.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPrevioussecond | 1.3.6.1.4.1.818.1.1.12.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampsecond | 1.3.6.1.4.1.818.1.1.12.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampsecond | 1.3.6.1.4.1.818.1.1.12.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizesecond | 1.3.6.1.4.1.818.1.1.12.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventSecondTable | 1.3.6.1.4.1.818.1.1.12.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventSecondEntry | 1.3.6.1.4.1.818.1.1.12.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodesecond | 1.3.6.1.4.1.818.1.1.12.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatussecond | 1.3.6.1.4.1.818.1.1.12.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimesecond | 1.3.6.1.4.1.818.1.1.12.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadsecond | 1.3.6.1.4.1.818.1.1.12.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritesecond | 1.3.6.1.4.1.818.1.1.12.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the second value of the table with the lowest index number. |
| NUM upsParametersStartAddresssecond | 1.3.6.1.4.1.818.1.1.12.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizesecond | 1.3.6.1.4.1.818.1.1.12.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterSecondTable | 1.3.6.1.4.1.818.1.1.12.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterSecondEntry | 1.3.6.1.4.1.818.1.1.12.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexsecond | 1.3.6.1.4.1.818.1.1.12.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuesecond | 1.3.6.1.4.1.818.1.1.12.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatussecond | 1.3.6.1.4.1.818.1.1.12.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailsecond | 1.3.6.1.4.1.818.1.1.12.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailsecond | 1.3.6.1.4.1.818.1.1.12.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2second | 1.3.6.1.4.1.818.1.1.12.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5second | 1.3.6.1.4.1.818.1.1.12.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10second | 1.3.6.1.4.1.818.1.1.12.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200second | 1.3.6.1.4.1.818.1.1.12.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelsecond | 1.3.6.1.4.1.818.1.1.12.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimesecond | 1.3.6.1.4.1.818.1.1.12.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPsecondERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionsecond | 1.3.6.1.4.1.818.1.1.12.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodesecond | 1.3.6.1.4.1.818.1.1.12.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLocksecond | 1.3.6.1.4.1.818.1.1.12.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLocksecond | 1.3.6.1.4.1.818.1.1.12.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapssecond | 1.3.6.1.4.1.818.1.1.12.11 | |||
| NTF upsTrapAlarmBatteryBadsecond | 1.3.6.1.4.1.818.1.1.12.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatterysecond | 1.3.6.1.4.1.818.1.1.12.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatterysecond | 1.3.6.1.4.1.818.1.1.12.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatterysecond | 1.3.6.1.4.1.818.1.1.12.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadsecond | 1.3.6.1.4.1.818.1.1.12.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadsecond | 1.3.6.1.4.1.818.1.1.12.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadsecond | 1.3.6.1.4.1.818.1.1.12.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadsecond | 1.3.6.1.4.1.818.1.1.12.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypasssecond | 1.3.6.1.4.1.818.1.1.12.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadsecond | 1.3.6.1.4.1.818.1.1.12.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedsecond | 1.3.6.1.4.1.818.1.1.12.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedsecond | 1.3.6.1.4.1.818.1.1.12.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedsecond | 1.3.6.1.4.1.818.1.1.12.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOffsecond | 1.3.6.1.4.1.818.1.1.12.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOffsecond | 1.3.6.1.4.1.818.1.1.12.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultsecond | 1.3.6.1.4.1.818.1.1.12.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedsecond | 1.3.6.1.4.1.818.1.1.12.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostsecond | 1.3.6.1.4.1.818.1.1.12.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowersecond | 1.3.6.1.4.1.818.1.1.12.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingsecond | 1.3.6.1.4.1.818.1.1.12.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentsecond | 1.3.6.1.4.1.818.1.1.12.11.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgresssecond | 1.3.6.1.4.1.818.1.1.12.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOffsecond | 1.3.6.1.4.1.818.1.1.12.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.28 | A problem on the Connectivity Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailuresecond | 1.3.6.1.4.1.818.1.1.12.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnsecond | 1.3.6.1.4.1.818.1.1.12.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnsecond | 1.3.6.1.4.1.818.1.1.12.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnsecond | 1.3.6.1.4.1.818.1.1.12.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowsecond | 1.3.6.1.4.1.818.1.1.12.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighsecond | 1.3.6.1.4.1.818.1.1.12.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredsecond | 1.3.6.1.4.1.818.1.1.12.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticsecond | 1.3.6.1.4.1.818.1.1.12.12 | |||
| I32 upsDiagnosticBusJACommunicationStatussecond | 1.3.6.1.4.1.818.1.1.12.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatussecond | 1.3.6.1.4.1.818.1.1.12.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimesecond | 1.3.6.1.4.1.818.1.1.12.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimesecond | 1.3.6.1.4.1.818.1.1.12.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimesecond | 1.3.6.1.4.1.818.1.1.12.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimesecond | 1.3.6.1.4.1.818.1.1.12.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceChecksecond | 1.3.6.1.4.1.818.1.1.12.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geThirdUPS | 1.3.6.1.4.1.818.1.1.13 | |||
| upsIdentthird | 1.3.6.1.4.1.818.1.1.13.1 | |||
| STR upsIdentManufacturerthird | 1.3.6.1.4.1.818.1.1.13.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelthird | 1.3.6.1.4.1.818.1.1.13.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionthird | 1.3.6.1.4.1.818.1.1.13.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionthird | 1.3.6.1.4.1.818.1.1.13.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamethird | 1.3.6.1.4.1.818.1.1.13.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicesthird | 1.3.6.1.4.1.818.1.1.13.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumberthird | 1.3.6.1.4.1.818.1.1.13.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionthird | 1.3.6.1.4.1.818.1.1.13.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimethird | 1.3.6.1.4.1.818.1.1.13.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatterythird | 1.3.6.1.4.1.818.1.1.13.2 | |||
| INT upsBatteryStatusthird | 1.3.6.1.4.1.818.1.1.13.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBatterythird | 1.3.6.1.4.1.818.1.1.13.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingthird | 1.3.6.1.4.1.818.1.1.13.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingthird | 1.3.6.1.4.1.818.1.1.13.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagethird | 1.3.6.1.4.1.818.1.1.13.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentthird | 1.3.6.1.4.1.818.1.1.13.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturethird | 1.3.6.1.4.1.818.1.1.13.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplethird | 1.3.6.1.4.1.818.1.1.13.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputthird | 1.3.6.1.4.1.818.1.1.13.3 | |||
| C32 upsInputLineBadsthird | 1.3.6.1.4.1.818.1.1.13.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinesthird | 1.3.6.1.4.1.818.1.1.13.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputThirdTable | 1.3.6.1.4.1.818.1.1.13.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputThirdEntry | 1.3.6.1.4.1.818.1.1.13.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexthird | 1.3.6.1.4.1.818.1.1.13.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencythird | 1.3.6.1.4.1.818.1.1.13.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagethird | 1.3.6.1.4.1.818.1.1.13.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentthird | 1.3.6.1.4.1.818.1.1.13.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowerthird | 1.3.6.1.4.1.818.1.1.13.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinthird | 1.3.6.1.4.1.818.1.1.13.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxthird | 1.3.6.1.4.1.818.1.1.13.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputthird | 1.3.6.1.4.1.818.1.1.13.4 | |||
| INT upsOutputSourcethird | 1.3.6.1.4.1.818.1.1.13.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencythird | 1.3.6.1.4.1.818.1.1.13.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinesthird | 1.3.6.1.4.1.818.1.1.13.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputThirdTable | 1.3.6.1.4.1.818.1.1.13.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputThirdEntry | 1.3.6.1.4.1.818.1.1.13.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagethird | 1.3.6.1.4.1.818.1.1.13.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowerthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentthird | 1.3.6.1.4.1.818.1.1.13.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypassthird | 1.3.6.1.4.1.818.1.1.13.5 | |||
| NUM upsBypassFrequencythird | 1.3.6.1.4.1.818.1.1.13.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinesthird | 1.3.6.1.4.1.818.1.1.13.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassThirdTable | 1.3.6.1.4.1.818.1.1.13.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassThirdEntry | 1.3.6.1.4.1.818.1.1.13.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexthird | 1.3.6.1.4.1.818.1.1.13.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagethird | 1.3.6.1.4.1.818.1.1.13.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentthird | 1.3.6.1.4.1.818.1.1.13.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowerthird | 1.3.6.1.4.1.818.1.1.13.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmthird | 1.3.6.1.4.1.818.1.1.13.6 | |||
| G32 upsAlarmsPresentthird | 1.3.6.1.4.1.818.1.1.13.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmThirdTable | 1.3.6.1.4.1.818.1.1.13.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmThirdEntry | 1.3.6.1.4.1.818.1.1.13.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdthird | 1.3.6.1.4.1.818.1.1.13.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrthird | 1.3.6.1.4.1.818.1.1.13.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimethird | 1.3.6.1.4.1.818.1.1.13.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmsthird | 1.3.6.1.4.1.818.1.1.13.6.3 | |||
| upsAlarmBatteryBadthird | 1.3.6.1.4.1.818.1.1.13.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatterythird | 1.3.6.1.4.1.818.1.1.13.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatterythird | 1.3.6.1.4.1.818.1.1.13.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatterythird | 1.3.6.1.4.1.818.1.1.13.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadthird | 1.3.6.1.4.1.818.1.1.13.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadthird | 1.3.6.1.4.1.818.1.1.13.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadthird | 1.3.6.1.4.1.818.1.1.13.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadthird | 1.3.6.1.4.1.818.1.1.13.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypassthird | 1.3.6.1.4.1.818.1.1.13.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadthird | 1.3.6.1.4.1.818.1.1.13.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedthird | 1.3.6.1.4.1.818.1.1.13.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedthird | 1.3.6.1.4.1.818.1.1.13.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedthird | 1.3.6.1.4.1.818.1.1.13.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOffthird | 1.3.6.1.4.1.818.1.1.13.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOffthird | 1.3.6.1.4.1.818.1.1.13.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultthird | 1.3.6.1.4.1.818.1.1.13.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedthird | 1.3.6.1.4.1.818.1.1.13.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostthird | 1.3.6.1.4.1.818.1.1.13.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowerthird | 1.3.6.1.4.1.818.1.1.13.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingthird | 1.3.6.1.4.1.818.1.1.13.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentthird | 1.3.6.1.4.1.818.1.1.13.6.3.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgressthird | 1.3.6.1.4.1.818.1.1.13.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOffthird | 1.3.6.1.4.1.818.1.1.13.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailurethird | 1.3.6.1.4.1.818.1.1.13.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingthird | 1.3.6.1.4.1.818.1.1.13.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplethird | 1.3.6.1.4.1.818.1.1.13.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAthird | 1.3.6.1.4.1.818.1.1.13.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestthird | 1.3.6.1.4.1.818.1.1.13.7 | |||
| OID upsTestIdthird | 1.3.6.1.4.1.818.1.1.13.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockthird | 1.3.6.1.4.1.818.1.1.13.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummarythird | 1.3.6.1.4.1.818.1.1.13.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailthird | 1.3.6.1.4.1.818.1.1.13.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimethird | 1.3.6.1.4.1.818.1.1.13.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimethird | 1.3.6.1.4.1.818.1.1.13.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTeststhird | 1.3.6.1.4.1.818.1.1.13.7.7 | |||
| upsTestNoTestsInitiatedthird | 1.3.6.1.4.1.818.1.1.13.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgressthird | 1.3.6.1.4.1.818.1.1.13.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestthird | 1.3.6.1.4.1.818.1.1.13.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestthird | 1.3.6.1.4.1.818.1.1.13.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationthird | 1.3.6.1.4.1.818.1.1.13.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlthird | 1.3.6.1.4.1.818.1.1.13.8 | |||
| INT upsShutdownTypethird | 1.3.6.1.4.1.818.1.1.13.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelaythird | 1.3.6.1.4.1.818.1.1.13.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of Seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelaythird | 1.3.6.1.4.1.818.1.1.13.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationthird | 1.3.6.1.4.1.818.1.1.13.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartthird | 1.3.6.1.4.1.818.1.1.13.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumthird | 1.3.6.1.4.1.818.1.1.13.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleThirdTable | 1.3.6.1.4.1.818.1.1.13.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleThirdEntry | 1.3.6.1.4.1.818.1.1.13.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexthird | 1.3.6.1.4.1.818.1.1.13.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOffthird | 1.3.6.1.4.1.818.1.1.13.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModethird | 1.3.6.1.4.1.818.1.1.13.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOffthird | 1.3.6.1.4.1.818.1.1.13.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodthird | 1.3.6.1.4.1.818.1.1.13.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOffthird | 1.3.6.1.4.1.818.1.1.13.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOffthird | 1.3.6.1.4.1.818.1.1.13.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcethird | 1.3.6.1.4.1.818.1.1.13.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigthird | 1.3.6.1.4.1.818.1.1.13.9 | |||
| NUM upsConfigInputVoltagethird | 1.3.6.1.4.1.818.1.1.13.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqthird | 1.3.6.1.4.1.818.1.1.13.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagethird | 1.3.6.1.4.1.818.1.1.13.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqthird | 1.3.6.1.4.1.818.1.1.13.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAthird | 1.3.6.1.4.1.818.1.1.13.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowerthird | 1.3.6.1.4.1.818.1.1.13.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimethird | 1.3.6.1.4.1.818.1.1.13.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatusthird | 1.3.6.1.4.1.818.1.1.13.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointthird | 1.3.6.1.4.1.818.1.1.13.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointthird | 1.3.6.1.4.1.818.1.1.13.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacitythird | 1.3.6.1.4.1.818.1.1.13.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentthird | 1.3.6.1.4.1.818.1.1.13.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownthird | 1.3.6.1.4.1.818.1.1.13.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelaythird | 1.3.6.1.4.1.818.1.1.13.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetthird | 1.3.6.1.4.1.818.1.1.13.10 | |||
| NUM upsEventGetNextthird | 1.3.6.1.4.1.818.1.1.13.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviousthird | 1.3.6.1.4.1.818.1.1.13.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampthird | 1.3.6.1.4.1.818.1.1.13.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampthird | 1.3.6.1.4.1.818.1.1.13.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizethird | 1.3.6.1.4.1.818.1.1.13.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventThirdTable | 1.3.6.1.4.1.818.1.1.13.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventThirdEntry | 1.3.6.1.4.1.818.1.1.13.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexthird | 1.3.6.1.4.1.818.1.1.13.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodethird | 1.3.6.1.4.1.818.1.1.13.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatusthird | 1.3.6.1.4.1.818.1.1.13.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimethird | 1.3.6.1.4.1.818.1.1.13.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadthird | 1.3.6.1.4.1.818.1.1.13.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritethird | 1.3.6.1.4.1.818.1.1.13.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the third value of the table with the lowest index number. |
| NUM upsParametersStartAddressthird | 1.3.6.1.4.1.818.1.1.13.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizethird | 1.3.6.1.4.1.818.1.1.13.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterThirdTable | 1.3.6.1.4.1.818.1.1.13.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterThirdEntry | 1.3.6.1.4.1.818.1.1.13.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexthird | 1.3.6.1.4.1.818.1.1.13.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuethird | 1.3.6.1.4.1.818.1.1.13.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatusthird | 1.3.6.1.4.1.818.1.1.13.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailthird | 1.3.6.1.4.1.818.1.1.13.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailthird | 1.3.6.1.4.1.818.1.1.13.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2third | 1.3.6.1.4.1.818.1.1.13.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5third | 1.3.6.1.4.1.818.1.1.13.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10third | 1.3.6.1.4.1.818.1.1.13.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200third | 1.3.6.1.4.1.818.1.1.13.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelthird | 1.3.6.1.4.1.818.1.1.13.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimethird | 1.3.6.1.4.1.818.1.1.13.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMP second ERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionthird | 1.3.6.1.4.1.818.1.1.13.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodethird | 1.3.6.1.4.1.818.1.1.13.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockthird | 1.3.6.1.4.1.818.1.1.13.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockthird | 1.3.6.1.4.1.818.1.1.13.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapsthird | 1.3.6.1.4.1.818.1.1.13.11 | |||
| NTF upsTrapAlarmBatteryBadthird | 1.3.6.1.4.1.818.1.1.13.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatterythird | 1.3.6.1.4.1.818.1.1.13.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatterythird | 1.3.6.1.4.1.818.1.1.13.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatterythird | 1.3.6.1.4.1.818.1.1.13.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadthird | 1.3.6.1.4.1.818.1.1.13.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadthird | 1.3.6.1.4.1.818.1.1.13.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadthird | 1.3.6.1.4.1.818.1.1.13.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadthird | 1.3.6.1.4.1.818.1.1.13.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypassthird | 1.3.6.1.4.1.818.1.1.13.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadthird | 1.3.6.1.4.1.818.1.1.13.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedthird | 1.3.6.1.4.1.818.1.1.13.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedthird | 1.3.6.1.4.1.818.1.1.13.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedthird | 1.3.6.1.4.1.818.1.1.13.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOffthird | 1.3.6.1.4.1.818.1.1.13.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOffthird | 1.3.6.1.4.1.818.1.1.13.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailurethird | 1.3.6.1.4.1.818.1.1.13.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailurethird | 1.3.6.1.4.1.818.1.1.13.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultthird | 1.3.6.1.4.1.818.1.1.13.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedthird | 1.3.6.1.4.1.818.1.1.13.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostthird | 1.3.6.1.4.1.818.1.1.13.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowerthird | 1.3.6.1.4.1.818.1.1.13.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingthird | 1.3.6.1.4.1.818.1.1.13.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentthird | 1.3.6.1.4.1.818.1.1.13.11.23 | The UPS will turn off power to the load in less than 5 secondss; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgressthird | 1.3.6.1.4.1.818.1.1.13.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOffthird | 1.3.6.1.4.1.818.1.1.13.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailurethird | 1.3.6.1.4.1.818.1.1.13.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailurethird | 1.3.6.1.4.1.818.1.1.13.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailurethird | 1.3.6.1.4.1.818.1.1.13.11.28 | A problem on the Connectivity Bus communication is detected | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailurethird | 1.3.6.1.4.1.818.1.1.13.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailurethird | 1.3.6.1.4.1.818.1.1.13.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailurethird | 1.3.6.1.4.1.818.1.1.13.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnthird | 1.3.6.1.4.1.818.1.1.13.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnthird | 1.3.6.1.4.1.818.1.1.13.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnthird | 1.3.6.1.4.1.818.1.1.13.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestorethird | 1.3.6.1.4.1.818.1.1.13.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestorethird | 1.3.6.1.4.1.818.1.1.13.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestorethird | 1.3.6.1.4.1.818.1.1.13.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowthird | 1.3.6.1.4.1.818.1.1.13.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighthird | 1.3.6.1.4.1.818.1.1.13.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredthird | 1.3.6.1.4.1.818.1.1.13.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticthird | 1.3.6.1.4.1.818.1.1.13.12 | |||
| I32 upsDiagnosticBusJACommunicationStatusthird | 1.3.6.1.4.1.818.1.1.13.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatusthird | 1.3.6.1.4.1.818.1.1.13.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimethird | 1.3.6.1.4.1.818.1.1.13.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimethird | 1.3.6.1.4.1.818.1.1.13.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimethird | 1.3.6.1.4.1.818.1.1.13.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimethird | 1.3.6.1.4.1.818.1.1.13.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckthird | 1.3.6.1.4.1.818.1.1.13.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geFourthUPS | 1.3.6.1.4.1.818.1.1.14 | |||
| upsIdentfourth | 1.3.6.1.4.1.818.1.1.14.1 | |||
| STR upsIdentManufacturerfourth | 1.3.6.1.4.1.818.1.1.14.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelfourth | 1.3.6.1.4.1.818.1.1.14.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionfourth | 1.3.6.1.4.1.818.1.1.14.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionfourth | 1.3.6.1.4.1.818.1.1.14.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamefourth | 1.3.6.1.4.1.818.1.1.14.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicesfourth | 1.3.6.1.4.1.818.1.1.14.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumberfourth | 1.3.6.1.4.1.818.1.1.14.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionfourth | 1.3.6.1.4.1.818.1.1.14.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimefourth | 1.3.6.1.4.1.818.1.1.14.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatteryfourth | 1.3.6.1.4.1.818.1.1.14.2 | |||
| INT upsBatteryStatusfourth | 1.3.6.1.4.1.818.1.1.14.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBatteryfourth | 1.3.6.1.4.1.818.1.1.14.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingfourth | 1.3.6.1.4.1.818.1.1.14.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingfourth | 1.3.6.1.4.1.818.1.1.14.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagefourth | 1.3.6.1.4.1.818.1.1.14.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentfourth | 1.3.6.1.4.1.818.1.1.14.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturefourth | 1.3.6.1.4.1.818.1.1.14.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplefourth | 1.3.6.1.4.1.818.1.1.14.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputfourth | 1.3.6.1.4.1.818.1.1.14.3 | |||
| C32 upsInputLineBadsfourth | 1.3.6.1.4.1.818.1.1.14.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinesfourth | 1.3.6.1.4.1.818.1.1.14.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputFourthTable | 1.3.6.1.4.1.818.1.1.14.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputFourthEntry | 1.3.6.1.4.1.818.1.1.14.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencyfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagefourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowerfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxfourth | 1.3.6.1.4.1.818.1.1.14.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputfourth | 1.3.6.1.4.1.818.1.1.14.4 | |||
| INT upsOutputSourcefourth | 1.3.6.1.4.1.818.1.1.14.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencyfourth | 1.3.6.1.4.1.818.1.1.14.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinesfourth | 1.3.6.1.4.1.818.1.1.14.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputFourthTable | 1.3.6.1.4.1.818.1.1.14.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputFourthEntry | 1.3.6.1.4.1.818.1.1.14.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagefourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowerfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentfourth | 1.3.6.1.4.1.818.1.1.14.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypassfourth | 1.3.6.1.4.1.818.1.1.14.5 | |||
| NUM upsBypassFrequencyfourth | 1.3.6.1.4.1.818.1.1.14.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinesfourth | 1.3.6.1.4.1.818.1.1.14.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassFourthTable | 1.3.6.1.4.1.818.1.1.14.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassFourthEntry | 1.3.6.1.4.1.818.1.1.14.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagefourth | 1.3.6.1.4.1.818.1.1.14.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentfourth | 1.3.6.1.4.1.818.1.1.14.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowerfourth | 1.3.6.1.4.1.818.1.1.14.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmfourth | 1.3.6.1.4.1.818.1.1.14.6 | |||
| G32 upsAlarmsPresentfourth | 1.3.6.1.4.1.818.1.1.14.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmFourthTable | 1.3.6.1.4.1.818.1.1.14.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmFourthEntry | 1.3.6.1.4.1.818.1.1.14.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdfourth | 1.3.6.1.4.1.818.1.1.14.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrfourth | 1.3.6.1.4.1.818.1.1.14.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimefourth | 1.3.6.1.4.1.818.1.1.14.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmsfourth | 1.3.6.1.4.1.818.1.1.14.6.3 | |||
| upsAlarmBatteryBadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatteryfourth | 1.3.6.1.4.1.818.1.1.14.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatteryfourth | 1.3.6.1.4.1.818.1.1.14.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatteryfourth | 1.3.6.1.4.1.818.1.1.14.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypassfourth | 1.3.6.1.4.1.818.1.1.14.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadfourth | 1.3.6.1.4.1.818.1.1.14.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedfourth | 1.3.6.1.4.1.818.1.1.14.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedfourth | 1.3.6.1.4.1.818.1.1.14.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedfourth | 1.3.6.1.4.1.818.1.1.14.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOfffourth | 1.3.6.1.4.1.818.1.1.14.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOfffourth | 1.3.6.1.4.1.818.1.1.14.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultfourth | 1.3.6.1.4.1.818.1.1.14.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedfourth | 1.3.6.1.4.1.818.1.1.14.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostfourth | 1.3.6.1.4.1.818.1.1.14.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowerfourth | 1.3.6.1.4.1.818.1.1.14.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingfourth | 1.3.6.1.4.1.818.1.1.14.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentfourth | 1.3.6.1.4.1.818.1.1.14.6.3.23 | The UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgressfourth | 1.3.6.1.4.1.818.1.1.14.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOfffourth | 1.3.6.1.4.1.818.1.1.14.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.28 | A problem on the Connectivity Bus communication is detected | ||
| upsAlarmHighSpeedBusJBCRCFailurefourth | 1.3.6.1.4.1.818.1.1.14.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingfourth | 1.3.6.1.4.1.818.1.1.14.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplefourth | 1.3.6.1.4.1.818.1.1.14.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAfourth | 1.3.6.1.4.1.818.1.1.14.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestfourth | 1.3.6.1.4.1.818.1.1.14.7 | |||
| OID upsTestIdfourth | 1.3.6.1.4.1.818.1.1.14.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockfourth | 1.3.6.1.4.1.818.1.1.14.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummaryfourth | 1.3.6.1.4.1.818.1.1.14.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailfourth | 1.3.6.1.4.1.818.1.1.14.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimefourth | 1.3.6.1.4.1.818.1.1.14.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimefourth | 1.3.6.1.4.1.818.1.1.14.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestsfourth | 1.3.6.1.4.1.818.1.1.14.7.7 | |||
| upsTestNoTestsInitiatedfourth | 1.3.6.1.4.1.818.1.1.14.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgressfourth | 1.3.6.1.4.1.818.1.1.14.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestfourth | 1.3.6.1.4.1.818.1.1.14.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestfourth | 1.3.6.1.4.1.818.1.1.14.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationfourth | 1.3.6.1.4.1.818.1.1.14.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlfourth | 1.3.6.1.4.1.818.1.1.14.8 | |||
| INT upsShutdownTypefourth | 1.3.6.1.4.1.818.1.1.14.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelayfourth | 1.3.6.1.4.1.818.1.1.14.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of fourths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of fourths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelayfourth | 1.3.6.1.4.1.818.1.1.14.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of fourths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of fourths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationfourth | 1.3.6.1.4.1.818.1.1.14.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of fourths, after which time the output will be started, including starting the UPS, if necessary. If the number of fourths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 fourths. When read, upsRebootWithDuration shall return the number of fourths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartfourth | 1.3.6.1.4.1.818.1.1.14.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumfourth | 1.3.6.1.4.1.818.1.1.14.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleFourthTable | 1.3.6.1.4.1.818.1.1.14.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleFourthEntry | 1.3.6.1.4.1.818.1.1.14.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOfffourth | 1.3.6.1.4.1.818.1.1.14.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModefourth | 1.3.6.1.4.1.818.1.1.14.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOfffourth | 1.3.6.1.4.1.818.1.1.14.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodfourth | 1.3.6.1.4.1.818.1.1.14.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOfffourth | 1.3.6.1.4.1.818.1.1.14.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOfffourth | 1.3.6.1.4.1.818.1.1.14.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcefourth | 1.3.6.1.4.1.818.1.1.14.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigfourth | 1.3.6.1.4.1.818.1.1.14.9 | |||
| NUM upsConfigInputVoltagefourth | 1.3.6.1.4.1.818.1.1.14.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqfourth | 1.3.6.1.4.1.818.1.1.14.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagefourth | 1.3.6.1.4.1.818.1.1.14.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqfourth | 1.3.6.1.4.1.818.1.1.14.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAfourth | 1.3.6.1.4.1.818.1.1.14.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowerfourth | 1.3.6.1.4.1.818.1.1.14.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimefourth | 1.3.6.1.4.1.818.1.1.14.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatusfourth | 1.3.6.1.4.1.818.1.1.14.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointfourth | 1.3.6.1.4.1.818.1.1.14.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointfourth | 1.3.6.1.4.1.818.1.1.14.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacityfourth | 1.3.6.1.4.1.818.1.1.14.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentfourth | 1.3.6.1.4.1.818.1.1.14.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownfourth | 1.3.6.1.4.1.818.1.1.14.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelayfourth | 1.3.6.1.4.1.818.1.1.14.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetfourth | 1.3.6.1.4.1.818.1.1.14.10 | |||
| NUM upsEventGetNextfourth | 1.3.6.1.4.1.818.1.1.14.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviousfourth | 1.3.6.1.4.1.818.1.1.14.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampfourth | 1.3.6.1.4.1.818.1.1.14.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampfourth | 1.3.6.1.4.1.818.1.1.14.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizefourth | 1.3.6.1.4.1.818.1.1.14.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventFourthTable | 1.3.6.1.4.1.818.1.1.14.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventFourthEntry | 1.3.6.1.4.1.818.1.1.14.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodefourth | 1.3.6.1.4.1.818.1.1.14.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatusfourth | 1.3.6.1.4.1.818.1.1.14.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimefourth | 1.3.6.1.4.1.818.1.1.14.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadfourth | 1.3.6.1.4.1.818.1.1.14.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritefourth | 1.3.6.1.4.1.818.1.1.14.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the fourth value of the table with the lowest index number. |
| NUM upsParametersStartAddressfourth | 1.3.6.1.4.1.818.1.1.14.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizefourth | 1.3.6.1.4.1.818.1.1.14.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterFourthTable | 1.3.6.1.4.1.818.1.1.14.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterFourthEntry | 1.3.6.1.4.1.818.1.1.14.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexfourth | 1.3.6.1.4.1.818.1.1.14.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuefourth | 1.3.6.1.4.1.818.1.1.14.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatusfourth | 1.3.6.1.4.1.818.1.1.14.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailfourth | 1.3.6.1.4.1.818.1.1.14.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailfourth | 1.3.6.1.4.1.818.1.1.14.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2fourth | 1.3.6.1.4.1.818.1.1.14.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5fourth | 1.3.6.1.4.1.818.1.1.14.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10fourth | 1.3.6.1.4.1.818.1.1.14.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200fourth | 1.3.6.1.4.1.818.1.1.14.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelfourth | 1.3.6.1.4.1.818.1.1.14.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimefourth | 1.3.6.1.4.1.818.1.1.14.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfourthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionfourth | 1.3.6.1.4.1.818.1.1.14.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodefourth | 1.3.6.1.4.1.818.1.1.14.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockfourth | 1.3.6.1.4.1.818.1.1.14.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockfourth | 1.3.6.1.4.1.818.1.1.14.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapsfourth | 1.3.6.1.4.1.818.1.1.14.11 | |||
| NTF upsTrapAlarmBatteryBadfourth | 1.3.6.1.4.1.818.1.1.14.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatteryfourth | 1.3.6.1.4.1.818.1.1.14.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatteryfourth | 1.3.6.1.4.1.818.1.1.14.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatteryfourth | 1.3.6.1.4.1.818.1.1.14.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadfourth | 1.3.6.1.4.1.818.1.1.14.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadfourth | 1.3.6.1.4.1.818.1.1.14.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadfourth | 1.3.6.1.4.1.818.1.1.14.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadfourth | 1.3.6.1.4.1.818.1.1.14.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypassfourth | 1.3.6.1.4.1.818.1.1.14.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadfourth | 1.3.6.1.4.1.818.1.1.14.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedfourth | 1.3.6.1.4.1.818.1.1.14.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedfourth | 1.3.6.1.4.1.818.1.1.14.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedfourth | 1.3.6.1.4.1.818.1.1.14.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOfffourth | 1.3.6.1.4.1.818.1.1.14.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOfffourth | 1.3.6.1.4.1.818.1.1.14.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultfourth | 1.3.6.1.4.1.818.1.1.14.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedfourth | 1.3.6.1.4.1.818.1.1.14.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostfourth | 1.3.6.1.4.1.818.1.1.14.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowerfourth | 1.3.6.1.4.1.818.1.1.14.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingfourth | 1.3.6.1.4.1.818.1.1.14.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentfourth | 1.3.6.1.4.1.818.1.1.14.11.23 | The UPS will turn off power to the load in less than 5 fourths; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgressfourth | 1.3.6.1.4.1.818.1.1.14.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOfffourth | 1.3.6.1.4.1.818.1.1.14.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.28 | A problem on the Connectivity Bus communication is detected | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailurefourth | 1.3.6.1.4.1.818.1.1.14.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnfourth | 1.3.6.1.4.1.818.1.1.14.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnfourth | 1.3.6.1.4.1.818.1.1.14.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnfourth | 1.3.6.1.4.1.818.1.1.14.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestorefourth | 1.3.6.1.4.1.818.1.1.14.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestorefourth | 1.3.6.1.4.1.818.1.1.14.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestorefourth | 1.3.6.1.4.1.818.1.1.14.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowfourth | 1.3.6.1.4.1.818.1.1.14.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighfourth | 1.3.6.1.4.1.818.1.1.14.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredfourth | 1.3.6.1.4.1.818.1.1.14.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticfourth | 1.3.6.1.4.1.818.1.1.14.12 | |||
| I32 upsDiagnosticBusJACommunicationStatusfourth | 1.3.6.1.4.1.818.1.1.14.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatusfourth | 1.3.6.1.4.1.818.1.1.14.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimefourth | 1.3.6.1.4.1.818.1.1.14.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimefourth | 1.3.6.1.4.1.818.1.1.14.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimefourth | 1.3.6.1.4.1.818.1.1.14.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimefourth | 1.3.6.1.4.1.818.1.1.14.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckfourth | 1.3.6.1.4.1.818.1.1.14.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geFifthUPS | 1.3.6.1.4.1.818.1.1.15 | |||
| upsIdentfifth | 1.3.6.1.4.1.818.1.1.15.1 | |||
| STR upsIdentManufacturerfifth | 1.3.6.1.4.1.818.1.1.15.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelfifth | 1.3.6.1.4.1.818.1.1.15.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionfifth | 1.3.6.1.4.1.818.1.1.15.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionfifth | 1.3.6.1.4.1.818.1.1.15.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamefifth | 1.3.6.1.4.1.818.1.1.15.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicesfifth | 1.3.6.1.4.1.818.1.1.15.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumberfifth | 1.3.6.1.4.1.818.1.1.15.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionfifth | 1.3.6.1.4.1.818.1.1.15.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimefifth | 1.3.6.1.4.1.818.1.1.15.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatteryfifth | 1.3.6.1.4.1.818.1.1.15.2 | |||
| INT upsBatteryStatusfifth | 1.3.6.1.4.1.818.1.1.15.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| I32 upsSecondsOnBatteryfifth | 1.3.6.1.4.1.818.1.1.15.2.2 | Integer32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingfifth | 1.3.6.1.4.1.818.1.1.15.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingfifth | 1.3.6.1.4.1.818.1.1.15.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagefifth | 1.3.6.1.4.1.818.1.1.15.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentfifth | 1.3.6.1.4.1.818.1.1.15.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturefifth | 1.3.6.1.4.1.818.1.1.15.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplefifth | 1.3.6.1.4.1.818.1.1.15.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputfifth | 1.3.6.1.4.1.818.1.1.15.3 | |||
| C32 upsInputLineBadsfifth | 1.3.6.1.4.1.818.1.1.15.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinesfifth | 1.3.6.1.4.1.818.1.1.15.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputFifthTable | 1.3.6.1.4.1.818.1.1.15.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputFifthEntry | 1.3.6.1.4.1.818.1.1.15.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencyfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagefifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowerfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxfifth | 1.3.6.1.4.1.818.1.1.15.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputfifth | 1.3.6.1.4.1.818.1.1.15.4 | |||
| INT upsOutputSourcefifth | 1.3.6.1.4.1.818.1.1.15.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencyfifth | 1.3.6.1.4.1.818.1.1.15.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinesfifth | 1.3.6.1.4.1.818.1.1.15.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputFifthTable | 1.3.6.1.4.1.818.1.1.15.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputFifthEntry | 1.3.6.1.4.1.818.1.1.15.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagefifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowerfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentfifth | 1.3.6.1.4.1.818.1.1.15.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypassfifth | 1.3.6.1.4.1.818.1.1.15.5 | |||
| NUM upsBypassFrequencyfifth | 1.3.6.1.4.1.818.1.1.15.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinesfifth | 1.3.6.1.4.1.818.1.1.15.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassFifthTable | 1.3.6.1.4.1.818.1.1.15.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassFifthEntry | 1.3.6.1.4.1.818.1.1.15.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagefifth | 1.3.6.1.4.1.818.1.1.15.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentfifth | 1.3.6.1.4.1.818.1.1.15.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowerfifth | 1.3.6.1.4.1.818.1.1.15.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmfifth | 1.3.6.1.4.1.818.1.1.15.6 | |||
| G32 upsAlarmsPresentfifth | 1.3.6.1.4.1.818.1.1.15.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmFifthTable | 1.3.6.1.4.1.818.1.1.15.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmFifthEntry | 1.3.6.1.4.1.818.1.1.15.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdfifth | 1.3.6.1.4.1.818.1.1.15.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrfifth | 1.3.6.1.4.1.818.1.1.15.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimefifth | 1.3.6.1.4.1.818.1.1.15.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmsfifth | 1.3.6.1.4.1.818.1.1.15.6.3 | |||
| upsAlarmBatteryBadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatteryfifth | 1.3.6.1.4.1.818.1.1.15.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatteryfifth | 1.3.6.1.4.1.818.1.1.15.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatteryfifth | 1.3.6.1.4.1.818.1.1.15.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypassfifth | 1.3.6.1.4.1.818.1.1.15.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadfifth | 1.3.6.1.4.1.818.1.1.15.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedfifth | 1.3.6.1.4.1.818.1.1.15.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedfifth | 1.3.6.1.4.1.818.1.1.15.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedfifth | 1.3.6.1.4.1.818.1.1.15.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOfffifth | 1.3.6.1.4.1.818.1.1.15.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOfffifth | 1.3.6.1.4.1.818.1.1.15.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultfifth | 1.3.6.1.4.1.818.1.1.15.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedfifth | 1.3.6.1.4.1.818.1.1.15.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostfifth | 1.3.6.1.4.1.818.1.1.15.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowerfifth | 1.3.6.1.4.1.818.1.1.15.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingfifth | 1.3.6.1.4.1.818.1.1.15.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentfifth | 1.3.6.1.4.1.818.1.1.15.6.3.23 | The UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgressfifth | 1.3.6.1.4.1.818.1.1.15.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOfffifth | 1.3.6.1.4.1.818.1.1.15.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailurefifth | 1.3.6.1.4.1.818.1.1.15.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingfifth | 1.3.6.1.4.1.818.1.1.15.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplefifth | 1.3.6.1.4.1.818.1.1.15.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAfifth | 1.3.6.1.4.1.818.1.1.15.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestfifth | 1.3.6.1.4.1.818.1.1.15.7 | |||
| OID upsTestIdfifth | 1.3.6.1.4.1.818.1.1.15.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockfifth | 1.3.6.1.4.1.818.1.1.15.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummaryfifth | 1.3.6.1.4.1.818.1.1.15.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailfifth | 1.3.6.1.4.1.818.1.1.15.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimefifth | 1.3.6.1.4.1.818.1.1.15.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimefifth | 1.3.6.1.4.1.818.1.1.15.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestsfifth | 1.3.6.1.4.1.818.1.1.15.7.7 | |||
| upsTestNoTestsInitiatedfifth | 1.3.6.1.4.1.818.1.1.15.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgressfifth | 1.3.6.1.4.1.818.1.1.15.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestfifth | 1.3.6.1.4.1.818.1.1.15.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestfifth | 1.3.6.1.4.1.818.1.1.15.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationfifth | 1.3.6.1.4.1.818.1.1.15.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlfifth | 1.3.6.1.4.1.818.1.1.15.8 | |||
| INT upsShutdownTypefifth | 1.3.6.1.4.1.818.1.1.15.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelayfifth | 1.3.6.1.4.1.818.1.1.15.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of fifths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of fifths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelayfifth | 1.3.6.1.4.1.818.1.1.15.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of fifths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of fifths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationfifth | 1.3.6.1.4.1.818.1.1.15.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of fifths, after which time the output will be started, including starting the UPS, if necessary. If the number of fifths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 fifths. When read, upsRebootWithDuration shall return the number of fifths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartfifth | 1.3.6.1.4.1.818.1.1.15.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumfifth | 1.3.6.1.4.1.818.1.1.15.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleFifthTable | 1.3.6.1.4.1.818.1.1.15.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleFifthEntry | 1.3.6.1.4.1.818.1.1.15.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOfffifth | 1.3.6.1.4.1.818.1.1.15.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModefifth | 1.3.6.1.4.1.818.1.1.15.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOfffifth | 1.3.6.1.4.1.818.1.1.15.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodfifth | 1.3.6.1.4.1.818.1.1.15.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOfffifth | 1.3.6.1.4.1.818.1.1.15.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOfffifth | 1.3.6.1.4.1.818.1.1.15.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcefifth | 1.3.6.1.4.1.818.1.1.15.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigfifth | 1.3.6.1.4.1.818.1.1.15.9 | |||
| NUM upsConfigInputVoltagefifth | 1.3.6.1.4.1.818.1.1.15.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqfifth | 1.3.6.1.4.1.818.1.1.15.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagefifth | 1.3.6.1.4.1.818.1.1.15.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqfifth | 1.3.6.1.4.1.818.1.1.15.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAfifth | 1.3.6.1.4.1.818.1.1.15.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowerfifth | 1.3.6.1.4.1.818.1.1.15.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimefifth | 1.3.6.1.4.1.818.1.1.15.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatusfifth | 1.3.6.1.4.1.818.1.1.15.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointfifth | 1.3.6.1.4.1.818.1.1.15.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointfifth | 1.3.6.1.4.1.818.1.1.15.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacityfifth | 1.3.6.1.4.1.818.1.1.15.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentfifth | 1.3.6.1.4.1.818.1.1.15.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownfifth | 1.3.6.1.4.1.818.1.1.15.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelayfifth | 1.3.6.1.4.1.818.1.1.15.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetfifth | 1.3.6.1.4.1.818.1.1.15.10 | |||
| NUM upsEventGetNextfifth | 1.3.6.1.4.1.818.1.1.15.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviousfifth | 1.3.6.1.4.1.818.1.1.15.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampfifth | 1.3.6.1.4.1.818.1.1.15.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampfifth | 1.3.6.1.4.1.818.1.1.15.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizefifth | 1.3.6.1.4.1.818.1.1.15.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventFifthTable | 1.3.6.1.4.1.818.1.1.15.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventFifthEntry | 1.3.6.1.4.1.818.1.1.15.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodefifth | 1.3.6.1.4.1.818.1.1.15.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatusfifth | 1.3.6.1.4.1.818.1.1.15.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimefifth | 1.3.6.1.4.1.818.1.1.15.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadfifth | 1.3.6.1.4.1.818.1.1.15.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritefifth | 1.3.6.1.4.1.818.1.1.15.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the fifth value of the table with the lowest index number. |
| NUM upsParametersStartAddressfifth | 1.3.6.1.4.1.818.1.1.15.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizefifth | 1.3.6.1.4.1.818.1.1.15.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterFifthTable | 1.3.6.1.4.1.818.1.1.15.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterFifthEntry | 1.3.6.1.4.1.818.1.1.15.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexfifth | 1.3.6.1.4.1.818.1.1.15.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuefifth | 1.3.6.1.4.1.818.1.1.15.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatusfifth | 1.3.6.1.4.1.818.1.1.15.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailfifth | 1.3.6.1.4.1.818.1.1.15.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailfifth | 1.3.6.1.4.1.818.1.1.15.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2fifth | 1.3.6.1.4.1.818.1.1.15.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5fifth | 1.3.6.1.4.1.818.1.1.15.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10fifth | 1.3.6.1.4.1.818.1.1.15.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200fifth | 1.3.6.1.4.1.818.1.1.15.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelfifth | 1.3.6.1.4.1.818.1.1.15.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimefifth | 1.3.6.1.4.1.818.1.1.15.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPfifthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionfifth | 1.3.6.1.4.1.818.1.1.15.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodefifth | 1.3.6.1.4.1.818.1.1.15.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockfifth | 1.3.6.1.4.1.818.1.1.15.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockfifth | 1.3.6.1.4.1.818.1.1.15.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapsfifth | 1.3.6.1.4.1.818.1.1.15.11 | |||
| NTF upsTrapAlarmBatteryBadfifth | 1.3.6.1.4.1.818.1.1.15.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatteryfifth | 1.3.6.1.4.1.818.1.1.15.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatteryfifth | 1.3.6.1.4.1.818.1.1.15.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatteryfifth | 1.3.6.1.4.1.818.1.1.15.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadfifth | 1.3.6.1.4.1.818.1.1.15.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadfifth | 1.3.6.1.4.1.818.1.1.15.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadfifth | 1.3.6.1.4.1.818.1.1.15.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadfifth | 1.3.6.1.4.1.818.1.1.15.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypassfifth | 1.3.6.1.4.1.818.1.1.15.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadfifth | 1.3.6.1.4.1.818.1.1.15.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedfifth | 1.3.6.1.4.1.818.1.1.15.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedfifth | 1.3.6.1.4.1.818.1.1.15.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedfifth | 1.3.6.1.4.1.818.1.1.15.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOfffifth | 1.3.6.1.4.1.818.1.1.15.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOfffifth | 1.3.6.1.4.1.818.1.1.15.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultfifth | 1.3.6.1.4.1.818.1.1.15.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedfifth | 1.3.6.1.4.1.818.1.1.15.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostfifth | 1.3.6.1.4.1.818.1.1.15.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowerfifth | 1.3.6.1.4.1.818.1.1.15.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingfifth | 1.3.6.1.4.1.818.1.1.15.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentfifth | 1.3.6.1.4.1.818.1.1.15.11.23 | The UPS will turn off power to the load in less than 5 fifths; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgressfifth | 1.3.6.1.4.1.818.1.1.15.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOfffifth | 1.3.6.1.4.1.818.1.1.15.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.28 | A problem on the Connectivity Bus communication is detected | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailurefifth | 1.3.6.1.4.1.818.1.1.15.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnfifth | 1.3.6.1.4.1.818.1.1.15.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnfifth | 1.3.6.1.4.1.818.1.1.15.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnfifth | 1.3.6.1.4.1.818.1.1.15.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestorefifth | 1.3.6.1.4.1.818.1.1.15.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestorefifth | 1.3.6.1.4.1.818.1.1.15.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestorefifth | 1.3.6.1.4.1.818.1.1.15.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowfifth | 1.3.6.1.4.1.818.1.1.15.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighfifth | 1.3.6.1.4.1.818.1.1.15.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredfifth | 1.3.6.1.4.1.818.1.1.15.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticfifth | 1.3.6.1.4.1.818.1.1.15.12 | |||
| I32 upsDiagnosticBusJACommunicationStatusfifth | 1.3.6.1.4.1.818.1.1.15.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatusfifth | 1.3.6.1.4.1.818.1.1.15.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimefifth | 1.3.6.1.4.1.818.1.1.15.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimefifth | 1.3.6.1.4.1.818.1.1.15.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimefifth | 1.3.6.1.4.1.818.1.1.15.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimefifth | 1.3.6.1.4.1.818.1.1.15.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckfifth | 1.3.6.1.4.1.818.1.1.15.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geSixthUPS | 1.3.6.1.4.1.818.1.1.16 | |||
| upsIdentsixth | 1.3.6.1.4.1.818.1.1.16.1 | |||
| STR upsIdentManufacturersixth | 1.3.6.1.4.1.818.1.1.16.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelsixth | 1.3.6.1.4.1.818.1.1.16.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionsixth | 1.3.6.1.4.1.818.1.1.16.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionsixth | 1.3.6.1.4.1.818.1.1.16.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNamesixth | 1.3.6.1.4.1.818.1.1.16.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicessixth | 1.3.6.1.4.1.818.1.1.16.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumbersixth | 1.3.6.1.4.1.818.1.1.16.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionsixth | 1.3.6.1.4.1.818.1.1.16.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimesixth | 1.3.6.1.4.1.818.1.1.16.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatterysixth | 1.3.6.1.4.1.818.1.1.16.2 | |||
| INT upsBatteryStatussixth | 1.3.6.1.4.1.818.1.1.16.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| NUM upsSecondsOnBatterysixth | 1.3.6.1.4.1.818.1.1.16.2.2 | NonNegativeInteger32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingsixth | 1.3.6.1.4.1.818.1.1.16.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingsixth | 1.3.6.1.4.1.818.1.1.16.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltagesixth | 1.3.6.1.4.1.818.1.1.16.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentsixth | 1.3.6.1.4.1.818.1.1.16.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperaturesixth | 1.3.6.1.4.1.818.1.1.16.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRipplesixth | 1.3.6.1.4.1.818.1.1.16.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputsixth | 1.3.6.1.4.1.818.1.1.16.3 | |||
| C32 upsInputLineBadssixth | 1.3.6.1.4.1.818.1.1.16.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinessixth | 1.3.6.1.4.1.818.1.1.16.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputSixthTable | 1.3.6.1.4.1.818.1.1.16.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputSixthEntry | 1.3.6.1.4.1.818.1.1.16.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencysixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltagesixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentsixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowersixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinsixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxsixth | 1.3.6.1.4.1.818.1.1.16.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputsixth | 1.3.6.1.4.1.818.1.1.16.4 | |||
| INT upsOutputSourcesixth | 1.3.6.1.4.1.818.1.1.16.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencysixth | 1.3.6.1.4.1.818.1.1.16.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinessixth | 1.3.6.1.4.1.818.1.1.16.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputSixthTable | 1.3.6.1.4.1.818.1.1.16.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputSixthEntry | 1.3.6.1.4.1.818.1.1.16.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltagesixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowersixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentsixth | 1.3.6.1.4.1.818.1.1.16.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypasssixth | 1.3.6.1.4.1.818.1.1.16.5 | |||
| NUM upsBypassFrequencysixth | 1.3.6.1.4.1.818.1.1.16.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinessixth | 1.3.6.1.4.1.818.1.1.16.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassSixthTable | 1.3.6.1.4.1.818.1.1.16.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassSixthEntry | 1.3.6.1.4.1.818.1.1.16.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltagesixth | 1.3.6.1.4.1.818.1.1.16.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentsixth | 1.3.6.1.4.1.818.1.1.16.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowersixth | 1.3.6.1.4.1.818.1.1.16.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmsixth | 1.3.6.1.4.1.818.1.1.16.6 | |||
| G32 upsAlarmsPresentsixth | 1.3.6.1.4.1.818.1.1.16.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmSixthTable | 1.3.6.1.4.1.818.1.1.16.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmSixthEntry | 1.3.6.1.4.1.818.1.1.16.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdsixth | 1.3.6.1.4.1.818.1.1.16.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrsixth | 1.3.6.1.4.1.818.1.1.16.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimesixth | 1.3.6.1.4.1.818.1.1.16.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmssixth | 1.3.6.1.4.1.818.1.1.16.6.3 | |||
| upsAlarmBatteryBadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatterysixth | 1.3.6.1.4.1.818.1.1.16.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatterysixth | 1.3.6.1.4.1.818.1.1.16.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatterysixth | 1.3.6.1.4.1.818.1.1.16.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypasssixth | 1.3.6.1.4.1.818.1.1.16.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadsixth | 1.3.6.1.4.1.818.1.1.16.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedsixth | 1.3.6.1.4.1.818.1.1.16.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedsixth | 1.3.6.1.4.1.818.1.1.16.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedsixth | 1.3.6.1.4.1.818.1.1.16.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOffsixth | 1.3.6.1.4.1.818.1.1.16.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOffsixth | 1.3.6.1.4.1.818.1.1.16.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultsixth | 1.3.6.1.4.1.818.1.1.16.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedsixth | 1.3.6.1.4.1.818.1.1.16.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostsixth | 1.3.6.1.4.1.818.1.1.16.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowersixth | 1.3.6.1.4.1.818.1.1.16.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingsixth | 1.3.6.1.4.1.818.1.1.16.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentsixth | 1.3.6.1.4.1.818.1.1.16.6.3.23 | The UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgresssixth | 1.3.6.1.4.1.818.1.1.16.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOffsixth | 1.3.6.1.4.1.818.1.1.16.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailuresixth | 1.3.6.1.4.1.818.1.1.16.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingsixth | 1.3.6.1.4.1.818.1.1.16.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRipplesixth | 1.3.6.1.4.1.818.1.1.16.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAsixth | 1.3.6.1.4.1.818.1.1.16.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestsixth | 1.3.6.1.4.1.818.1.1.16.7 | |||
| OID upsTestIdsixth | 1.3.6.1.4.1.818.1.1.16.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLocksixth | 1.3.6.1.4.1.818.1.1.16.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummarysixth | 1.3.6.1.4.1.818.1.1.16.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailsixth | 1.3.6.1.4.1.818.1.1.16.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimesixth | 1.3.6.1.4.1.818.1.1.16.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimesixth | 1.3.6.1.4.1.818.1.1.16.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestssixth | 1.3.6.1.4.1.818.1.1.16.7.7 | |||
| upsTestNoTestsInitiatedsixth | 1.3.6.1.4.1.818.1.1.16.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgresssixth | 1.3.6.1.4.1.818.1.1.16.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestsixth | 1.3.6.1.4.1.818.1.1.16.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestsixth | 1.3.6.1.4.1.818.1.1.16.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationsixth | 1.3.6.1.4.1.818.1.1.16.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlsixth | 1.3.6.1.4.1.818.1.1.16.8 | |||
| INT upsShutdownTypesixth | 1.3.6.1.4.1.818.1.1.16.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelaysixth | 1.3.6.1.4.1.818.1.1.16.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of sixths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of sixths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelaysixth | 1.3.6.1.4.1.818.1.1.16.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of sixths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of sixths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationsixth | 1.3.6.1.4.1.818.1.1.16.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of sixths, after which time the output will be started, including starting the UPS, if necessary. If the number of sixths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 sixths. When read, upsRebootWithDuration shall return the number of sixths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartsixth | 1.3.6.1.4.1.818.1.1.16.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumsixth | 1.3.6.1.4.1.818.1.1.16.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleSixthTable | 1.3.6.1.4.1.818.1.1.16.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleSixthEntry | 1.3.6.1.4.1.818.1.1.16.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOffsixth | 1.3.6.1.4.1.818.1.1.16.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModesixth | 1.3.6.1.4.1.818.1.1.16.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOffsixth | 1.3.6.1.4.1.818.1.1.16.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodsixth | 1.3.6.1.4.1.818.1.1.16.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOffsixth | 1.3.6.1.4.1.818.1.1.16.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOffsixth | 1.3.6.1.4.1.818.1.1.16.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourcesixth | 1.3.6.1.4.1.818.1.1.16.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigsixth | 1.3.6.1.4.1.818.1.1.16.9 | |||
| NUM upsConfigInputVoltagesixth | 1.3.6.1.4.1.818.1.1.16.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqsixth | 1.3.6.1.4.1.818.1.1.16.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltagesixth | 1.3.6.1.4.1.818.1.1.16.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqsixth | 1.3.6.1.4.1.818.1.1.16.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAsixth | 1.3.6.1.4.1.818.1.1.16.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowersixth | 1.3.6.1.4.1.818.1.1.16.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimesixth | 1.3.6.1.4.1.818.1.1.16.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatussixth | 1.3.6.1.4.1.818.1.1.16.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointsixth | 1.3.6.1.4.1.818.1.1.16.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointsixth | 1.3.6.1.4.1.818.1.1.16.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacitysixth | 1.3.6.1.4.1.818.1.1.16.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentsixth | 1.3.6.1.4.1.818.1.1.16.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownsixth | 1.3.6.1.4.1.818.1.1.16.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelaysixth | 1.3.6.1.4.1.818.1.1.16.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetsixth | 1.3.6.1.4.1.818.1.1.16.10 | |||
| NUM upsEventGetNextsixth | 1.3.6.1.4.1.818.1.1.16.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPrevioussixth | 1.3.6.1.4.1.818.1.1.16.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampsixth | 1.3.6.1.4.1.818.1.1.16.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampsixth | 1.3.6.1.4.1.818.1.1.16.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizesixth | 1.3.6.1.4.1.818.1.1.16.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventSixthTable | 1.3.6.1.4.1.818.1.1.16.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventSixthEntry | 1.3.6.1.4.1.818.1.1.16.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodesixth | 1.3.6.1.4.1.818.1.1.16.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatussixth | 1.3.6.1.4.1.818.1.1.16.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimesixth | 1.3.6.1.4.1.818.1.1.16.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadsixth | 1.3.6.1.4.1.818.1.1.16.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWritesixth | 1.3.6.1.4.1.818.1.1.16.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the sixth value of the table with the lowest index number. |
| NUM upsParametersStartAddresssixth | 1.3.6.1.4.1.818.1.1.16.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizesixth | 1.3.6.1.4.1.818.1.1.16.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterSixthTable | 1.3.6.1.4.1.818.1.1.16.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterSixthEntry | 1.3.6.1.4.1.818.1.1.16.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexsixth | 1.3.6.1.4.1.818.1.1.16.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValuesixth | 1.3.6.1.4.1.818.1.1.16.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatussixth | 1.3.6.1.4.1.818.1.1.16.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailsixth | 1.3.6.1.4.1.818.1.1.16.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailsixth | 1.3.6.1.4.1.818.1.1.16.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2sixth | 1.3.6.1.4.1.818.1.1.16.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5sixth | 1.3.6.1.4.1.818.1.1.16.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10sixth | 1.3.6.1.4.1.818.1.1.16.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200sixth | 1.3.6.1.4.1.818.1.1.16.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelsixth | 1.3.6.1.4.1.818.1.1.16.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimesixth | 1.3.6.1.4.1.818.1.1.16.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPsixthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionsixth | 1.3.6.1.4.1.818.1.1.16.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodesixth | 1.3.6.1.4.1.818.1.1.16.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLocksixth | 1.3.6.1.4.1.818.1.1.16.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLocksixth | 1.3.6.1.4.1.818.1.1.16.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapssixth | 1.3.6.1.4.1.818.1.1.16.11 | |||
| NTF upsTrapAlarmBatteryBadsixth | 1.3.6.1.4.1.818.1.1.16.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatterysixth | 1.3.6.1.4.1.818.1.1.16.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatterysixth | 1.3.6.1.4.1.818.1.1.16.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatterysixth | 1.3.6.1.4.1.818.1.1.16.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadsixth | 1.3.6.1.4.1.818.1.1.16.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadsixth | 1.3.6.1.4.1.818.1.1.16.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadsixth | 1.3.6.1.4.1.818.1.1.16.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadsixth | 1.3.6.1.4.1.818.1.1.16.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypasssixth | 1.3.6.1.4.1.818.1.1.16.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadsixth | 1.3.6.1.4.1.818.1.1.16.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedsixth | 1.3.6.1.4.1.818.1.1.16.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedsixth | 1.3.6.1.4.1.818.1.1.16.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedsixth | 1.3.6.1.4.1.818.1.1.16.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOffsixth | 1.3.6.1.4.1.818.1.1.16.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOffsixth | 1.3.6.1.4.1.818.1.1.16.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultsixth | 1.3.6.1.4.1.818.1.1.16.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedsixth | 1.3.6.1.4.1.818.1.1.16.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostsixth | 1.3.6.1.4.1.818.1.1.16.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowersixth | 1.3.6.1.4.1.818.1.1.16.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingsixth | 1.3.6.1.4.1.818.1.1.16.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentsixth | 1.3.6.1.4.1.818.1.1.16.11.23 | The UPS will turn off power to the load in less than 5 sixths; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgresssixth | 1.3.6.1.4.1.818.1.1.16.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOffsixth | 1.3.6.1.4.1.818.1.1.16.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.28 | A problem on the Connectivity Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailuresixth | 1.3.6.1.4.1.818.1.1.16.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnsixth | 1.3.6.1.4.1.818.1.1.16.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnsixth | 1.3.6.1.4.1.818.1.1.16.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnsixth | 1.3.6.1.4.1.818.1.1.16.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestoresixth | 1.3.6.1.4.1.818.1.1.16.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestoresixth | 1.3.6.1.4.1.818.1.1.16.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestoresixth | 1.3.6.1.4.1.818.1.1.16.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowsixth | 1.3.6.1.4.1.818.1.1.16.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighsixth | 1.3.6.1.4.1.818.1.1.16.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredsixth | 1.3.6.1.4.1.818.1.1.16.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticsixth | 1.3.6.1.4.1.818.1.1.16.12 | |||
| I32 upsDiagnosticBusJACommunicationStatussixth | 1.3.6.1.4.1.818.1.1.16.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatussixth | 1.3.6.1.4.1.818.1.1.16.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimesixth | 1.3.6.1.4.1.818.1.1.16.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimesixth | 1.3.6.1.4.1.818.1.1.16.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimesixth | 1.3.6.1.4.1.818.1.1.16.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimesixth | 1.3.6.1.4.1.818.1.1.16.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceChecksixth | 1.3.6.1.4.1.818.1.1.16.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geSeventhUPS | 1.3.6.1.4.1.818.1.1.17 | |||
| upsIdentseventh | 1.3.6.1.4.1.818.1.1.17.1 | |||
| STR upsIdentManufacturerseventh | 1.3.6.1.4.1.818.1.1.17.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModelseventh | 1.3.6.1.4.1.818.1.1.17.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersionseventh | 1.3.6.1.4.1.818.1.1.17.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersionseventh | 1.3.6.1.4.1.818.1.1.17.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNameseventh | 1.3.6.1.4.1.818.1.1.17.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevicesseventh | 1.3.6.1.4.1.818.1.1.17.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumberseventh | 1.3.6.1.4.1.818.1.1.17.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersionseventh | 1.3.6.1.4.1.818.1.1.17.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimeseventh | 1.3.6.1.4.1.818.1.1.17.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatteryseventh | 1.3.6.1.4.1.818.1.1.17.2 | |||
| INT upsBatteryStatusseventh | 1.3.6.1.4.1.818.1.1.17.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| NUM upsSecondsOnBatteryseventh | 1.3.6.1.4.1.818.1.1.17.2.2 | NonNegativeInteger32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingseventh | 1.3.6.1.4.1.818.1.1.17.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingseventh | 1.3.6.1.4.1.818.1.1.17.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltageseventh | 1.3.6.1.4.1.818.1.1.17.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrentseventh | 1.3.6.1.4.1.818.1.1.17.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperatureseventh | 1.3.6.1.4.1.818.1.1.17.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRippleseventh | 1.3.6.1.4.1.818.1.1.17.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputseventh | 1.3.6.1.4.1.818.1.1.17.3 | |||
| C32 upsInputLineBadsseventh | 1.3.6.1.4.1.818.1.1.17.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLinesseventh | 1.3.6.1.4.1.818.1.1.17.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputSeventhTable | 1.3.6.1.4.1.818.1.1.17.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputSeventhEntry | 1.3.6.1.4.1.818.1.1.17.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencyseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltageseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrentseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowerseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMinseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxseventh | 1.3.6.1.4.1.818.1.1.17.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputseventh | 1.3.6.1.4.1.818.1.1.17.4 | |||
| INT upsOutputSourceseventh | 1.3.6.1.4.1.818.1.1.17.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencyseventh | 1.3.6.1.4.1.818.1.1.17.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLinesseventh | 1.3.6.1.4.1.818.1.1.17.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputSeventhTable | 1.3.6.1.4.1.818.1.1.17.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputSeventhEntry | 1.3.6.1.4.1.818.1.1.17.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltageseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrentseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowerseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactorseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrentseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrentseventh | 1.3.6.1.4.1.818.1.1.17.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypassseventh | 1.3.6.1.4.1.818.1.1.17.5 | |||
| NUM upsBypassFrequencyseventh | 1.3.6.1.4.1.818.1.1.17.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLinesseventh | 1.3.6.1.4.1.818.1.1.17.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassSeventhTable | 1.3.6.1.4.1.818.1.1.17.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassSeventhEntry | 1.3.6.1.4.1.818.1.1.17.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltageseventh | 1.3.6.1.4.1.818.1.1.17.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrentseventh | 1.3.6.1.4.1.818.1.1.17.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowerseventh | 1.3.6.1.4.1.818.1.1.17.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmseventh | 1.3.6.1.4.1.818.1.1.17.6 | |||
| G32 upsAlarmsPresentseventh | 1.3.6.1.4.1.818.1.1.17.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmSeventhTable | 1.3.6.1.4.1.818.1.1.17.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmSeventhEntry | 1.3.6.1.4.1.818.1.1.17.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdseventh | 1.3.6.1.4.1.818.1.1.17.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescrseventh | 1.3.6.1.4.1.818.1.1.17.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimeseventh | 1.3.6.1.4.1.818.1.1.17.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmsseventh | 1.3.6.1.4.1.818.1.1.17.6.3 | |||
| upsAlarmBatteryBadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatteryseventh | 1.3.6.1.4.1.818.1.1.17.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatteryseventh | 1.3.6.1.4.1.818.1.1.17.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatteryseventh | 1.3.6.1.4.1.818.1.1.17.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypassseventh | 1.3.6.1.4.1.818.1.1.17.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadseventh | 1.3.6.1.4.1.818.1.1.17.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedseventh | 1.3.6.1.4.1.818.1.1.17.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedseventh | 1.3.6.1.4.1.818.1.1.17.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedseventh | 1.3.6.1.4.1.818.1.1.17.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOffseventh | 1.3.6.1.4.1.818.1.1.17.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOffseventh | 1.3.6.1.4.1.818.1.1.17.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaultseventh | 1.3.6.1.4.1.818.1.1.17.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedseventh | 1.3.6.1.4.1.818.1.1.17.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLostseventh | 1.3.6.1.4.1.818.1.1.17.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowerseventh | 1.3.6.1.4.1.818.1.1.17.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingseventh | 1.3.6.1.4.1.818.1.1.17.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminentseventh | 1.3.6.1.4.1.818.1.1.17.6.3.23 | The UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgressseventh | 1.3.6.1.4.1.818.1.1.17.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOffseventh | 1.3.6.1.4.1.818.1.1.17.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.28 | A problem on the Connectivity Bus communication is detected. | ||
| upsAlarmHighSpeedBusJBCRCFailureseventh | 1.3.6.1.4.1.818.1.1.17.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingseventh | 1.3.6.1.4.1.818.1.1.17.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRippleseventh | 1.3.6.1.4.1.818.1.1.17.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAseventh | 1.3.6.1.4.1.818.1.1.17.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTestseventh | 1.3.6.1.4.1.818.1.1.17.7 | |||
| OID upsTestIdseventh | 1.3.6.1.4.1.818.1.1.17.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockseventh | 1.3.6.1.4.1.818.1.1.17.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummaryseventh | 1.3.6.1.4.1.818.1.1.17.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetailseventh | 1.3.6.1.4.1.818.1.1.17.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimeseventh | 1.3.6.1.4.1.818.1.1.17.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimeseventh | 1.3.6.1.4.1.818.1.1.17.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestsseventh | 1.3.6.1.4.1.818.1.1.17.7.7 | |||
| upsTestNoTestsInitiatedseventh | 1.3.6.1.4.1.818.1.1.17.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgressseventh | 1.3.6.1.4.1.818.1.1.17.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTestseventh | 1.3.6.1.4.1.818.1.1.17.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTestseventh | 1.3.6.1.4.1.818.1.1.17.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationseventh | 1.3.6.1.4.1.818.1.1.17.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControlseventh | 1.3.6.1.4.1.818.1.1.17.8 | |||
| INT upsShutdownTypeseventh | 1.3.6.1.4.1.818.1.1.17.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelayseventh | 1.3.6.1.4.1.818.1.1.17.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of sevenths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of sevenths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelayseventh | 1.3.6.1.4.1.818.1.1.17.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of sevenths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of sevenths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationseventh | 1.3.6.1.4.1.818.1.1.17.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of sevenths, after which time the output will be started, including starting the UPS, if necessary. If the number of sevenths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 sevenths. When read, upsRebootWithDuration shall return the number of sevenths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestartseventh | 1.3.6.1.4.1.818.1.1.17.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumseventh | 1.3.6.1.4.1.818.1.1.17.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleSeventhTable | 1.3.6.1.4.1.818.1.1.17.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleSeventhEntry | 1.3.6.1.4.1.818.1.1.17.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOffseventh | 1.3.6.1.4.1.818.1.1.17.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModeseventh | 1.3.6.1.4.1.818.1.1.17.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOffseventh | 1.3.6.1.4.1.818.1.1.17.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodseventh | 1.3.6.1.4.1.818.1.1.17.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOffseventh | 1.3.6.1.4.1.818.1.1.17.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOffseventh | 1.3.6.1.4.1.818.1.1.17.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourceseventh | 1.3.6.1.4.1.818.1.1.17.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigseventh | 1.3.6.1.4.1.818.1.1.17.9 | |||
| NUM upsConfigInputVoltageseventh | 1.3.6.1.4.1.818.1.1.17.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqseventh | 1.3.6.1.4.1.818.1.1.17.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltageseventh | 1.3.6.1.4.1.818.1.1.17.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqseventh | 1.3.6.1.4.1.818.1.1.17.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAseventh | 1.3.6.1.4.1.818.1.1.17.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowerseventh | 1.3.6.1.4.1.818.1.1.17.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimeseventh | 1.3.6.1.4.1.818.1.1.17.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatusseventh | 1.3.6.1.4.1.818.1.1.17.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointseventh | 1.3.6.1.4.1.818.1.1.17.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointseventh | 1.3.6.1.4.1.818.1.1.17.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacityseventh | 1.3.6.1.4.1.818.1.1.17.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrentseventh | 1.3.6.1.4.1.818.1.1.17.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdownseventh | 1.3.6.1.4.1.818.1.1.17.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelayseventh | 1.3.6.1.4.1.818.1.1.17.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSetseventh | 1.3.6.1.4.1.818.1.1.17.10 | |||
| NUM upsEventGetNextseventh | 1.3.6.1.4.1.818.1.1.17.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviousseventh | 1.3.6.1.4.1.818.1.1.17.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampseventh | 1.3.6.1.4.1.818.1.1.17.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampseventh | 1.3.6.1.4.1.818.1.1.17.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizeseventh | 1.3.6.1.4.1.818.1.1.17.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventSeventhTable | 1.3.6.1.4.1.818.1.1.17.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventSeventhEntry | 1.3.6.1.4.1.818.1.1.17.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodeseventh | 1.3.6.1.4.1.818.1.1.17.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatusseventh | 1.3.6.1.4.1.818.1.1.17.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimeseventh | 1.3.6.1.4.1.818.1.1.17.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadseventh | 1.3.6.1.4.1.818.1.1.17.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWriteseventh | 1.3.6.1.4.1.818.1.1.17.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the seventh value of the table with the lowest index number. |
| NUM upsParametersStartAddressseventh | 1.3.6.1.4.1.818.1.1.17.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizeseventh | 1.3.6.1.4.1.818.1.1.17.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterSeventhTable | 1.3.6.1.4.1.818.1.1.17.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterSeventhEntry | 1.3.6.1.4.1.818.1.1.17.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexseventh | 1.3.6.1.4.1.818.1.1.17.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValueseventh | 1.3.6.1.4.1.818.1.1.17.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatusseventh | 1.3.6.1.4.1.818.1.1.17.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfailseventh | 1.3.6.1.4.1.818.1.1.17.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfailseventh | 1.3.6.1.4.1.818.1.1.17.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2seventh | 1.3.6.1.4.1.818.1.1.17.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5seventh | 1.3.6.1.4.1.818.1.1.17.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10seventh | 1.3.6.1.4.1.818.1.1.17.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200seventh | 1.3.6.1.4.1.818.1.1.17.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRelseventh | 1.3.6.1.4.1.818.1.1.17.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimeseventh | 1.3.6.1.4.1.818.1.1.17.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPseventhERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissionseventh | 1.3.6.1.4.1.818.1.1.17.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodeseventh | 1.3.6.1.4.1.818.1.1.17.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockseventh | 1.3.6.1.4.1.818.1.1.17.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockseventh | 1.3.6.1.4.1.818.1.1.17.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapsseventh | 1.3.6.1.4.1.818.1.1.17.11 | |||
| NTF upsTrapAlarmBatteryBadseventh | 1.3.6.1.4.1.818.1.1.17.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatteryseventh | 1.3.6.1.4.1.818.1.1.17.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatteryseventh | 1.3.6.1.4.1.818.1.1.17.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatteryseventh | 1.3.6.1.4.1.818.1.1.17.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadseventh | 1.3.6.1.4.1.818.1.1.17.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadseventh | 1.3.6.1.4.1.818.1.1.17.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadseventh | 1.3.6.1.4.1.818.1.1.17.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadseventh | 1.3.6.1.4.1.818.1.1.17.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypassseventh | 1.3.6.1.4.1.818.1.1.17.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadseventh | 1.3.6.1.4.1.818.1.1.17.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedseventh | 1.3.6.1.4.1.818.1.1.17.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedseventh | 1.3.6.1.4.1.818.1.1.17.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedseventh | 1.3.6.1.4.1.818.1.1.17.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOffseventh | 1.3.6.1.4.1.818.1.1.17.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOffseventh | 1.3.6.1.4.1.818.1.1.17.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaultseventh | 1.3.6.1.4.1.818.1.1.17.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedseventh | 1.3.6.1.4.1.818.1.1.17.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLostseventh | 1.3.6.1.4.1.818.1.1.17.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowerseventh | 1.3.6.1.4.1.818.1.1.17.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingseventh | 1.3.6.1.4.1.818.1.1.17.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminentseventh | 1.3.6.1.4.1.818.1.1.17.11.23 | The UPS will turn off power to the load in less than 5 sevenths; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgressseventh | 1.3.6.1.4.1.818.1.1.17.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOffseventh | 1.3.6.1.4.1.818.1.1.17.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.28 | A problem on the Connectivity Bus communication is detected | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailureseventh | 1.3.6.1.4.1.818.1.1.17.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOnseventh | 1.3.6.1.4.1.818.1.1.17.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOnseventh | 1.3.6.1.4.1.818.1.1.17.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOnseventh | 1.3.6.1.4.1.818.1.1.17.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestoreseventh | 1.3.6.1.4.1.818.1.1.17.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestoreseventh | 1.3.6.1.4.1.818.1.1.17.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestoreseventh | 1.3.6.1.4.1.818.1.1.17.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLowseventh | 1.3.6.1.4.1.818.1.1.17.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHighseventh | 1.3.6.1.4.1.818.1.1.17.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredseventh | 1.3.6.1.4.1.818.1.1.17.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticseventh | 1.3.6.1.4.1.818.1.1.17.12 | |||
| I32 upsDiagnosticBusJACommunicationStatusseventh | 1.3.6.1.4.1.818.1.1.17.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatusseventh | 1.3.6.1.4.1.818.1.1.17.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimeseventh | 1.3.6.1.4.1.818.1.1.17.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimeseventh | 1.3.6.1.4.1.818.1.1.17.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimeseventh | 1.3.6.1.4.1.818.1.1.17.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimeseventh | 1.3.6.1.4.1.818.1.1.17.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckseventh | 1.3.6.1.4.1.818.1.1.17.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geEighthUPS | 1.3.6.1.4.1.818.1.1.18 | |||
| upsIdenteighth | 1.3.6.1.4.1.818.1.1.18.1 | |||
| STR upsIdentManufacturereighth | 1.3.6.1.4.1.818.1.1.18.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModeleighth | 1.3.6.1.4.1.818.1.1.18.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersioneighth | 1.3.6.1.4.1.818.1.1.18.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersioneighth | 1.3.6.1.4.1.818.1.1.18.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentNameeighth | 1.3.6.1.4.1.818.1.1.18.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDeviceseighth | 1.3.6.1.4.1.818.1.1.18.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumbereighth | 1.3.6.1.4.1.818.1.1.18.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersioneighth | 1.3.6.1.4.1.818.1.1.18.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTimeeighth | 1.3.6.1.4.1.818.1.1.18.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBatteryeighth | 1.3.6.1.4.1.818.1.1.18.2 | |||
| INT upsBatteryStatuseighth | 1.3.6.1.4.1.818.1.1.18.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| NUM upsSecondsOnBatteryeighth | 1.3.6.1.4.1.818.1.1.18.2.2 | NonNegativeInteger32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemainingeighth | 1.3.6.1.4.1.818.1.1.18.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemainingeighth | 1.3.6.1.4.1.818.1.1.18.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltageeighth | 1.3.6.1.4.1.818.1.1.18.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrenteighth | 1.3.6.1.4.1.818.1.1.18.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperatureeighth | 1.3.6.1.4.1.818.1.1.18.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| I32 upsBatteryRippleeighth | 1.3.6.1.4.1.818.1.1.18.2.8 | Integer32 | read-only | The present DC link RMS voltage ripple.(*) |
| upsInputeighth | 1.3.6.1.4.1.818.1.1.18.3 | |||
| C32 upsInputLineBadseighth | 1.3.6.1.4.1.818.1.1.18.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLineseighth | 1.3.6.1.4.1.818.1.1.18.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputEighthTable | 1.3.6.1.4.1.818.1.1.18.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputEighthEntry | 1.3.6.1.4.1.818.1.1.18.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequencyeighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltageeighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrenteighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePowereighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMineighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMaxeighth | 1.3.6.1.4.1.818.1.1.18.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutputeighth | 1.3.6.1.4.1.818.1.1.18.4 | |||
| INT upsOutputSourceeighth | 1.3.6.1.4.1.818.1.1.18.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequencyeighth | 1.3.6.1.4.1.818.1.1.18.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLineseighth | 1.3.6.1.4.1.818.1.1.18.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputEighthTable | 1.3.6.1.4.1.818.1.1.18.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputEighthEntry | 1.3.6.1.4.1.818.1.1.18.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltageeighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrenteighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPowereighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoadeighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| I32 upsOutputPowerFactoreighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.6 | Integer32 | read-only | The present output power factor. The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If the measure is not available due to a small load for a consistent calculation, the NA value is then returned.(*) |
| I32 upsOutputPeakCurrenteighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.7 | Integer32 | read-only | The present output peak current.(*) |
| I32 upsOutputShareCurrenteighth | 1.3.6.1.4.1.818.1.1.18.4.4.1.8 | Integer32 | read-only | In a parallel system ideally all the UPS are requested to contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UPS, so that this current component doesn't feed the load. The share part of the UPS current represents an undesired UPS loading, and therefore it should be minimized. If the share current is too high, the UPS results overloaded and in some conditions (i.e. very high load) the system could turn on bypass reducing dramatically the global system reliability. PMAD detects the amount of share currents in a parallel system, generating an alarm if this value is above a parameter-based threshold. Single UPS systems don't have this feature, NA will be provided.(*) |
| upsBypasseighth | 1.3.6.1.4.1.818.1.1.18.5 | |||
| NUM upsBypassFrequencyeighth | 1.3.6.1.4.1.818.1.1.18.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLineseighth | 1.3.6.1.4.1.818.1.1.18.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassEighthTable | 1.3.6.1.4.1.818.1.1.18.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassEighthEntry | 1.3.6.1.4.1.818.1.1.18.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltageeighth | 1.3.6.1.4.1.818.1.1.18.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrenteighth | 1.3.6.1.4.1.818.1.1.18.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPowereighth | 1.3.6.1.4.1.818.1.1.18.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarmeighth | 1.3.6.1.4.1.818.1.1.18.6 | |||
| G32 upsAlarmsPresenteighth | 1.3.6.1.4.1.818.1.1.18.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmEighthTable | 1.3.6.1.4.1.818.1.1.18.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmEighthEntry | 1.3.6.1.4.1.818.1.1.18.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmIdeighth | 1.3.6.1.4.1.818.1.1.18.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescreighth | 1.3.6.1.4.1.818.1.1.18.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTimeeighth | 1.3.6.1.4.1.818.1.1.18.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarmseighth | 1.3.6.1.4.1.818.1.1.18.6.3 | |||
| upsAlarmBatteryBadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBatteryeighth | 1.3.6.1.4.1.818.1.1.18.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBatteryeighth | 1.3.6.1.4.1.818.1.1.18.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBatteryeighth | 1.3.6.1.4.1.818.1.1.18.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverloadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypasseighth | 1.3.6.1.4.1.818.1.1.18.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBadeighth | 1.3.6.1.4.1.818.1.1.18.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequestedeighth | 1.3.6.1.4.1.818.1.1.18.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequestedeighth | 1.3.6.1.4.1.818.1.1.18.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailedeighth | 1.3.6.1.4.1.818.1.1.18.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOffeighth | 1.3.6.1.4.1.818.1.1.18.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOffeighth | 1.3.6.1.4.1.818.1.1.18.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFaulteighth | 1.3.6.1.4.1.818.1.1.18.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailedeighth | 1.3.6.1.4.1.818.1.1.18.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLosteighth | 1.3.6.1.4.1.818.1.1.18.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPowereighth | 1.3.6.1.4.1.818.1.1.18.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPendingeighth | 1.3.6.1.4.1.818.1.1.18.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminenteighth | 1.3.6.1.4.1.818.1.1.18.6.3.23 | The UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgresseighth | 1.3.6.1.4.1.818.1.1.18.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOffeighth | 1.3.6.1.4.1.818.1.1.18.6.3.25 | The receptacle are switch off | ||
| upsAlarmHighSpeedBusFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.26 | A problem on the High Speed Bus communication is detected | ||
| upsAlarmHighSpeedBusJACRCFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.27 | A High Speed Bus CRC failure on Bus JA is detected. | ||
| upsAlarmConnectivityBusFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.28 | A problem on the Connectivity Bus communication is detected | ||
| upsAlarmHighSpeedBusJBCRCFailureeighth | 1.3.6.1.4.1.818.1.1.18.6.3.29 | A High Speed Bus CRC failure on Bus JB is detected. | ||
| upsAlarmCurrentSharingeighth | 1.3.6.1.4.1.818.1.1.18.6.3.30 | The UPS detects an high current sharing on the parallel system. | ||
| upsAlarmDCRippleeighth | 1.3.6.1.4.1.818.1.1.18.6.3.31 | The UPS detects an high ripple voltage on his DC link. | ||
| U32 upsAlarmMaskAeighth | 1.3.6.1.4.1.818.1.1.18.6.4 | Unsigned32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTesteighth | 1.3.6.1.4.1.818.1.1.18.7 | |||
| OID upsTestIdeighth | 1.3.6.1.4.1.818.1.1.18.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLockeighth | 1.3.6.1.4.1.818.1.1.18.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: tryagain: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lockvalue = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lockvalue, upsTestId = requestedtest) if (errorindex == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto tryagain } if (errorindex == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lockvalue + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummaryeighth | 1.3.6.1.4.1.818.1.1.18.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetaileighth | 1.3.6.1.4.1.818.1.1.18.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTimeeighth | 1.3.6.1.4.1.818.1.1.18.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTimeeighth | 1.3.6.1.4.1.818.1.1.18.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTestseighth | 1.3.6.1.4.1.818.1.1.18.7.7 | |||
| upsTestNoTestsInitiatedeighth | 1.3.6.1.4.1.818.1.1.18.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgresseighth | 1.3.6.1.4.1.818.1.1.18.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTesteighth | 1.3.6.1.4.1.818.1.1.18.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTesteighth | 1.3.6.1.4.1.818.1.1.18.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibrationeighth | 1.3.6.1.4.1.818.1.1.18.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControleighth | 1.3.6.1.4.1.818.1.1.18.8 | |||
| INT upsShutdownTypeeighth | 1.3.6.1.4.1.818.1.1.18.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelayeighth | 1.3.6.1.4.1.818.1.1.18.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of eighths, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of eighths remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelayeighth | 1.3.6.1.4.1.818.1.1.18.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of eighths, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of eighths until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDurationeighth | 1.3.6.1.4.1.818.1.1.18.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of eighths, after which time the output will be started, including starting the UPS, if necessary. If the number of eighths required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 eighths. When read, upsRebootWithDuration shall return the number of eighths remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestarteighth | 1.3.6.1.4.1.818.1.1.18.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNumeighth | 1.3.6.1.4.1.818.1.1.18.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleEighthTable | 1.3.6.1.4.1.818.1.1.18.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleEighthEntry | 1.3.6.1.4.1.818.1.1.18.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOffeighth | 1.3.6.1.4.1.818.1.1.18.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSModeeighth | 1.3.6.1.4.1.818.1.1.18.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOffeighth | 1.3.6.1.4.1.818.1.1.18.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethodeighth | 1.3.6.1.4.1.818.1.1.18.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOffeighth | 1.3.6.1.4.1.818.1.1.18.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOffeighth | 1.3.6.1.4.1.818.1.1.18.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSourceeighth | 1.3.6.1.4.1.818.1.1.18.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfigeighth | 1.3.6.1.4.1.818.1.1.18.9 | |||
| NUM upsConfigInputVoltageeighth | 1.3.6.1.4.1.818.1.1.18.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreqeighth | 1.3.6.1.4.1.818.1.1.18.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltageeighth | 1.3.6.1.4.1.818.1.1.18.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreqeighth | 1.3.6.1.4.1.818.1.1.18.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVAeighth | 1.3.6.1.4.1.818.1.1.18.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPowereighth | 1.3.6.1.4.1.818.1.1.18.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTimeeighth | 1.3.6.1.4.1.818.1.1.18.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatuseighth | 1.3.6.1.4.1.818.1.1.18.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPointeighth | 1.3.6.1.4.1.818.1.1.18.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPointeighth | 1.3.6.1.4.1.818.1.1.18.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacityeighth | 1.3.6.1.4.1.818.1.1.18.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrenteighth | 1.3.6.1.4.1.818.1.1.18.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdowneighth | 1.3.6.1.4.1.818.1.1.18.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelayeighth | 1.3.6.1.4.1.818.1.1.18.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSeteighth | 1.3.6.1.4.1.818.1.1.18.10 | |||
| NUM upsEventGetNexteighth | 1.3.6.1.4.1.818.1.1.18.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPreviouseighth | 1.3.6.1.4.1.818.1.1.18.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMPNOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStampeighth | 1.3.6.1.4.1.818.1.1.18.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStampeighth | 1.3.6.1.4.1.818.1.1.18.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSizeeighth | 1.3.6.1.4.1.818.1.1.18.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventEighthTable | 1.3.6.1.4.1.818.1.1.18.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventEighthEntry | 1.3.6.1.4.1.818.1.1.18.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| I32 upsEventCodeeighth | 1.3.6.1.4.1.818.1.1.18.10.6.1.2 | Integer32 | read-only | The event code in numerical format. |
| NUM upsEventStatuseighth | 1.3.6.1.4.1.818.1.1.18.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
| NUM upsEventTimeeighth | 1.3.6.1.4.1.818.1.1.18.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersReadeighth | 1.3.6.1.4.1.818.1.1.18.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWriteeighth | 1.3.6.1.4.1.818.1.1.18.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the eighth value of the table with the lowest index number. |
| NUM upsParametersStartAddresseighth | 1.3.6.1.4.1.818.1.1.18.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSizeeighth | 1.3.6.1.4.1.818.1.1.18.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterEighthTable | 1.3.6.1.4.1.818.1.1.18.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterEighthEntry | 1.3.6.1.4.1.818.1.1.18.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndexeighth | 1.3.6.1.4.1.818.1.1.18.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValueeighth | 1.3.6.1.4.1.818.1.1.18.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatuseighth | 1.3.6.1.4.1.818.1.1.18.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues |
| NUM upsMainsStatisticsMBfaileighth | 1.3.6.1.4.1.818.1.1.18.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfaileighth | 1.3.6.1.4.1.818.1.1.18.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2eighth | 1.3.6.1.4.1.818.1.1.18.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5eighth | 1.3.6.1.4.1.818.1.1.18.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10eighth | 1.3.6.1.4.1.818.1.1.18.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200eighth | 1.3.6.1.4.1.818.1.1.18.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypReleighth | 1.3.6.1.4.1.818.1.1.18.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTimeeighth | 1.3.6.1.4.1.818.1.1.18.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMPeighthERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermissioneighth | 1.3.6.1.4.1.818.1.1.18.10.21 | DisplayString | read-write | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCodeeighth | 1.3.6.1.4.1.818.1.1.18.10.22 | Integer32 | read-write | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLockeighth | 1.3.6.1.4.1.818.1.1.18.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLockeighth | 1.3.6.1.4.1.818.1.1.18.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTrapseighth | 1.3.6.1.4.1.818.1.1.18.11 | |||
| NTF upsTrapAlarmBatteryBadeighth | 1.3.6.1.4.1.818.1.1.18.11.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsTrapAlarmOnBatteryeighth | 1.3.6.1.4.1.818.1.1.18.11.2 | The UPS is drawing power from the batteries. | ||
| NTF upsTrapAlarmLowBatteryeighth | 1.3.6.1.4.1.818.1.1.18.11.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsTrapAlarmDepletedBatteryeighth | 1.3.6.1.4.1.818.1.1.18.11.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsTrapAlarmTempBadeighth | 1.3.6.1.4.1.818.1.1.18.11.5 | A temperature is out of tolerance. | ||
| NTF upsTrapAlarmInputBadeighth | 1.3.6.1.4.1.818.1.1.18.11.6 | An input condition is out of tolerance. | ||
| NTF upsTrapAlarmOutputBadeighth | 1.3.6.1.4.1.818.1.1.18.11.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsTrapAlarmOutputOverloadeighth | 1.3.6.1.4.1.818.1.1.18.11.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsTrapAlarmOnBypasseighth | 1.3.6.1.4.1.818.1.1.18.11.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapAlarmBypassBadeighth | 1.3.6.1.4.1.818.1.1.18.11.10 | The Bypass is out of tolerance. | ||
| NTF upsTrapAlarmOutputOffAsRequestedeighth | 1.3.6.1.4.1.818.1.1.18.11.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsTrapAlarmUpsOffAsRequestedeighth | 1.3.6.1.4.1.818.1.1.18.11.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsTrapAlarmChargerFailedeighth | 1.3.6.1.4.1.818.1.1.18.11.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsTrapAlarmUpsOutputOffeighth | 1.3.6.1.4.1.818.1.1.18.11.14 | The output of the UPS is in the off state. | ||
| NTF upsTrapAlarmUpsSystemOffeighth | 1.3.6.1.4.1.818.1.1.18.11.15 | The UPS system is in the off state. | ||
| NTF upsTrapAlarmFanFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsTrapAlarmFuseFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.17 | The failure of one or more fuses has been detected. | ||
| NTF upsTrapAlarmGeneralFaulteighth | 1.3.6.1.4.1.818.1.1.18.11.18 | A general fault in the UPS has been detected. | ||
| NTF upsTrapAlarmDiagnosticTestFailedeighth | 1.3.6.1.4.1.818.1.1.18.11.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsTrapAlarmCommunicationsLosteighth | 1.3.6.1.4.1.818.1.1.18.11.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsTrapAlarmAwaitingPowereighth | 1.3.6.1.4.1.818.1.1.18.11.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsTrapAlarmShutdownPendingeighth | 1.3.6.1.4.1.818.1.1.18.11.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsTrapAlarmShutdownImminenteighth | 1.3.6.1.4.1.818.1.1.18.11.23 | The UPS will turn off power to the load in less than 5 eighths; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsTrapAlarmTestInProgresseighth | 1.3.6.1.4.1.818.1.1.18.11.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsTrapAlarmReceptacleOffeighth | 1.3.6.1.4.1.818.1.1.18.11.25 | A receptacle has been switched off. | ||
| NTF upsTrapAlarmHighspeedBusFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.26 | A problem on the Highspeed Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJACRCFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.27 | A CRC failure on the Highspeed Bus JA is detected. | ||
| NTF upsTrapAlarmConnectivityBusFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.28 | A problem on the Connectivity Bus communication is detected. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.29 | A CRC failure on the Highspeed Bus JB is detected. | ||
| NTF upsTrapAlarmCurrentSharingFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.30 | An high current sharing on the parallel system is detected. | ||
| NTF upsTrapAlarmDCRippleFailureeighth | 1.3.6.1.4.1.818.1.1.18.11.31 | An high ripple voltage on his DC link is detected. | ||
| NTF upsTrapAlarmBatteryBadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.33 | A Battery bad condition is restored. | ||
| NTF upsTrapAlarmOnBatteryRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.34 | The UPS is drawing power from mains again. | ||
| NTF upsTrapAlarmLowBatteryRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.35 | A Low Battery condition is restored. | ||
| NTF upsTrapAlarmDepletedBatteryRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.36 | A Depleted Battery condition is restored. | ||
| NTF upsTrapAlarmTempBadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.37 | A bad temperature condition is restored. | ||
| NTF upsTrapAlarmInputBadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.38 | An input bad condition is restored. | ||
| NTF upsTrapAlarmOutputBadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.39 | An output bad condition is restored. | ||
| NTF upsTrapAlarmOutputOverloadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.40 | An output overload condition is restored. | ||
| NTF upsTrapAlarmOnBypassRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.41 | An On Bypass condition is restored. | ||
| NTF upsTrapAlarmBypassBadRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.42 | A Bypass bad condition is restored. | ||
| NTF upsTrapAlarmOutputOffAsRequestedRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.43 | A request shutdown has been restored. | ||
| NTF upsTrapAlarmUpsOffAsRequestedRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.44 | A entire UPS command has been restored. | ||
| NTF upsTrapAlarmChargerFailedRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.45 | A Charger Failer condition is restored. | ||
| NTF upsTrapAlarmUpsOutputOneighth | 1.3.6.1.4.1.818.1.1.18.11.46 | The output of the UPS switched in the on state. | ||
| NTF upsTrapAlarmUpsSystemOneighth | 1.3.6.1.4.1.818.1.1.18.11.47 | The UPS system is switched in the on state. | ||
| NTF upsTrapAlarmFanFailureRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.48 | A Fan failure condition is restored. | ||
| NTF upsTrapAlarmFuseFailureRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.49 | A Fuse failure condition is restored. | ||
| NTF upsTrapAlarmGeneralFaultRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.50 | A general fault is restored. | ||
| NTF upsTrapAlarmDiagnosticTestFailedRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsTrapAlarmCommunicationsLostRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsTrapAlarmAwaitingPowerRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.53 | A awaiting power condition is restored (*). | ||
| NTF upsTrapAlarmShutdownPendingRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsTrapAlarmShutdownImminentRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.55 | A shutdown imminent condition is restored. | ||
| NTF upsTrapAlarmTestInProgressRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.56 | The test is in progress is terminated. | ||
| NTF upsTrapAlarmReceptacleOneighth | 1.3.6.1.4.1.818.1.1.18.11.57 | A receptacle has been switched on. | ||
| NTF upsTrapAlarmHighspeedBusRestoreeighth | 1.3.6.1.4.1.818.1.1.18.11.58 | A problem on the Highspeed Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJACRCRestoreeighth | 1.3.6.1.4.1.818.1.1.18.11.59 | A CRC failure on the Highspeed Bus JA is restored. | ||
| NTF upsTrapAlarmConnectivityBusRestoreeighth | 1.3.6.1.4.1.818.1.1.18.11.60 | A problem on the Connectivity Bus communication is restored. | ||
| NTF upsTrapAlarmHighspeedBusJBCRCRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.61 | A CRC failure on the Highspeed Bus JB is restored. | ||
| NTF upsTrapAlarmCurrentSharingRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.62 | An high current sharing on the parallel system is restored. | ||
| NTF upsTrapAlarmDCRippleRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.63 | An high ripple voltage on his DC link is restored. | ||
| NTF upsTrapAlarmValueLoweighth | 1.3.6.1.4.1.818.1.1.18.11.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsTrapAlarmValueHigheighth | 1.3.6.1.4.1.818.1.1.18.11.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsTrapAlarmValueLowRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.133 | A ValueLow alarm condition is restored. | ||
| NTF upsTrapAlarmValueHighRestoredeighth | 1.3.6.1.4.1.818.1.1.18.11.134 | A ValueHigh alarm condition is restored. | ||
| upsDiagnosticeighth | 1.3.6.1.4.1.818.1.1.18.12 | |||
| I32 upsDiagnosticBusJACommunicationStatuseighth | 1.3.6.1.4.1.818.1.1.18.12.1 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBusJBCommunicationStatuseighth | 1.3.6.1.4.1.818.1.1.18.12.2 | Integer32 | read-only | Bit oriented values associated to the ID of the UPS (bit0 = UPS1 ... bit7 = UPS8). The correspondent UPS is not present on the high speed bus communication JA if bit=0.(*) |
| I32 upsDiagnosticBatteryLifetimeeighth | 1.3.6.1.4.1.818.1.1.18.12.3 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticFansLifetimeeighth | 1.3.6.1.4.1.818.1.1.18.12.4 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticDCcapacitorsLifetimeeighth | 1.3.6.1.4.1.818.1.1.18.12.5 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticACcapacitorsLifetimeeighth | 1.3.6.1.4.1.818.1.1.18.12.6 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| I32 upsDiagnosticGlobalServiceCheckeighth | 1.3.6.1.4.1.818.1.1.18.12.7 | Integer32 | read-only | The critical components are associated to Service parameters indicating the remaining lifetime. They are initially set to default values depending to the data given by the component supplier. The parameter values decrease over time and when one of them reaches zero (lifetime expiration) a service check warning is generated, indicating that a check or a replacement is suggested for that component. The service technician is then required to re-set the default value after the replacing of the component.(*) |
| geDevices | 1.3.6.1.4.1.818.1.100 | |||
| geDevicesDescriptions | 1.3.6.1.4.1.818.1.100.1 | |||
| advSNMPWebIntCard | 1.3.6.1.4.1.818.1.100.1.1 | |||
| snmpWebIntCard | 1.3.6.1.4.1.818.1.100.1.2 | |||
| snmpWebIntBox | 1.3.6.1.4.1.818.1.100.1.3 |
RFC description
GE parallel UPS monitoring for battery, power factor, diagnostics, and multi-unit system management.