LIEBERT-GP-CONDITIONS-MIB

MIB Reference — IPNetwork Monitor

All MIBsLIEBERT-GP-CONDITIONS-MIB

Organization: Liebert Corporation

Last Updated: 2013-02-12

Category: Alarm and Event Management, Domain: Power Management, Domain: Power/UPS, Hardware and Environment

Description:

Liebert Corporation MIB defining alarm conditions and event status monitoring for Liebert power and cooling infrastructure.

Imported Objects

From LIEBERT-GP-REGISTRATION-MIB

lgpConditionsOBJECT-IDENTITY
liebertConditionsModuleRegOBJECT-IDENTITY

From SNMPv2-SMI

Gauge32
MODULE-IDENTITY
OBJECT-IDENTITY
OBJECT-TYPE
TimeTicks
Unsigned32

From SNMPv2-TC

DisplayString

What Is LIEBERT-GP-CONDITIONS-MIB?

LIEBERT-GP-CONDITIONS-MIB is a vendor proprietary MIB from Liebert Corporation (now Vertiv) covering power and cooling infrastructure such as UPS units and precision (CRAC) cooling systems used in data centers. It exposes a generalized 'conditions' framework rather than fixed named sensors, listing currently active alarm/status condition entries along with their descriptions and well-known condition-type identifiers. It is specifically built for monitoring hardware status: it reports whether any alarm condition is currently present and details each active condition, which in practice surfaces things like environmental faults, power issues, or cooling failures on the monitored unit. It is typically used alongside other Liebert enterprise MIBs (e.g. registration/identity MIBs) that identify the specific device model. It is typically deployed in data center facilities monitoring Liebert UPS and cooling equipment through an NMS to catch faults quickly. Facilities teams configuring LIEBERT-GP-CONDITIONS-MIB SNMP monitoring for a data center typically pair it with polling intervals short enough to catch a transient cooling or power condition before it escalates.

IPNetwork Monitor allows you to monitor SNMP objects defined in LIEBERT-GP-CONDITIONS-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.

What Can Be Monitored

  • active alarm conditions present
  • condition descriptions
  • well-known condition type codes
  • vendor-specific flexible conditions
  • condition acknowledge/reset control
  • device network name

Supported Devices

  • Vertiv/Liebert data center power/cooling equipment (any generation, GlobalProducts conditions framework)

Monitoring Examples

An admin polling lgpConditionsTable sees every currently active alarm/condition entry, each carrying an lgpConditionDescription and a code from lgpConditionsWellKnown identifying the condition type. lgpConditionsPresent acts as a fast top-level indicator so a monitoring system can alert only when it goes non-zero rather than walking the full table on every poll. lgpConditionControlTable/lgpConditionControl let an operator acknowledge or reset condition states, while lgpFlexConditions covers vendor-defined condition types beyond the standard well-known set, and lgpNetworkName labels which unit generated the report.

OIDs
OID symbolicOID numericTypeAccessDescription
liebertGlobalProductsConditionsModule1.3.6.1.4.1.476.1.42.1.3.1The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
lgpConditionsWellKnown1.3.6.1.4.1.476.1.42.3.2.1
lgpConditionHighTemperature1.3.6.1.4.1.476.1.42.3.2.1.1The temperature has exceeded the high temperature threshold.
lgpConditionLowTemperature1.3.6.1.4.1.476.1.42.3.2.1.2The temperature is below the low temperature threshold.
lgpConditionHighHumidity1.3.6.1.4.1.476.1.42.3.2.1.3The humidity has exceeded the high humidity threshold.
lgpConditionLowHumidity1.3.6.1.4.1.476.1.42.3.2.1.4The humidity is below the low humidity threshold.
lgpConditionLossOfAirflow1.3.6.1.4.1.476.1.42.3.2.1.5The system has detected a loss of air flow.
lgpConditionLossOfAirflow11.3.6.1.4.1.476.1.42.3.2.1.5.1The system has detected a loss of air flow at sensor 1.
lgpConditionLossOfAirflow21.3.6.1.4.1.476.1.42.3.2.1.5.2The system has detected a loss of air flow at sensor 2.
lgpConditionLossOfAirflowBlower11.3.6.1.4.1.476.1.42.3.2.1.5.3The system has detected a loss of air flow from blower 1.
lgpConditionLossOfAirflowAllBlowers1.3.6.1.4.1.476.1.42.3.2.1.5.4No air flow through the unit due to failure of all blowers.
lgpConditionChangeFilter1.3.6.1.4.1.476.1.42.3.2.1.6The system has detected a condition indicating the air filter should be changed.
lgpConditionCompressorHighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7This system has detected an excessive head pressure condition.
lgpConditionCompressor1HighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.1The system has detected excessive head pressure in compressor 1.
lgpConditionCompressor1AHighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.1.1The system has detected excessive head pressure in compressor 1A.
lgpConditionCompressor1BHighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.1.2The system has detected excessive head pressure in compressor 1B.
lgpConditionCompressor2HighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.2The system has detected excessive head pressure in compressor 2.
lgpConditionCompressor2AHighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.2.1The system has detected excessive head pressure in compressor 2A.
lgpConditionCompressor2BHighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.2.2The system has detected excessive head pressure in compressor 2B.
lgpConditionCompressor3HighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.3The system has detected excessive head pressure in compressor 3.
lgpConditionCompressor4HighHeadPressure1.3.6.1.4.1.476.1.42.3.2.1.7.4The system has detected excessive head pressure in compressor 4.
lgpConditionCompressorOverload1.3.6.1.4.1.476.1.42.3.2.1.8This system has detected a compressor overload condition.
lgpConditionCompressor1Overload1.3.6.1.4.1.476.1.42.3.2.1.8.1The system has detected an overload condition on compressor 1.
lgpConditionCompressor2Overload1.3.6.1.4.1.476.1.42.3.2.1.8.2The system has detected an overload condition on compressor 2.
lgpConditionCompressorShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9A compressor has exceeded the maximum number of starts in a minimum time period.
lgpConditionCompressor1ShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.1The system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressor1AShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.1.1The system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressor1BShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.1.2The system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressor2ShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.2The system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressor2AShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.2.1The system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressor2BShortCycle1.3.6.1.4.1.476.1.42.3.2.1.9.2.2The system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time.
lgpConditionCompressorLowSuctionPressure1.3.6.1.4.1.476.1.42.3.2.1.10The pressure at a compressor inlet has dropped below the minimum setting.
lgpConditionCompressor1LowSuctionPressure1.3.6.1.4.1.476.1.42.3.2.1.10.1The pressure at compressor 1 inlet has dropped below the minimum setting.
lgpConditionCompressor2LowSuctionPressure1.3.6.1.4.1.476.1.42.3.2.1.10.2The pressure at compressor 2 inlet has dropped below the minimum setting.
lgpConditionMainFanOverLoad1.3.6.1.4.1.476.1.42.3.2.1.11The system has detected a main fan overload condition.
lgpConditionManualOverride1.3.6.1.4.1.476.1.42.3.2.1.12The system has detected a manual override condition.
lgpConditionStandbyGlycoolPumpOn1.3.6.1.4.1.476.1.42.3.2.1.13The standby Glycol or Glycool pump is activated.
lgpConditionWaterUnderFloor1.3.6.1.4.1.476.1.42.3.2.1.14Moisture has been detected under the floor.
lgpConditionHumidifierProblem1.3.6.1.4.1.476.1.42.3.2.1.15The system has detected a humidifier problem.
lgpConditionLowWaterInHumidifier1.3.6.1.4.1.476.1.42.3.2.1.16The system has detected a low water condition in the humidifier reservoir.
lgpConditionSmokeDetected1.3.6.1.4.1.476.1.42.3.2.1.17The system has detected smoke.
lgpConditionLowWaterFlow1.3.6.1.4.1.476.1.42.3.2.1.18The system has detected a low water flow rate condition.
lgpConditionLostPower1.3.6.1.4.1.476.1.42.3.2.1.19The system has lost power before being switched off using the controls. This condition is activated when power is restored.
lgpGeneralFault1.3.6.1.4.1.476.1.42.3.2.1.20A fault condition has been detected that is not identified in the well known list.
lgpConditionLocalAlarm1.3.6.1.4.1.476.1.42.3.2.1.21This system has detected a local, or customer, alarm condition.
lgpConditionLocalAlarm11.3.6.1.4.1.476.1.42.3.2.1.21.1The system has detected that customer alarm condition 1 is active.
lgpConditionLocalAlarm21.3.6.1.4.1.476.1.42.3.2.1.21.2The system has detected that customer alarm condition 2 is active.
lgpConditionLocalAlarm31.3.6.1.4.1.476.1.42.3.2.1.21.3The system has detected that customer alarm condition 3 is active.
lgpConditionLocalAlarm41.3.6.1.4.1.476.1.42.3.2.1.21.4The system has detected that customer alarm condition 4 is active.
lgpConditionLocalAlarm51.3.6.1.4.1.476.1.42.3.2.1.21.5The system has detected that customer alarm condition 5 is active.
lgpConditionLocalAlarm61.3.6.1.4.1.476.1.42.3.2.1.21.6The system has detected that customer alarm condition 6 is active.
lgpConditionLocalAlarm71.3.6.1.4.1.476.1.42.3.2.1.21.7The system has detected that customer alarm condition 7 is active.
lgpConditionLocalAlarm81.3.6.1.4.1.476.1.42.3.2.1.21.8The system has detected that customer alarm condition 8 is active.
lgpConditionStandbyUnitOn1.3.6.1.4.1.476.1.42.3.2.1.22The system has detected the standby unit is operating.
lgpConditionCompressorLowPressure1.3.6.1.4.1.476.1.42.3.2.1.23This system has detected a low head compressor condition.
lgpConditionCompressor1LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.1The system has detected low pressure in compressor 1.
lgpConditionTandemCompressorCircuit1LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.1.1The system has detected low pressure in tandem compressor circuit 1.
lgpConditionCompressor2LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.2The system has detected low pressure in compressor 2.
lgpConditionTandemCompressorCircuit2LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.2.1The system has detected low pressure in tandem compressor circuit 2.
lgpConditionCompressor3LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.3The system has detected low pressure in compressor 3.
lgpConditionCompressor4LowPressure1.3.6.1.4.1.476.1.42.3.2.1.23.4The system has detected low pressure in compressor 4.
lgpConditionHighWaterInPan1.3.6.1.4.1.476.1.42.3.2.1.24The system has detected a high water condition in the condenser pan.
lgpConditionFaultySensor1.3.6.1.4.1.476.1.42.3.2.1.25The system has detected a faulty temperature/humidity sensor.
lgpConditionServiceCooling1.3.6.1.4.1.476.1.42.3.2.1.26The Cooling system requires scheduled maintenance.
lgpConditionServiceHumidifier1.3.6.1.4.1.476.1.42.3.2.1.27The Humidifier requires scheduled maintenance.
lgpConditionSystemControlBatteryLow1.3.6.1.4.1.476.1.42.3.2.1.28Charge level of the system control's battery is below the alarm set point.
lgpConditionGroundSystemFault1.3.6.1.4.1.476.1.42.3.2.1.29The system has detected a ground system fault.
lgpConditionGroundFailure1.3.6.1.4.1.476.1.42.3.2.1.30The system has detected a ground failure.
lgpConditionSecurityBreach1.3.6.1.4.1.476.1.42.3.2.1.31The system has detected a security breach.
lgpConditionEmergencyShutdown1.3.6.1.4.1.476.1.42.3.2.1.32The system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency.
lgpConditionOnBypass1.3.6.1.4.1.476.1.42.3.2.1.33This system has detected the load is being powered by a bypass source.
lgpConditionLoadOnBypass1.3.6.1.4.1.476.1.42.3.2.1.33.1The load is being powered by a bypass source.
lgpConditionLoadOnMaintenceBypass1.3.6.1.4.1.476.1.42.3.2.1.33.2The load is being powered by a maintenance bypass source.
lgpConditionParallelSysLoadOnBypass1.3.6.1.4.1.476.1.42.3.2.1.33.3The parallel system has transferred to bypass.
lgpConditionLoadOnBypassByImpact1.3.6.1.4.1.476.1.42.3.2.1.33.4The system has detected a load impact and has transferred the load to the bypass source.
lgpConditionLoadTransferedToBypass1.3.6.1.4.1.476.1.42.3.2.1.33.5The system has transferred to bypass. The load is being powered by the bypass source.
lgpConditionEmergencyTransferToBypass1.3.6.1.4.1.476.1.42.3.2.1.33.6The system has performed an emergency transfer to bypass.
lgpConditionOutputToLoadVoltTHD1.3.6.1.4.1.476.1.42.3.2.1.34The total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionLogicFailure1.3.6.1.4.1.476.1.42.3.2.1.35The system has detected a control logic failure.
lgpConditionPowerSupplyFault1.3.6.1.4.1.476.1.42.3.2.1.36This system had detected a power supply fault condition.
lgpConditionPowerSupply1Fault1.3.6.1.4.1.476.1.42.3.2.1.36.1The system has detected power supply 1 is in a fault condition.
lgpConditionPowerSupply2Fault1.3.6.1.4.1.476.1.42.3.2.1.36.2The system has detected power supply 2 is in a fault condition.
lgpConditionPowerSupplyFailure1.3.6.1.4.1.476.1.42.3.2.1.37This system has detected a power supply failure condition.
lgpConditionPowerSupply1Failure1.3.6.1.4.1.476.1.42.3.2.1.37.1The system has detected power supply 1 has failed.
lgpConditionPowerSupply2Failure1.3.6.1.4.1.476.1.42.3.2.1.37.2The system has detected power supply 2 has failed.
lgpConditionSource1PowerSupplyInputFailure1.3.6.1.4.1.476.1.42.3.2.1.37.3The system has detected the source 1 Power supply input has failed.
lgpConditionSource2PowerSupplyInputFailure1.3.6.1.4.1.476.1.42.3.2.1.37.4The system has detected the source 2 Power supply input has failed.
lgpConditionPowerSupplyLogicFailure1.3.6.1.4.1.476.1.42.3.2.1.37.5The system has detected a power supply logic failure.
lgpConditionCompressorPowerSupplyFailure1.3.6.1.4.1.476.1.42.3.2.1.37.6The system has detected the power supply to the compressors has failed.
lgpConditionOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38This system has detected an over voltage condition.
lgpConditionSource1OverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.1The system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSource2OverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.2The system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.3The system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInputOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.4The system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time.
lgpConditionBypassOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.5The system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBypassOverVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.38.6The system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.7The system has detected a battery over voltage condition.
lgpConditionDcBusOverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.8This system has detected a DC Bus over voltage condition.
lgpConditionDcBus1OverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.8.1The system has detected an over voltage condition on DC Bus 1.
lgpConditionDcBus2OverVoltage1.3.6.1.4.1.476.1.42.3.2.1.38.8.2The system has detected an over voltage condition on DC Bus 2.
lgpConditionDcBus1OverVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.38.8.3The system has detected an over voltage failure condition on DC Bus 1.
lgpConditionDcBus2OverVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.38.8.4The system has detected an over voltage failure condition on DC Bus 2.
lgpConditionUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39This system has detected an under voltage condition.
lgpConditionSource1UnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.1The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSource2UnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.2The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.3The system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSource1UnderVoltageRMS1.3.6.1.4.1.476.1.42.3.2.1.39.4The system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
lgpConditionSource2UnderVoltageRMS1.3.6.1.4.1.476.1.42.3.2.1.39.5The system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of time.
lgpConditionInputUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.6The system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBypassUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.7The system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBypassUnderVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.39.8The system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.9The system has detected a battery under voltage condition.
lgpConditionDcBusUnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.10This system has detected a DC bus under voltage condition
lgpConditionDcBus1UnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.10.1The system has detected an under voltage condition on DC Bus 1.
lgpConditionDcBus2UnderVoltage1.3.6.1.4.1.476.1.42.3.2.1.39.10.2The system has detected an under voltage condition on DC Bus 2.
lgpConditionDcBus1UnderVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.39.10.3The system has detected an under voltage failure condition on DC Bus 1.
lgpConditionDcBus2UnderVoltageFailure1.3.6.1.4.1.476.1.42.3.2.1.39.10.4The system has detected an under voltage failure condition on DC Bus 2.
lgpConditionOverload1.3.6.1.4.1.476.1.42.3.2.1.40This system has detected an overload condition.
lgpConditionSource1Overload1.3.6.1.4.1.476.1.42.3.2.1.40.1The system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSystemOverload1.3.6.1.4.1.476.1.42.3.2.1.40.2The system has detected an overload condition.
lgpConditionSource1PeakCurrentOverLoad1.3.6.1.4.1.476.1.42.3.2.1.40.3The system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
lgpConditionSource2PeakCurrentOverLoad1.3.6.1.4.1.476.1.42.3.2.1.40.4The system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount of time.
lgpConditionOutputToLoadOverLimit1.3.6.1.4.1.476.1.42.3.2.1.40.5The system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit.
lgpConditionOutputToLoadOverload1.3.6.1.4.1.476.1.42.3.2.1.40.6The system has detected an output overload condition.
lgpConditionParallelSysOverload1.3.6.1.4.1.476.1.42.3.2.1.40.7The parallel system has detected an overload condition.
lgpConditionBypassCurrentOverload1.3.6.1.4.1.476.1.42.3.2.1.40.8With the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current.
lgpConditionBypassCurrentOverloadPhsA1.3.6.1.4.1.476.1.42.3.2.1.40.8.1With the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
lgpConditionBypassCurrentOverloadPhsB1.3.6.1.4.1.476.1.42.3.2.1.40.8.2With the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
lgpConditionBypassCurrentOverloadPhsC1.3.6.1.4.1.476.1.42.3.2.1.40.8.3With the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
lgpConditionScrShort1.3.6.1.4.1.476.1.42.3.2.1.41This system has detected a Silicon Controlled Rectifier (SCR) short condition.
lgpConditionSource1ScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.1The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition.
lgpConditionSource2ScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.2The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition.
lgpConditionBypassScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.3The system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass.
lgpConditionInvStaticSwScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.4The system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs).
lgpConditionSource1NeutralScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.5The system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
lgpConditionSource2NeutralScrShort1.3.6.1.4.1.476.1.42.3.2.1.41.6The system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
lgpConditionScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42This system has detected a Silicon Controlled Rectifier (SCR) open condition.
lgpConditionSource1ScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42.1The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition.
lgpConditionSource2ScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42.2The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition.
lgpConditionBypassScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42.3The system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass.
lgpConditionSource1NeutralScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42.4The system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
lgpConditionSource2NeutralScrOpen1.3.6.1.4.1.476.1.42.3.2.1.42.5The system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
lgpConditionFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43This system has detected a fan failure condition.
lgpConditionFan1Failure1.3.6.1.4.1.476.1.42.3.2.1.43.1The system has detected a fan 1 failure condition.
lgpConditionRedundantFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43.2A failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy.
lgpConditionMultipleFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43.3Multiple fans have failed resulting in a decreased ability to cool the system's internal components.
lgpConditionBlowerFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43.4The system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans.
lgpConditionBottomBlowerFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43.4.1The bottom environmental unit blower fan is not operating within its normal parameters.
lgpConditionTopBlowerFanFailure1.3.6.1.4.1.476.1.42.3.2.1.43.4.2The top environmental unit blower fan is not operating within its normal parameters.
lgpConditionCondenserFanVFDFailure1.3.6.1.4.1.476.1.42.3.2.1.43.5The system has detected a problem with the Variable Frequency Drive system for the condenser fan.
lgpConditionFanPowerFailure1.3.6.1.4.1.476.1.42.3.2.1.43.6The system has detected a power failure on one or more fans.
lgpConditionTransferInhibited1.3.6.1.4.1.476.1.42.3.2.1.44The system is preventing a transfer of the load to the alternate source.
lgpConditionAutoReTransferPrimed1.3.6.1.4.1.476.1.42.3.2.1.45The system is capable to retransfer to the preferred source.
lgpConditionSourcesOutOfSync1.3.6.1.4.1.476.1.42.3.2.1.46The system has detected that the input sources are not within the specified phase difference (synchronization window).
lgpConditionSourceFailure1.3.6.1.4.1.476.1.42.3.2.1.47This system has detected an input source failure condition.
lgpConditionSource1Failure1.3.6.1.4.1.476.1.42.3.2.1.47.1The system has detected source 1 has failed.
lgpConditionSource2Failure1.3.6.1.4.1.476.1.42.3.2.1.47.2The system has detected source 2 has failed.
lgpConditionAutoReTransferInhibited1.3.6.1.4.1.476.1.42.3.2.1.48The system is preventing a retransfer of the load back to the preferred source.
lgpConditionAutoReTransferFailed1.3.6.1.4.1.476.1.42.3.2.1.49The system is failing to automatically retransfer the load back to the preferred source.
lgpConditionFuseOpen1.3.6.1.4.1.476.1.42.3.2.1.50This system has detected an open fuse condition.
lgpConditionControlFuse1Open1.3.6.1.4.1.476.1.42.3.2.1.50.1The system has detected a control power fuse 1 open condition.
lgpConditionControlFuse2Open1.3.6.1.4.1.476.1.42.3.2.1.50.2The system has detected a control power fuse 2 open condition.
lgpConditionRectifierFuseOpen1.3.6.1.4.1.476.1.42.3.2.1.50.3The system has detected a rectifier fuse open condition.
lgpConditionInverterFuseOpen1.3.6.1.4.1.476.1.42.3.2.1.50.4The system has detected an inverter fuse open condition.
lgpConditionOutputToLoadFuseOpen1.3.6.1.4.1.476.1.42.3.2.1.50.5The system has detected an output to load fuse open condition.
lgpConditionDcCapacitorFuseOpen1.3.6.1.4.1.476.1.42.3.2.1.50.6The system has detected a DC capacitor fuse open condition.
lgpConditionDisconnect1.3.6.1.4.1.476.1.42.3.2.1.51The system has detected a disconnect condition.
lgpConditionSource1DisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.1The system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource2DisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.2The system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource1PduDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.3The system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource2PduDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.4The system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOutputToLoadDisconnect1Open1.3.6.1.4.1.476.1.42.3.2.1.51.5The system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOutputToLoadDisconnect2Open1.3.6.1.4.1.476.1.42.3.2.1.51.6The system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource1BypassDisconnectClosed1.3.6.1.4.1.476.1.42.3.2.1.51.7The system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource2BypassDisconnectClosed1.3.6.1.4.1.476.1.42.3.2.1.51.8The system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOutputToLoadNeutralDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.9The system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionBatteryDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.10The system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionBatteryDiscOpenCab011.3.6.1.4.1.476.1.42.3.2.1.51.10.1The system has detected the cabinet 1 battery disconnect is open.
lgpConditionBatteryDiscOpenCab021.3.6.1.4.1.476.1.42.3.2.1.51.10.2The system has detected the cabinet 2 battery disconnect is open.
lgpConditionBatteryDiscOpenCab031.3.6.1.4.1.476.1.42.3.2.1.51.10.3The system has detected the cabinet 3 battery disconnect is open.
lgpConditionBatteryDiscOpenCab041.3.6.1.4.1.476.1.42.3.2.1.51.10.4The system has detected the cabinet 4 battery disconnect is open.
lgpConditionBatteryDiscOpenCab051.3.6.1.4.1.476.1.42.3.2.1.51.10.5The system has detected the cabinet 5 battery disconnect is open.
lgpConditionBatteryDiscOpenCab061.3.6.1.4.1.476.1.42.3.2.1.51.10.6The system has detected the cabinet 6 battery disconnect is open.
lgpConditionBatteryDiscOpenCab071.3.6.1.4.1.476.1.42.3.2.1.51.10.7The system has detected the cabinet 7 battery disconnect is open.
lgpConditionBatteryDiscOpenCab081.3.6.1.4.1.476.1.42.3.2.1.51.10.8The system has detected the cabinet 8 battery disconnect is open.
lgpConditionInputDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.11The system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOutputToLoadDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.12The system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionBypassDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.13The system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionStaticSwitchDisconnectOpen1.3.6.1.4.1.476.1.42.3.2.1.51.14The system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionBreakerOpenFailure1.3.6.1.4.1.476.1.42.3.2.1.51.15A breaker in the system has failed to respond to an Open signal.
lgpConditionBreakerCloseFailure1.3.6.1.4.1.476.1.42.3.2.1.51.16A breaker in the system has failed to respond to a Close signal.
lgpConditionFrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52This system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time.
lgpConditionSource1FrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52.1The frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time.
lgpConditionSource2FrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52.2The frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time.
lgpConditionInputFrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52.3The frequency for the input has been outside of the pre-determined thresholds for a specified period of time.
lgpConditionOutputToLoadFrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52.4The frequency for the output has been outside of the pre-determined thresholds for a specified period of time.
lgpConditionBypassFrequencyDeviation1.3.6.1.4.1.476.1.42.3.2.1.52.5The frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time.
lgpConditionOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53This system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSource1OverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.1The system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionSource2OverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.2The system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.3The system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadOverCurrentPhsA1.3.6.1.4.1.476.1.42.3.2.1.53.3.1The system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadOverCurrentPhsB1.3.6.1.4.1.476.1.42.3.2.1.53.3.2The system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionOutputToLoadOverCurrentPhsC1.3.6.1.4.1.476.1.42.3.2.1.53.3.3The system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionGroundOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.4A ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionRectifierOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.5The system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.6The system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterOverCurrentPhsA1.3.6.1.4.1.476.1.42.3.2.1.53.6.1The system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterOverCurrentPhsB1.3.6.1.4.1.476.1.42.3.2.1.53.6.2The system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterOverCurrentPhsC1.3.6.1.4.1.476.1.42.3.2.1.53.6.3The system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryConverterOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.7The system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryBalancerOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.8The system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionHumidifierOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.9The system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amount of time.
lgpConditionInputOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.10There is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time.
lgpConditionSource1NeutralOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.11The system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold for a pre-defined amount of time.
lgpConditionSource2NeutralOverCurrent1.3.6.1.4.1.476.1.42.3.2.1.53.12The system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold for a pre-defined amount of time.
lgpConditionSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54This system has detected a sensor failure condition.
lgpConditionOutputToLoadVoltageSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.1The system had detected an output to load voltage sensor failure.
lgpConditionSource1VoltageSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.2The system had detected a source 1 voltage sensor failure.
lgpConditionSource2VoltageSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.3The system had detected a source 2 voltage sensor failure.
lgpConditionSource1ScrSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.4The system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure.
lgpConditionSource2ScrSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.5The system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure.
lgpConditionSource1CurrentSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.6The system has detected a source 1 current sensor failure.
lgpConditionSource2CurrentSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.7The system has detected a source 2 current sensor failure.
lgpConditionRoomTempHumiditySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.8The system has detected a device temperature and humidity sensor failure.
lgpConditionGlycolTempSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.9The system has detected a glycol temperature sensor failure.
lgpConditionLocal1SensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.10The system has detected a local 1 sensor failure.
lgpConditionCompressor1SensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.11The system has detected a compressor 1 digital scroll sensor failure condition.
lgpConditionCompressor2SensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.12The system has detected a compressor 2 digital scroll sensor failure condition.
lgpConditionSupplySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.13The system has detected a supply sensor failure.
lgpConditionCabinetTemperatureSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.14The system has detected a cabinet temperature sensor failure.
lgpConditionCabinetHumiditySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.15The system has detected a cabinet humidity sensor failure.
lgpConditionRoomTempSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.16The system has detected a room temperature sensor failure.
lgpConditionBatteryTempSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.17The system has detected a battery temperature sensor failure.
lgpConditionAirSensorAFailure1.3.6.1.4.1.476.1.42.3.2.1.54.18The system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range.
lgpConditionAirSensorBFailure1.3.6.1.4.1.476.1.42.3.2.1.54.19The system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range.
lgpConditionChilledWaterSupplySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.20The system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range.
lgpConditionRefrigerantSupplySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.21The system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range.
lgpConditionFluidSupplySensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.22The system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range.
lgpConditionCompressorLowPressureSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.23The system has detected that a compressor low pressure transducer is disconnected or the signal is out of range.
lgpConditionCompressor1LowPressureSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.23.1The system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range.
lgpConditionRemoteSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.24The system has detected that a remote sensor is disconnected or the signal is out of range.
lgpConditionAirSupplyTempSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.25The system has detected that the supply air temperature sensor is disconnected or the signal is out of range.
lgpConditionAirReturnTempSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.26The system has detected that the return air temperature sensor is disconnected or the signal is out of range.
lgpConditionCompressorHighPressureSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.54.27The system has detected that a compressor high pressure transducer is disconnected or the signal is out of range.
lgpConditionInternalCommunicationFailure1.3.6.1.4.1.476.1.42.3.2.1.55This system has detected an internal communication failure condition.
lgpConditionExternalCommunicationFailure1.3.6.1.4.1.476.1.42.3.2.1.56This system has detected an external communication failure condition.
lgpConditionSourceGateDriveFailure1.3.6.1.4.1.476.1.42.3.2.1.57This system has detected a source gate drive failure condition.
lgpConditionSource1GateDriveFailure1.3.6.1.4.1.476.1.42.3.2.1.57.1The system has detected a source 1 gate drive failure.
lgpConditionSource2GateDriveFailure1.3.6.1.4.1.476.1.42.3.2.1.57.2The system has detected a source 2 gate drive failure.
lgpConditionDisconnectFailure1.3.6.1.4.1.476.1.42.3.2.1.58This system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOutputToLoadNeutralDisconnectFailure1.3.6.1.4.1.476.1.42.3.2.1.58.1The system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource1DisconnectShuntTripFailure1.3.6.1.4.1.476.1.42.3.2.1.58.2The system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionSource2DisconnectShuntTripFailure1.3.6.1.4.1.476.1.42.3.2.1.58.3The system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionInverterDisconnectFailure1.3.6.1.4.1.476.1.42.3.2.1.58.4The system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionBatteryDisconnectFailure1.3.6.1.4.1.476.1.42.3.2.1.58.5The system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionRectifierDisconnectFailure1.3.6.1.4.1.476.1.42.3.2.1.58.6The system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker, contactor, isolating switch, disconnecting switch, etc.).
lgpConditionOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59This system has detected an over temperature condition.
lgpConditionHeatSink1OverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.1The system has detected a heat sink 1 over temperature condition.
lgpConditionAmbient1OverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.2The system has detected an ambient over temperature condition at location 1.
lgpConditionSystemOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.3The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionTransformerOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.4The transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.5The battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionRectifierOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.6The system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.7The system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionRectifierInductorOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.8The system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionInverterInductorOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.9The system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryConverterOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.10The system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a device, or system, defined amount of time.
lgpConditionBatteryBalancerInductorOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.11The system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined threshold for a specified amount of time.
lgpConditionChilledWaterOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.12The system has detected a chilled water over temperature condition.
lgpConditionElectricHeatersOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.13The system has detected an electric heater over temperature condition.
lgpConditionInletAirOverTemperature1.3.6.1.4.1.476.1.42.3.2.1.59.14The system has detected an inlet air over temperature condition.
lgpConditionSystemOverTempWarning1.3.6.1.4.1.476.1.42.3.2.1.59.15The system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a device, or system, defined amount of time. The system is still operational but a threshold has been exceeded.
lgpConditionHighTemperatureBattString1.3.6.1.4.1.476.1.42.3.2.1.59.16The system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold.
lgpConditionLoadOnAlternateSource1.3.6.1.4.1.476.1.42.3.2.1.60The system has detected that the load is being supplied by the alternate source.
lgpConditionPhaseRotationError1.3.6.1.4.1.476.1.42.3.2.1.61This system has detected a phase rotation error condition.
lgpConditionSource1PhaseRotationError1.3.6.1.4.1.476.1.42.3.2.1.61.1The system has detected a phase rotation error on source 1.
lgpConditionSource2PhaseRotationError1.3.6.1.4.1.476.1.42.3.2.1.61.2The system has detected a phase rotation error on source 2.
lgpConditionBypassPhaseRotationError1.3.6.1.4.1.476.1.42.3.2.1.61.3The system has detected a phase rotation error on the bypass.
lgpConditionInputPhaseRotationError1.3.6.1.4.1.476.1.42.3.2.1.61.4The system has detected a phase rotation error on the input.
lgpConditionControlModuleFailure1.3.6.1.4.1.476.1.42.3.2.1.62This system has detected a control module failure condition.
lgpConditionControlModule1Failure1.3.6.1.4.1.476.1.42.3.2.1.62.1The system has detected a control module 1 failure.
lgpConditionHistoryLogFull1.3.6.1.4.1.476.1.42.3.2.1.63The system has detected the history log is full.
lgpConditionConfigurationModified1.3.6.1.4.1.476.1.42.3.2.1.64The system has detected the configuration has been modified.
lgpConditionPasswordModified1.3.6.1.4.1.476.1.42.3.2.1.65The system has detected the password has been modified.
lgpConditionTimeModified1.3.6.1.4.1.476.1.42.3.2.1.66The system has detected the time has been modified.
lgpConditionDateModified1.3.6.1.4.1.476.1.42.3.2.1.67The system has detected the date has been modified.
lgpConditionEventLogCleared1.3.6.1.4.1.476.1.42.3.2.1.68The system has detected the event log has been cleared.
lgpConditionHistoryLogCleared1.3.6.1.4.1.476.1.42.3.2.1.69The system has detected the history log has been cleared.
lgpConditionUtilityFailure1.3.6.1.4.1.476.1.42.3.2.1.70The system has detected a utility failure.
lgpConditionBatteryTestInProgress1.3.6.1.4.1.476.1.42.3.2.1.71The system is performing a battery test at this time.
lgpConditionLoadOnBattery1.3.6.1.4.1.476.1.42.3.2.1.72The system load is being supported by the battery.
lgpConditionReplaceBattery1.3.6.1.4.1.476.1.42.3.2.1.74The system has detected the batteries are due to be replaced.
lgpConditionUpsShutdownPending1.3.6.1.4.1.476.1.42.3.2.1.75The system is in a shutdown pending condition.
lgpConditionBatteryChargerFailed1.3.6.1.4.1.476.1.42.3.2.1.76The system has detected the battery charger has failed.
lgpConditionBypassVoltageUnqualified1.3.6.1.4.1.476.1.42.3.2.1.77The system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time.
lgpConditionCheckAirFilter1.3.6.1.4.1.476.1.42.3.2.1.78The system has detected it is time to check the air filter.
lgpConditionBrownOut1.3.6.1.4.1.476.1.42.3.2.1.79The system has detected a brown out condition.
lgpConditionMultipleTransferLockout1.3.6.1.4.1.476.1.42.3.2.1.80The system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time.
lgpConditionBypassPhaseLost1.3.6.1.4.1.476.1.42.3.2.1.81The system has detected one or more bypass phases are missing.
lgpConditionMaintenceBypassInhibited1.3.6.1.4.1.476.1.42.3.2.1.82The system is preventing a transfer of the load to maintenance bypass.
lgpConditionLoadLockedOnBypass1.3.6.1.4.1.476.1.42.3.2.1.83An error has been detected requiring the system to be put into a 'locked on bypass' state.
lgpConditionOutputToLoadShort1.3.6.1.4.1.476.1.42.3.2.1.84The system has detected an output to load short circuit condition.
lgpConditionEmergencyTransferToInverter1.3.6.1.4.1.476.1.42.3.2.1.85The system has detected an emergency transfer of the load to inverter.
lgpConditonEmergencyPowerOff1.3.6.1.4.1.476.1.42.3.2.1.86The system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system.
lgpConditionInverterBackFeed1.3.6.1.4.1.476.1.42.3.2.1.87The system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input.
lgpConditionDcGroundFault1.3.6.1.4.1.476.1.42.3.2.1.88The system has detected a DC ground fault.
lgpConditionDcGroundFaultPos1.3.6.1.4.1.476.1.42.3.2.1.88.1Ground fault current has been detected in the positive DC link to ground.
lgpConditionDcGroundFaultNeg1.3.6.1.4.1.476.1.42.3.2.1.88.2Ground fault current has been detected in the negative DC link to ground.
lgpConditionStaticTransferSwitchInhibited1.3.6.1.4.1.476.1.42.3.2.1.89The system is preventing the use of the static transfer switch.
lgpConditionBatteryLogFullWarning1.3.6.1.4.1.476.1.42.3.2.1.90The system has detected the battery log is approaching the maximum record limit.
lgpConditionInputCurrentUnbalanced1.3.6.1.4.1.476.1.42.3.2.1.91The system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
lgpConditionSelfTestFailed1.3.6.1.4.1.476.1.42.3.2.1.92The system has detected a self-test failure.
lgpConditionInverterOutOfSynchronization1.3.6.1.4.1.476.1.42.3.2.1.93The system has detected an Inverter out of sync condition.
lgpConditionModuleAlarm1.3.6.1.4.1.476.1.42.3.2.1.94This system has detected an alarm within the multi-module system.
lgpConditioniModuleUnit1Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.1The multi-module system has detected an alarm condition on unit 1.
lgpConditioniModuleUnit2Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.2The multi-module system has detected an alarm condition on unit 2.
lgpConditioniModuleUnit3Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.3The multi-module system has detected an alarm condition on unit 3.
lgpConditioniModuleUnit4Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.4The multi-module system has detected an alarm condition on unit 4.
lgpConditioniModuleUnit5Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.5The multi-module system has detected an alarm condition on unit 5.
lgpConditioniModuleUnit6Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.6The multi-module system has detected an alarm condition on unit 6.
lgpConditioniModuleUnit7Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.7The multi-module system has detected an alarm condition on unit 7.
lgpConditioniModuleUnit8Alarm1.3.6.1.4.1.476.1.42.3.2.1.94.8The multi-module system has detected an alarm condition on unit 8.
lgpConditionActiveModuleAlarm1.3.6.1.4.1.476.1.42.3.2.1.95The system has detected an active alarm in one, or more, of the sub-modules of the multi-module system.
lgpConditionControlFailure1.3.6.1.4.1.476.1.42.3.2.1.96This system has detected a control failure condition.
lgpConditionMainControlFailure1.3.6.1.4.1.476.1.42.3.2.1.96.1The system has detected a main control failure condition.
lgpConditionRedundantControlFailure1.3.6.1.4.1.476.1.42.3.2.1.96.2The system has detected a redundant control failure condition.
lgpConditionParallelSysControlFailure1.3.6.1.4.1.476.1.42.3.2.1.96.3The parallel system has detected a control failure condition with one of the controls.
lgpConditionMainControlCommFailure1.3.6.1.4.1.476.1.42.3.2.1.96.4One or more communications failures have occurred in the main control.
lgpConditionControlBoardFailure1.3.6.1.4.1.476.1.42.3.2.1.96.5The system has detected a control board failure.
lgpConditionHumidifierControlBdFailure1.3.6.1.4.1.476.1.42.3.2.1.96.5.1Humidifier control board is required to be connected, but no signal is detected.
lgpConditionControlWarning1.3.6.1.4.1.476.1.42.3.2.1.97This system has detected a control warning conditions.
lgpConditionMainControlWarning1.3.6.1.4.1.476.1.42.3.2.1.97.1The system has detected a main control warning condition.
lgpConditionRedundantControlWarning1.3.6.1.4.1.476.1.42.3.2.1.97.2The system has detected a redundant control warning condition.
lgpConditionUserInterfaceFailure1.3.6.1.4.1.476.1.42.3.2.1.98The system has detected a user interface control failure condition.
lgpConditionLostPowerRedundancy1.3.6.1.4.1.476.1.42.3.2.1.99The system has detected the number of redundant power modules has fallen below the minimum redundant power module setting.
lgpConditionPowerModuleFailure1.3.6.1.4.1.476.1.42.3.2.1.100The system has detected a power module failure condition in the system.
lgpConditionBatteryModuleFailure1.3.6.1.4.1.476.1.42.3.2.1.101The system has detected a battery module failure condition in the system.
lgpConditionOutputToLoadOff1.3.6.1.4.1.476.1.42.3.2.1.102The system has detected that there is no power being supplied to the load.
lgpConditionSystemOff1.3.6.1.4.1.476.1.42.3.2.1.103The system is off.
lgpConditionRectifierStartupFailure1.3.6.1.4.1.476.1.42.3.2.1.104The system has detected a rectifier under voltage start-up failure condition.
lgpConditionRectifierFault1.3.6.1.4.1.476.1.42.3.2.1.105The system has detected a rectifier fault condition.
lgpConditionInverterShutdownLowDc1.3.6.1.4.1.476.1.42.3.2.1.106The system has shutdown the inverter due to a DC bus under voltage.
lgpConditionInverterFault1.3.6.1.4.1.476.1.42.3.2.1.107The system has detected an inverter fault condition.
lgpConditionInverterDcOffsetOverrun1.3.6.1.4.1.476.1.42.3.2.1.108The system has detected an over run of the inverter DC offset voltage.
lgpConditionParallelSysLowBatteryWarning1.3.6.1.4.1.476.1.42.3.2.1.109The parallel system has detected a low battery warning condition.
lgpConditionParallelSysLoadShareFault1.3.6.1.4.1.476.1.42.3.2.1.110The parallel system has detected a load share fault condition.
lgpConditionBatteryFault1.3.6.1.4.1.476.1.42.3.2.1.111The system has detected a battery fault condition. The battery conductors are either reversed or disconnected.
lgpConditionBatteryConverterFailure1.3.6.1.4.1.476.1.42.3.2.1.112The system has detected a battery converter failure condition.
lgpConditionBatteryBalancerFault1.3.6.1.4.1.476.1.42.3.2.1.113The system has detected a battery balancer fault condition.
lgpConditionpsUpsOperationFault1.3.6.1.4.1.476.1.42.3.2.1.114The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
lgpConditionOutputToLoadOnJointMode1.3.6.1.4.1.476.1.42.3.2.1.115The system load is being supported by both the battery and rectifier.
lgpConditionInputNeutralLost1.3.6.1.4.1.476.1.42.3.2.1.116The system had detected the main input neutral is disconnected.
lgpConditionLowBatteryWarning1.3.6.1.4.1.476.1.42.3.2.1.117The battery's remaining charge is less than or equal to the configured low threshold.
lgpConditionInternalFault1.3.6.1.4.1.476.1.42.3.2.1.118The system has detected an internal fault.
lgpConditionBatteryTestFailed1.3.6.1.4.1.476.1.42.3.2.1.119The system has detected a battery self-test failure.
lgpConditionPowerModuleWarning1.3.6.1.4.1.476.1.42.3.2.1.120The system has detected an alarm condition on one, or more, power modules.
lgpConditionBatteryModuleWarning1.3.6.1.4.1.476.1.42.3.2.1.121The system has detected an alarm condition on one, or more, battery modules.
lgpConditionControlModuleWarning1.3.6.1.4.1.476.1.42.3.2.1.122The system has detected a control module warning.
lgpConditionUpsOperationFault1.3.6.1.4.1.476.1.42.3.2.1.123The system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
lgpConditionActiveAlarm1.3.6.1.4.1.476.1.42.3.2.1.124The system has detected an alarm condition.
lgpConditionRectifierCommunicationFailure1.3.6.1.4.1.476.1.42.3.2.1.125The system has detected an internal communication failure condition with the rectifier.
lgpConditionInverterCommunicationFailure1.3.6.1.4.1.476.1.42.3.2.1.126The system has detected an internal communication failure condition with the inverter.
lgpConditionParallelSysConnectionFault1.3.6.1.4.1.476.1.42.3.2.1.127The parallel system has detected a connection fault. One or more of the devices are not properly connected.
lgpConditionParallelSysCommunicationFailure1.3.6.1.4.1.476.1.42.3.2.1.128The parallel system has detected a communication failure.
lgpConditionLostBatteryRedundancy1.3.6.1.4.1.476.1.42.3.2.1.129The system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold.
lgpConditionCompPumpDownFailure1.3.6.1.4.1.476.1.42.3.2.1.130The system has detected that a compressor has failed to pump down.
lgpConditionComp1PumpDownFailure1.3.6.1.4.1.476.1.42.3.2.1.130.1The system has detected that compressor 1 has failed to pump down.
lgpConditionComp2PumpDownFailure1.3.6.1.4.1.476.1.42.3.2.1.130.2The system has detected that compressor 2 has failed to pump down.
lgpConditionChilledWaterLowWaterFlow1.3.6.1.4.1.476.1.42.3.2.1.131The system has detected a chilled water low water flow condition.
lgpConditionChilledWaterLowWaterFlowCircuit21.3.6.1.4.1.476.1.42.3.2.1.131.2The system has detected a chilled water low water flow condition for circuit 2.
lgpConditionAirFilterClogged1.3.6.1.4.1.476.1.42.3.2.1.132The system has detected a air filter clogged condition.
lgpConditionHumidifierFailure1.3.6.1.4.1.476.1.42.3.2.1.133The system has detected a humidifier failure condition.
lgpConditionRunHoursExceeded1.3.6.1.4.1.476.1.42.3.2.1.134The system has detected a pre-determined run hours threshold has been exceeded.
lgpConditionUnitRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.1The system has detected the system run hours has exceeded the pre-determined threshold.
lgpConditionComp1RunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.2The system has detected the compressor 1 run hours has exceeded the pre-determined threshold.
lgpConditionComp2RunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.3The system has detected the compressor 2 run hours has exceeded the pre-determined threshold.
lgpConditionFreeCoolRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.4The system has detected the free cooling run hours has exceeded the pre-determined threshold.
lgpConditionElectricalHeater1RunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.5The system has detected the electrical heater's run hours have exceeded the pre-determined threshold.
lgpConditionElectricalHeater2RunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.6The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
lgpConditionElectricalHeater3RunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.7The system has detected the electrical heater's run hours have exceeded the pre-determined limit.
lgpConditionHotWaterRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.8The system has detected the hot water run hours have exceeded the pre-determined threshold.
lgpConditionHotGasRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.9The system has detected the hot gas run hours have exceeded the pre-determined threshold.
lgpConditionHumidifierRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.10The system has detected the humidifier run hours have exceeded the pre-determined threshold.
lgpConditionDehumidiferRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.11The system has detected the dehumidifier run hours have exceeded the pre-determined threshold.
lgpConditionFanRunHrsExceeded1.3.6.1.4.1.476.1.42.3.2.1.134.12The system has detected the unit blower fan run hours have exceeded the pre-determined threshold.
lgpConditionCommWarning1.3.6.1.4.1.476.1.42.3.2.1.135The system has detected a loss of communications with another module.
lgpConditionCommWarningUnit11.3.6.1.4.1.476.1.42.3.2.1.135.1The system has detected a loss of communications with unit 1.
lgpConditionCommWarningUnit21.3.6.1.4.1.476.1.42.3.2.1.135.2The system has detected a loss of communications with unit 2.
lgpConditionCommWarningUnit31.3.6.1.4.1.476.1.42.3.2.1.135.3The system has detected a loss of communications with unit 3.
lgpConditionCommWarningUnit41.3.6.1.4.1.476.1.42.3.2.1.135.4The system has detected a loss of communications with unit 4.
lgpConditionCommWarningUnit51.3.6.1.4.1.476.1.42.3.2.1.135.5The system has detected a loss of communications with unit 5.
lgpConditionCommWarningUnit61.3.6.1.4.1.476.1.42.3.2.1.135.6The system has detected a loss of communications with unit 6.
lgpConditionCommWarningUnit71.3.6.1.4.1.476.1.42.3.2.1.135.7The system has detected a loss of communications with unit 7.
lgpConditionCommWarningUnit81.3.6.1.4.1.476.1.42.3.2.1.135.8The system has detected a loss of communications with unit 8.
lgpConditionCommWarningUnit91.3.6.1.4.1.476.1.42.3.2.1.135.9The system has detected a loss of communications with unit 9.
lgpConditionCommWarningUnit101.3.6.1.4.1.476.1.42.3.2.1.135.10The system has detected a loss of communications with unit 10.
lgpConditionCommWarningUnit111.3.6.1.4.1.476.1.42.3.2.1.135.11The system has detected a loss of communications with unit 11.
lgpConditionCommWarningUnit121.3.6.1.4.1.476.1.42.3.2.1.135.12The system has detected a loss of communications with unit 12.
lgpConditionCommWarningUnit131.3.6.1.4.1.476.1.42.3.2.1.135.13The system has detected a loss of communications with unit 13.
lgpConditionCommWarningUnit141.3.6.1.4.1.476.1.42.3.2.1.135.14The system has detected a loss of communications with unit 14.
lgpConditionCommWarningUnit151.3.6.1.4.1.476.1.42.3.2.1.135.15The system has detected a loss of communications with unit 15.
lgpConditionCommWarningUnit161.3.6.1.4.1.476.1.42.3.2.1.135.16The system has detected a loss of communications with unit 16.
lgpConditionUnitOn1.3.6.1.4.1.476.1.42.3.2.1.136The unit is on.
lgpConditionUnitOff1.3.6.1.4.1.476.1.42.3.2.1.137The unit is off.
lgpConditionSleepModeOff1.3.6.1.4.1.476.1.42.3.2.1.138The system sleep mode operation has been turned off.
lgpConditionPowerOn1.3.6.1.4.1.476.1.42.3.2.1.139The system power is on.
lgpConditionSystemOnStanby1.3.6.1.4.1.476.1.42.3.2.1.140The system is on standby.
lgpConditionPowerOff1.3.6.1.4.1.476.1.42.3.2.1.141The system power is off.
lgpConditionHighTemperatureGroup1.3.6.1.4.1.476.1.42.3.2.1.142The system has detected a high temperature condition. This group contains various high temperature conditions.
lgpConditionHighTemperatureSensor11.3.6.1.4.1.476.1.42.3.2.1.142.1The temperature has exceeded the high temperature threshold for sensor 1.
lgpConditionHighTemperatureDigitalScroll11.3.6.1.4.1.476.1.42.3.2.1.142.2The system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold.
lgpConditionHighTemperatureDigitalScroll21.3.6.1.4.1.476.1.42.3.2.1.142.3The system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold.
lgpConditionHighTemperatureUser11.3.6.1.4.1.476.1.42.3.2.1.142.4The temperature has exceeded the high temperature threshold for user configured temperature sensor 1.
lgpConditionHighTemperatureInternal1.3.6.1.4.1.476.1.42.3.2.1.142.5The system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold.
lgpConditionHighTemperatureExternalAirSensorA1.3.6.1.4.1.476.1.42.3.2.1.142.6The temperature has exceeded the high temperature threshold for external air sensor A.
lgpConditionHighTemperatureExternalAirSensorB1.3.6.1.4.1.476.1.42.3.2.1.142.7The temperature has exceeded the high temperature threshold for external air sensor B.
lgpConditionHighTemperatureRefrigerantSupply1.3.6.1.4.1.476.1.42.3.2.1.142.8The temperature has exceeded the high temperature threshold for the refrigerant supply.
lgpConditionHighTemperatureFluidSupply1.3.6.1.4.1.476.1.42.3.2.1.142.9The temperature has exceeded the high temperature threshold for the fluid supply.
lgpConditionHighTemperatureSupplyAir1.3.6.1.4.1.476.1.42.3.2.1.142.10The temperature has exceeded the high temperature threshold for the supply air.
lgpConditionHighTemperatureReturnAir1.3.6.1.4.1.476.1.42.3.2.1.142.11The temperature has exceeded the high temperature threshold for the return air.
lgpConditionLowTemperatureGroup1.3.6.1.4.1.476.1.42.3.2.1.143The system has detected a low temperature condition. This group contains various low temperature conditions.
lgpConditionLowTemperatureSensor11.3.6.1.4.1.476.1.42.3.2.1.143.1The temperature is below the low temperature threshold for sensor 1.
lgpConditionLowTemperatureInternal1.3.6.1.4.1.476.1.42.3.2.1.143.2The system has detected a low internal temperature condition. The temperature is below a specified temperature threshold.
lgpConditionLowTemperatureExternalAirSensorA1.3.6.1.4.1.476.1.42.3.2.1.143.3The temperature is below the low temperature threshold for external air sensor A.
lgpConditionLowTemperatureExternalAirSensorB1.3.6.1.4.1.476.1.42.3.2.1.143.4The temperature is below the low temperature threshold for external air sensor B.
lgpConditionLowTemperatureRefrigerantSupply1.3.6.1.4.1.476.1.42.3.2.1.143.5The temperature is below the low temperature threshold for the refrigerant supply.
lgpConditionLowTemperatureFluidSupply1.3.6.1.4.1.476.1.42.3.2.1.143.6The temperature is below the low temperature threshold for the fluid supply.
lgpConditionLowTemperatureSupplyAir1.3.6.1.4.1.476.1.42.3.2.1.143.7The temperature is below the low temperature threshold for the supply air.
lgpConditionHighHumidityGroup1.3.6.1.4.1.476.1.42.3.2.1.144The system has detected a high humidity condition. This group contains various high humidity conditions.
lgpConditionHighHumiditySensor11.3.6.1.4.1.476.1.42.3.2.1.144.1The humidity has exceeded the high humidity threshold for sensor 1.
lgpConditionHighHumidityReturnAir1.3.6.1.4.1.476.1.42.3.2.1.144.2The humidity has exceeded the high humidity threshold for the return air.
lgpConditionLowHumidityGroup1.3.6.1.4.1.476.1.42.3.2.1.145The system has detected a low humidity condition. This group contains various high humidity conditions.
lgpConditionLowHumiditySensor11.3.6.1.4.1.476.1.42.3.2.1.145.1The humidity is below the low humidity threshold for sensor 1.
lgpConditionLowHumidityReturnAir1.3.6.1.4.1.476.1.42.3.2.1.145.2The humidity is below the low humidity threshold for the return air.
lgpConditionPeerNetworkNoMaster1.3.6.1.4.1.476.1.42.3.2.1.146The system is unable to communicate with the master on the peer to peer network.
lgpConditionNoOnOffPermissions1.3.6.1.4.1.476.1.42.3.2.1.147The system lacks the permissions to execute the on/off operation.
lgpConditionPeerNetworkFailure1.3.6.1.4.1.476.1.42.3.2.1.148The system has detected a communication failure on the peer to peer network.
lgpConditionUnitDisabled1.3.6.1.4.1.476.1.42.3.2.1.149The unit is disabled.
lgpConditionUnitShutdown1.3.6.1.4.1.476.1.42.3.2.1.150The system has shutdown.
lgpConditionPeerNetworkDiscovered1.3.6.1.4.1.476.1.42.3.2.1.151The system has established communications on the peer to peer network.
lgpConditionLossOfWaterFlow1.3.6.1.4.1.476.1.42.3.2.1.152The system has detected a loss of water flow condition.
lgpConditionCondensatePumpHighWater1.3.6.1.4.1.476.1.42.3.2.1.153The system has detected high water in the condensate pump.
lgpConditionGeneralAlarm1.3.6.1.4.1.476.1.42.3.2.1.154The system has detected a general alarm condition.
lgpConditionProductSpecific1.3.6.1.4.1.476.1.42.3.2.1.155The system has detected a product specific condition. This condition is not currently available via the agent card.
lgpConditionReheatLockout1.3.6.1.4.1.476.1.42.3.2.1.156The system has locked out the electrical reheat operation for a specified amount of time.
lgpConditionHumidifierLockout1.3.6.1.4.1.476.1.42.3.2.1.157The system has locked out the humidifier operation for a specified amount of time.
lgpConditionCompressorsLockout1.3.6.1.4.1.476.1.42.3.2.1.158The system has locked out compressor operation for a specified amount of time.
lgpConditionCallService1.3.6.1.4.1.476.1.42.3.2.1.159The system has detected a condition that requires a service representative be contacted.
lgpConditionLowMemoryGroup1.3.6.1.4.1.476.1.42.3.2.1.160This group contains various low memory conditions.
lgpConditionLowMemory11.3.6.1.4.1.476.1.42.3.2.1.160.1The system has detected a low memory condition. The control board is low in memory resources.
lgpConditionMemoryFailureGroup1.3.6.1.4.1.476.1.42.3.2.1.161This group contains various memory device failure conditions.
lgpConditionMemory1Failure1.3.6.1.4.1.476.1.42.3.2.1.161.1The system has detected a memory 1 module failure.
lgpConditionMemory2Failure1.3.6.1.4.1.476.1.42.3.2.1.161.2The system has detected a memory 2 module failure.
lgpConditionUnitCodeErrorGroup1.3.6.1.4.1.476.1.42.3.2.1.162This group contains various memory device failure conditions.
lgpConditionUnitCodeNotConfigured1.3.6.1.4.1.476.1.42.3.2.1.162.1The system has detected the unit code is not configured. The unit code must be configured before system start-up.
lgpConditionUnitCode01OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.2The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode02OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.3The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode03OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.4The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode04OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.5The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode05OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.6The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode06OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.7The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode07OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.8The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode08OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.9The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode09OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.10The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode10OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.11The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode11OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.12The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode12OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.13The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode13OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.14The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode14OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.15The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode15OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.16The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode16OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.17The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode17OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.18The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionUnitCode18OutOfRange1.3.6.1.4.1.476.1.42.3.2.1.162.19The system has detected a unit code error. This digit of the unit code value is out of range.
lgpConditionHighExternalDewPoint1.3.6.1.4.1.476.1.42.3.2.1.163The system has detected a high external dew point condition. The room dew point has exceeded the specified threshold.
lgpConditionHcbDisconnected1.3.6.1.4.1.476.1.42.3.2.1.164The system has detected the humidifier control board is disconnected or not installed.
lgpConditionBmsResetTimerExpired1.3.6.1.4.1.476.1.42.3.2.1.165The BMS fan speed control reset counter has timed out.
lgpConditionAgentFirmwareCorrupt1.3.6.1.4.1.476.1.42.3.2.1.166The firmware update to the agent card has failed and the firmware is now corrupt.
lgpConditionSystemAccessGroup1.3.6.1.4.1.476.1.42.3.2.1.175This group contains various system access conditions. An examples is an open access panel.
lgpConditionFrontAccessOpen1.3.6.1.4.1.476.1.42.3.2.1.175.1The system has detected the front access panel/door is open.
lgpConditionRearAccessOpen1.3.6.1.4.1.476.1.42.3.2.1.175.2The system has detected the rear access panel/door is open.
lgpConditionsDamperFailure1.3.6.1.4.1.476.1.42.3.2.1.176This group contains various damper failure conditions.
lgpConditionEmergencyDamperFailure1.3.6.1.4.1.476.1.42.3.2.1.176.1The system has detected an emergency damper failure. The damper is in the wrong position.
lgpConditionRemoteShutdown1.3.6.1.4.1.476.1.42.3.2.1.177A remote shutdown occurred.
lgpConditionFireAlarm1.3.6.1.4.1.476.1.42.3.2.1.178Fire Alarm.
lgpConditionHeatersOverheated1.3.6.1.4.1.476.1.42.3.2.1.179Heaters Overheated.
lgpConditionCondenserFailureGroup1.3.6.1.4.1.476.1.42.3.2.1.180This group contains condenser failure conditions.
lgpConditionCondenser1Failure1.3.6.1.4.1.476.1.42.3.2.1.180.1Condenser 1 Failure.
lgpConditionCondenser2Failure1.3.6.1.4.1.476.1.42.3.2.1.180.2Condenser 2 Failure.
lgpConditionCondenserTVSSFailure1.3.6.1.4.1.476.1.42.3.2.1.180.3The condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
lgpConditionHumidifierCyclinderWorn1.3.6.1.4.1.476.1.42.3.2.1.181The system has detected the humidifier cylinder is worn.
lgpConditionUnderCurrent1.3.6.1.4.1.476.1.42.3.2.1.182The system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. The threshold and time that triggered this condition is system dependent.
lgpConditionHumidifierUnderCurrent1.3.6.1.4.1.476.1.42.3.2.1.182.1The system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amount of time.
lgpConditionInputUnderCurrent1.3.6.1.4.1.476.1.42.3.2.1.182.2There is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amount of time.
lgpConditionHeatRejectorGroup1.3.6.1.4.1.476.1.42.3.2.1.183This group contains failure conditions for the heat rejection unit.
lgpConditionHeatRejectorFanFailure1.3.6.1.4.1.476.1.42.3.2.1.183.1The heat rejecter fan has failed.
lgpConditionHeatRejectorVoltageSuppressionFailure1.3.6.1.4.1.476.1.42.3.2.1.183.2The heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations.
lgpConditionFreeCoolLockout1.3.6.1.4.1.476.1.42.3.2.1.184The free cooling capability has been disabled.
lgpConditionWaterLeakSensorFailure1.3.6.1.4.1.476.1.42.3.2.1.185The sensor used to detect water leaks is not connected or has failed.
lgpConditionNoLoadDetectedWarning1.3.6.1.4.1.476.1.42.3.2.1.186There is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been left on external bypass. This warning is triggered after a delay. The delay is specified by the object 'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output current falls below a certain threshold specified by the object 'lgpPwrNoLoadWarningLimit'
lgpConditionFirmwareGroup1.3.6.1.4.1.476.1.42.3.2.1.187Grouping level for firmware related conditions.
lgpConditionFirmwareUpdateRequired1.3.6.1.4.1.476.1.42.3.2.1.187.3The firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain corrupted firmware or the firmware on one or more components are incompatible with one another. When this condition is active the system may not be able to function to its full capacity or may not be able to function at all.
lgpConditionTestGroup1.3.6.1.4.1.476.1.42.3.2.1.188Objects in this group of conditions are related to testing or test events. This object is never active.
lgpConditionTest011.3.6.1.4.1.476.1.42.3.2.1.188.5This is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of this event upon user request so that user management stations can execute end-to-end event handling tests.
lgpConditionReceptacleBranchGroup1.3.6.1.4.1.476.1.42.3.2.1.190Grouping level for receptacle branch conditions.
lgpConditionRcpBranchFailure1.3.6.1.4.1.476.1.42.3.2.1.190.5The receptacle branch module or control system has failed. Service is required.
lgpConditionRcpBranchBreakerOpen1.3.6.1.4.1.476.1.42.3.2.1.190.10The receptacle branch breaker is open.
lgpConditionInputUnqualified1.3.6.1.4.1.476.1.42.3.2.1.192The input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out of range, or other similar issues.
lgpConditionBypassUnavailable1.3.6.1.4.1.476.1.42.3.2.1.193This summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or other similar causes.
lgpConditionAutoTransferFailed1.3.6.1.4.1.476.1.42.3.2.1.194The system is failing to automatically transfer the load to the alternate source.
lgpConditionSBSUnavailable1.3.6.1.4.1.476.1.42.3.2.1.195A Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload Exceeded, Bypass Power Supply Fail, Static Bypass Switch Fuse Failure, or other similar causes.
lgpConditionSBSOverload1.3.6.1.4.1.476.1.42.3.2.1.196On at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded.
lgpConditionExcessPulseParallel1.3.6.1.4.1.476.1.42.3.2.1.197The system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the static bypass switch (SBS) in parallel with the inverter.
lgpConditionRemoteBypassSwitchOffExt1.3.6.1.4.1.476.1.42.3.2.1.198The static bypass switch is off due to the state of an external signal.
lgpConditionManTransferInhibited1.3.6.1.4.1.476.1.42.3.2.1.199Manual transfer from inverter to bypass is inhibited. Bypass is not qualified.
lgpConditionManReTransferInhibited1.3.6.1.4.1.476.1.42.3.2.1.200Manual retransfer from bypass to inverter is inhibited.
lgpConditionBatteryChargeError1.3.6.1.4.1.476.1.42.3.2.1.201The battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc.
lgpConditionBatteryAutoTestInhibited1.3.6.1.4.1.476.1.42.3.2.1.202Automatic (scheduled) battery tests are inhibited.
lgpConditionBatteryChargeReducedExt1.3.6.1.4.1.476.1.42.3.2.1.203A reduced battery charging algorithm is being used due to an external signal.
lgpConditionBatteryCapacityLow1.3.6.1.4.1.476.1.42.3.2.1.204The battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilities, etc.
lgpConditionBatteryTempImbalance1.3.6.1.4.1.476.1.42.3.2.1.205The temperature difference between two batteries in the system exceeds the predefined threshold.
lgpConditionBatteryEqualize1.3.6.1.4.1.476.1.42.3.2.1.206The rectifier output voltage has been increased to equalize the battery voltage level.
lgpConditionBatteryChargeInhibitedExt1.3.6.1.4.1.476.1.42.3.2.1.207Battery charging is inhibited due to an external inhibit signal.
lgpConditionServiceExtBatteryMonitorGroup1.3.6.1.4.1.476.1.42.3.2.1.208This group contains battery monitor service conditions.
lgpConditionServiceExtBatteryMonitor11.3.6.1.4.1.476.1.42.3.2.1.208.1External battery monitor 1 indicates battery maintenance is required.
lgpConditionServiceExtBatteryMonitor21.3.6.1.4.1.476.1.42.3.2.1.208.2External battery monitor 2 indicates battery maintenance is required.
lgpConditionBatteryGroundFault1.3.6.1.4.1.476.1.42.3.2.1.209Battery system ground fault amperage exceeds the threshold.
lgpConditionBatteryLowShutdown1.3.6.1.4.1.476.1.42.3.2.1.210With the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit.
lgpConditionEmergencyPowerOffLocal1.3.6.1.4.1.476.1.42.3.2.1.211The system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system.
lgpConditionOutputLowPFLagging1.3.6.1.4.1.476.1.42.3.2.1.212The system has detected a lagging output power factor below the threshold, resulting in reduced load capacity.
lgpConditionOutputLowPFLeading1.3.6.1.4.1.476.1.42.3.2.1.213The system has detected a leading output power factor below the threshold, resulting in reduced load capacity.
lgpConditionOutputToLoadFault1.3.6.1.4.1.476.1.42.3.2.1.214The system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency.
lgpConditionInvRestartInhibitedExt1.3.6.1.4.1.476.1.42.3.2.1.215Restart of the inverter is inhibited by an external signal.
lgpConditionInverterShutdownOverload1.3.6.1.4.1.476.1.42.3.2.1.216The system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least one phase of the inverter power dissipation limit has been exceeded.
lgpConditionInverterOffExt1.3.6.1.4.1.476.1.42.3.2.1.217The inverter is off due to the state of an external signal.
lgpConditionInputContactGroup1.3.6.1.4.1.476.1.42.3.2.1.218The system has detected an active input contact.
lgpConditionInputContact011.3.6.1.4.1.476.1.42.3.2.1.218.1The system has detected that input contact 1 is active.
lgpConditionInputContact021.3.6.1.4.1.476.1.42.3.2.1.218.2The system has detected that input contact 2 is active.
lgpConditionInputContact031.3.6.1.4.1.476.1.42.3.2.1.218.3The system has detected that input contact 3 is active.
lgpConditionInputContact041.3.6.1.4.1.476.1.42.3.2.1.218.4The system has detected that input contact 4 is active.
lgpConditionInputContact051.3.6.1.4.1.476.1.42.3.2.1.218.5The system has detected that input contact 5 is active.
lgpConditionInputContact061.3.6.1.4.1.476.1.42.3.2.1.218.6The system has detected that input contact 6 is active.
lgpConditionInputContact071.3.6.1.4.1.476.1.42.3.2.1.218.7The system has detected that input contact 7 is active.
lgpConditionInputContact081.3.6.1.4.1.476.1.42.3.2.1.218.8The system has detected that input contact 8 is active.
lgpConditionInputContact091.3.6.1.4.1.476.1.42.3.2.1.218.9The system has detected that input contact 9 is active.
lgpConditionInputContact101.3.6.1.4.1.476.1.42.3.2.1.218.10The system has detected that input contact 10 is active.
lgpConditionInputContact111.3.6.1.4.1.476.1.42.3.2.1.218.11The system has detected that input contact 11 is active.
lgpConditionInputContact121.3.6.1.4.1.476.1.42.3.2.1.218.12The system has detected that input contact 12 is active.
lgpConditionInputContact131.3.6.1.4.1.476.1.42.3.2.1.218.13The system has detected that input contact 13 is active.
lgpConditionInputContact141.3.6.1.4.1.476.1.42.3.2.1.218.14The system has detected that input contact 14 is active.
lgpConditionInputContact151.3.6.1.4.1.476.1.42.3.2.1.218.15The system has detected that input contact 15 is active.
lgpConditionInputContact161.3.6.1.4.1.476.1.42.3.2.1.218.16The system has detected that input contact 16 is active.
lgpConditionRectifierOperInhibited1.3.6.1.4.1.476.1.42.3.2.1.219The operation of the rectifier is inhibited by an external signal.
lgpConditionBypassBackFeedBrkrOpen1.3.6.1.4.1.476.1.42.3.2.1.220The bypass backfeed breaker is in the open position.
lgpConditionAutoRestartInProgress1.3.6.1.4.1.476.1.42.3.2.1.221Auto restart is in progress. Becomes inactive when auto restart completes or fails.
lgpConditionAutoRestartInhibitedExt1.3.6.1.4.1.476.1.42.3.2.1.222Auto restart is inhibited due to an external signal.
lgpConditionAutoRestartFailed1.3.6.1.4.1.476.1.42.3.2.1.223Auto restart has failed.
lgpConditionInputOnGenerator1.3.6.1.4.1.476.1.42.3.2.1.224A generator is supplying the power to the system.
lgpConditionInputFilterCycleLock1.3.6.1.4.1.476.1.42.3.2.1.225The input filter disconnect has opened too many times within a given period of time.
lgpConditionServiceCodeActive1.3.6.1.4.1.476.1.42.3.2.1.226The system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state.
lgpConditionLoadBusSyncActive1.3.6.1.4.1.476.1.42.3.2.1.227Load Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS.
lgpConditionLoadBusSyncInhibited1.3.6.1.4.1.476.1.42.3.2.1.228The system has detected that conditions to perform Load Bus Sync Operation are not satisfied.
lgpConditionControlsResetRequired1.3.6.1.4.1.476.1.42.3.2.1.229A controls reset is required because one or more critical settings have changed.
lgpConditionEquipTempSensorFailed1.3.6.1.4.1.476.1.42.3.2.1.230A temperature sensor is reporting a value outside the bounds of a properly operating sensor.
lgpConditionInputCurrentImbalance1.3.6.1.4.1.476.1.42.3.2.1.231The current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or input filter.
lgpConditionPumpGroup1.3.6.1.4.1.476.1.42.3.2.1.232The system has detected an alarm with one of the pumps.
lgpConditionPumpFlowLoss1.3.6.1.4.1.476.1.42.3.2.1.232.1The system has detected a loss of flow with one or more pumps.
lgpConditionPump1FlowLoss1.3.6.1.4.1.476.1.42.3.2.1.232.1.1The system has detected a loss of flow with pump 1.
lgpConditionPump2FlowLoss1.3.6.1.4.1.476.1.42.3.2.1.232.1.2The system has detected a loss of flow with pump 2.
lgpConditionPumpShortCycle1.3.6.1.4.1.476.1.42.3.2.1.232.2The system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period.
lgpConditionPumpInverterShortCycle1.3.6.1.4.1.476.1.42.3.2.1.232.3The system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
lgpConditionPump1InverterShortCycle1.3.6.1.4.1.476.1.42.3.2.1.232.3.1The system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
lgpConditionPump2InverterShortCycle1.3.6.1.4.1.476.1.42.3.2.1.232.3.2The system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A short cycle is defined as powering on and off a number of times over a set time period.
lgpConditionValveGroup1.3.6.1.4.1.476.1.42.3.2.1.233The system has detected an alarm with one of the valves.
lgpConditionChilledWaterValvePosition1.3.6.1.4.1.476.1.42.3.2.1.233.1The system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value.
lgpConditionCondensationDetected1.3.6.1.4.1.476.1.42.3.2.1.234The system has detected condensation.
lgpConditionMaintenanceGroup1.3.6.1.4.1.476.1.42.3.2.1.235The system has detected a maintenance condition. This group contains various maintenance conditions.
lgpConditionMaintenanceDue1.3.6.1.4.1.476.1.42.3.2.1.235.1System is due for maintenance.
lgpConditionMaintenanceComplete1.3.6.1.4.1.476.1.42.3.2.1.235.2The system maintenance has been completed.
lgpConditionExternalEventSignalGroup1.3.6.1.4.1.476.1.42.3.2.1.236This group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive.
lgpConditionExternalFireDetect1.3.6.1.4.1.476.1.42.3.2.1.236.1Fire detected, as indicated by an external input signal.
lgpConditionExternalFlowLoss1.3.6.1.4.1.476.1.42.3.2.1.236.2Loss of flow is detected, as indicated by an external input signal.
lgpConditionExternalReheatLockout1.3.6.1.4.1.476.1.42.3.2.1.236.3The reheater is shut down and disabled by an external input signal.
lgpConditionExternalOverTemp1.3.6.1.4.1.476.1.42.3.2.1.236.4A temperature has exceeded its threshold, as indicated by an external input signal.
lgpConditionExternalCompLockout1.3.6.1.4.1.476.1.42.3.2.1.236.5The compressor is shut down and disabled by an external input signal.
lgpConditionExternalHumidifierLockout1.3.6.1.4.1.476.1.42.3.2.1.236.6The humidifier is shut down and disabled by an external input signal.
lgpConditionComponentShutdownGroup1.3.6.1.4.1.476.1.42.3.2.1.237This group contains conditions signaling shutdown of various system components.
lgpConditionComponentShutdownPartial1.3.6.1.4.1.476.1.42.3.2.1.237.1An event has occurred requiring some system components to be shutdown and disabled.
lgpConditionComponentShutdownHighPower1.3.6.1.4.1.476.1.42.3.2.1.237.2Supply to high power components has been shutdown.
lgpConditionCondenserProblemGroup1.3.6.1.4.1.476.1.42.3.2.1.238This group contains condenser conditions.
lgpConditionCondenser1Problem1.3.6.1.4.1.476.1.42.3.2.1.238.1Condenser 1 is not operating within its normal parameters.
lgpConditionHumidityOutOfPropBand1.3.6.1.4.1.476.1.42.3.2.1.239The system has detected a humidity reading that remained outside of the proportional control band for an extended period of time.
lgpConditionEnvRemoteSensorGroup1.3.6.1.4.1.476.1.42.3.2.1.240This group contains remote sensors.
lgpConditionEnvRemoteSensor1Issue1.3.6.1.4.1.476.1.42.3.2.1.240.1Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor2Issue1.3.6.1.4.1.476.1.42.3.2.1.240.2Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor3Issue1.3.6.1.4.1.476.1.42.3.2.1.240.3Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor4Issue1.3.6.1.4.1.476.1.42.3.2.1.240.4Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor5Issue1.3.6.1.4.1.476.1.42.3.2.1.240.5Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor6Issue1.3.6.1.4.1.476.1.42.3.2.1.240.6Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor7Issue1.3.6.1.4.1.476.1.42.3.2.1.240.7Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor8Issue1.3.6.1.4.1.476.1.42.3.2.1.240.8Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor9Issue1.3.6.1.4.1.476.1.42.3.2.1.240.9Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionEnvRemoteSensor10Issue1.3.6.1.4.1.476.1.42.3.2.1.240.10Remote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
lgpConditionNeutralSnubberBoardCommFailure1.3.6.1.4.1.476.1.42.3.2.1.241The Neutral Snubber board has stopped communicating.
lgpConditionRedundantChargerFailure1.3.6.1.4.1.476.1.42.3.2.1.242The redundant charger has failed.
lgpConditionBoardInputContactorPowerFailure1.3.6.1.4.1.476.1.42.3.2.1.243Board input contactor power failure.
lgpConditionBoard1InputContactorPowerFailure1.3.6.1.4.1.476.1.42.3.2.1.243.1Board1 input contactor power failure.
lgpConditionBoard2InputContactorPowerFailure1.3.6.1.4.1.476.1.42.3.2.1.243.2Board2 input contactor power failure.
lgpConditionTooManySensors1.3.6.1.4.1.476.1.42.3.2.1.5423The number of sensors installed on the device has exceeded the pre-determined limit.
lgpConditionDoorSwitchOpen1.3.6.1.4.1.476.1.42.3.2.1.5471An open door has been detected.
lgpConditionContactClosureOpen1.3.6.1.4.1.476.1.42.3.2.1.5479An open circuit has been detected.
lgpConditionContactClosureClosed1.3.6.1.4.1.476.1.42.3.2.1.5480A closed circuit has been detected.
lgpConditionSensorsNotDisplayed1.3.6.1.4.1.476.1.42.3.2.1.6119The number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionTooManySensors in that the system may currently have less than the maximum of installed sensors present but one or more of those sensors can not be displayed because the display order table (lgpPduAuxMeasOrderTable) contains entries for sensors that are not currently installed. This condition effectively prevents one or more installed sensors from being presented in the lgpPduAuxMeasTable. It is possible for both this condition and the lgpConditionTooManySensors condition to be active at the same time.
G32 lgpConditionsPresent1.3.6.1.4.1.476.1.42.3.2.2Gauge32read-onlyThe present number of conditions (rows) in the lgpConditionsTable.
lgpConditionsTable1.3.6.1.4.1.476.1.42.3.2.3not-accessibleA list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of rows in the table is given by (lgpConditionsPresent). The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row subject to the following rules: Rows are removed from the table based on the following rules: 1. If a condition does not require acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState'). 2. If a condition requires acknowledgement (see 'lgpConditionAckReq') the condition is removed as soon as the issue clears (see 'lgpConditionCurrentState') AND the condition is acknowledged (see 'lgpConditionAcknowledged'). 3. If the columns 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are not present for the condition then the condition will be removed as soon as the issue causing the condition clears. The agent creates the first row with lgpConditionId equal to 1, and increments the value of 'lgpConditionId' each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of lgpConditionId would otherwise be exceeded. The number of rows in the table at any given time is reflected by the value of 'lgpConditionsPresent'.
lgpConditionEntry1.3.6.1.4.1.476.1.42.3.2.3.1not-accessibleThis entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns of the table.
U32 lgpConditionId1.3.6.1.4.1.476.1.42.3.2.3.1.1Unsigned32read-onlyA unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table 'lgpConditionsTable'.
OID lgpConditionDescr1.3.6.1.4.1.476.1.42.3.2.3.1.2OBJECT IDENTIFIERread-onlyA reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.
TIK lgpConditionTime1.3.6.1.4.1.476.1.42.3.2.3.1.3TimeTicksread-onlyThe value of sysUpTime when the condition occurred (became active).
OID lgpConditionTableRef1.3.6.1.4.1.476.1.42.3.2.3.1.5OBJECT IDENTIFIERread-onlyThis object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID of a table that the object that the condition applies to is defined. The table row corresponding to this object will also contain a varbind 'lgpConditionTableRowRef' that will specify which instance (row) in the referenced table the object is defined in. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType alarm lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required In the above example the breaker opened for a Receptacle branch. The specific receptacle branch is specified by the additional varbind (lgpEventParmTableRowRef). In this case the notification is for the 4th receptacle branch on the 1st PDU in the cluster.
OID lgpConditionTableRowRef1.3.6.1.4.1.476.1.42.3.2.3.1.6OBJECT IDENTIFIERread-onlyThis is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cell exists represents the object that this condition applies to. Example: TABLE ROW: lgpConditionId 5 lgpConditionDescr lgpConditionRcpBranchBreakerOpen lgpConditionTime 393884848 lgpConditionTableRef lgpPduRbTable lgpConditionTableRowRef lgpPduRbEntryId.1.4 lgpConditionType lgpConditionCurrentState active lgpConditionSeverity major lgpConditionAcknowledged acknowledged lgpConditionAckReq required The table containing the definition of the receptacle branch (lgpPduRbTable) is given by the varbind (lgpConditionTableRef) The specific receptacle branch (instance) is specified by the varbind (lgpConditionTableRowRef). In this case the condition is for the 4th receptacle branch on the 1st PDU in the PDU cluster. If one wanted to retrieve the serial number for this receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.
INT lgpConditionType1.3.6.1.4.1.476.1.42.3.2.3.1.10INTEGERread-onlyThe type of condition in this row in the table.
INT lgpConditionCurrentState1.3.6.1.4.1.476.1.42.3.2.3.1.12INTEGERread-onlyIndication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no longer exists (i.e. the situation causing the condition has cleared or been resolved). The behavior of some devices is to remove the condition from this table when the condition clears. The behavior of other devices is to leave the condition entry in the table until the condition is acknowledged ( see lgpConditionAcknowledged and lgpConditionAckReq).
INT lgpConditionSeverity1.3.6.1.4.1.476.1.42.3.2.3.1.14INTEGERread-onlyThis represents the relative severity of the condition.
INT lgpConditionAcknowledged1.3.6.1.4.1.476.1.42.3.2.3.1.18INTEGERread-writeThis indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowledged' then the condition has been acknowledged. Writing a value of 'acknowledged' to this object acknowledges the condition and the value will be changed to 'acknowledged'. If the current state of the condition is 'active' (see lgpConditionCurrentState) the condition will, for all devices remain in the table regardless of the state of the 'lgpConditionAcknowledged' object. If the 'lgpConditionAckReq' is 'notRequired' or this column does not exist for the row then this object has no affect on the duration the condition stays in the lgpConditionsTable. If the 'lgpConditionAckReq' is 'required' then the condition will remain in the condition table until both the 'lgpConditionCurrentState' is 'inactive' AND 'lgpConditionAcknowledged' is 'acknowledged'.
INT lgpConditionAckReq1.3.6.1.4.1.476.1.42.3.2.3.1.19INTEGERread-onlyThis indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of 'required'. Those conditions that do not require user acknowledgement will have a value of 'notRequired' or in some devices the column may not be present at all. If a condition requires acknowledgement it will remain in the table until both the 'lgpConditionCurrentState' and 'lgpConditionAcknowledged' are 'inactive' and 'acknowledged' respectively (see lgpConditionAcknowledged). If a condition does not require acknowledgement it will be removed from the table as soon as its 'lgpConditionCurrentState' is 'inactive'.
lgpConditionControl1.3.6.1.4.1.476.1.42.3.2.4
INT lgpConditionControlEventReset1.3.6.1.4.1.476.1.42.3.2.4.1INTEGERread-writeEvent Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained even when the event has become inactive. The 'set' field is only cleared when the user clears it and the event is no longer active. This item will clear the 'set' field for all events that are not active.
INT lgpConditionControlEventAck1.3.6.1.4.1.476.1.42.3.2.4.2INTEGERread-writeEvent Acknowledge Command. This command will acknowledge all of the device's events.
lgpConditionControlTable1.3.6.1.4.1.476.1.42.3.2.4.20not-accessibleA list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controllable by the unit. This table does not necessarily contain all conditions supported by the unit. This table only contains conditions that are end-user modifiable.
lgpConditionControlEntry1.3.6.1.4.1.476.1.42.3.2.4.20.1not-accessibleThis entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP operations on columns of the table.
U32 lgpConditionControlIndex1.3.6.1.4.1.476.1.42.3.2.4.20.1.1Unsigned32not-accessibleThis is the index indicating the nth element of the table.
OID lgpConditionControlDescr1.3.6.1.4.1.476.1.42.3.2.4.20.1.2OBJECT IDENTIFIERread-onlyA reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier referenced here will be the same object identifier referenced in the lgpConditionsTable (column: lgpConditionDescr) when the condition is activated.
INT lgpConditionControlEnableStatus1.3.6.1.4.1.476.1.42.3.2.4.20.1.3INTEGERread-writeThe value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if the condition indicated by lgpConditionControlDescr becomes active. If the value is 'disabled' the device will never generate the event. This value is stored on the managed device. Some devices do not allow write access to some entries in this column. The 'lgpConditionControlEnableCapability' column indicates whether this entry can be written.
INT lgpConditionControlType1.3.6.1.4.1.476.1.42.3.2.4.20.1.4INTEGERread-writeThe 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType). For some units this is user configurable. This value is stored on the managed device.
INT lgpConditionControlEnableCapability1.3.6.1.4.1.476.1.42.3.2.4.20.1.5INTEGERread-onlySome devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlEnableStatus' entry for this row can be written.
STR lgpConditionDescription1.3.6.1.4.1.476.1.42.3.2.5DisplayStringread-onlyThe ASCII text description for the condition.
STR lgpNetworkName1.3.6.1.4.1.476.1.42.3.2.6DisplayStringread-onlyThe network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a network address. As an example the lgpAgentDnsLookupFailure trap which describes a network name that is failing or has failed to be resolved from a Domain Name Service (DNS) lookup. Refer to RFC 952 for further information.
lgpFlexConditions1.3.6.1.4.1.476.1.42.3.2.7

RFC description

Eaton Liebert vendor-private MIB for monitoring environmental and operational conditions in power/cooling systems.

Start monitoring Vertiv/Liebert power/cooling equipment (any generation, GP conditions) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.

Download LIEBERT-GP-CONDITIONS-MIB