| OID symbolic | OID numeric | Type | Access | Description |
| eatonPduMIB | 1.3.6.1.4.1.534.6.6.4 | | | The MIB module for Eaton PDUs (Power Distribution Units).
Copyright (C) Eaton Corporation (2007). |
| eatonPduMIBObjects | 1.3.6.1.4.1.534.6.6.4.1 | | | |
| mainPdu | 1.3.6.1.4.1.534.6.6.4.1.1 | | | |
| pduNameplate | 1.3.6.1.4.1.534.6.6.4.1.1.1 | | | |
| NUM pduRatingVA | 1.3.6.1.4.1.534.6.6.4.1.1.1.1 | PositiveInteger | read-only | The full VA rating of this PDU (for all phases). |
| NUM pduNominalOutputVoltage | 1.3.6.1.4.1.534.6.6.4.1.1.1.2 | PositiveInteger | read-only | The nominal Output Voltage of this PDU (as distributed
to the panels). May differ from the nominal Input Voltage
if the PDU has an input transformer.
This is either Line-to-Line or Line-to-Neutral,
as indicated in pduOutputVoltageUnits. |
| NUM pduNumPhases | 1.3.6.1.4.1.534.6.6.4.1.1.1.3 | PositiveInteger | read-only | The number of lines (phases) for this PDU.
The number of Input phases must equal the number
of Output phases. |
| NUM pduNumPanels | 1.3.6.1.4.1.534.6.6.4.1.1.1.4 | PositiveInteger | read-only | The number of panels or subfeeds contained in this PDU system.
This determines the number of rows found in the panel tables. |
| pduInput | 1.3.6.1.4.1.534.6.6.4.1.1.2 | | | |
| NUM pduFrequency | 1.3.6.1.4.1.534.6.6.4.1.1.2.1 | NonNegativeInteger | read-only | The present frequency reading for the full PDU. |
| NUM pduInputVA | 1.3.6.1.4.1.534.6.6.4.1.1.2.2 | NonNegativeInteger | read-only | The present VA input demand of the full PDU system. |
| NUM pduInputPower | 1.3.6.1.4.1.534.6.6.4.1.1.2.3 | NonNegativeInteger | read-only | The present input power demand of the full PDU system. |
| I32 pduInputPowerFactorEx | 1.3.6.1.4.1.534.6.6.4.1.1.2.4 | Integer32 | read-only | The input power factor for the full PDU system.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf. |
| NUM pduGroundCurrent | 1.3.6.1.4.1.534.6.6.4.1.1.2.5 | NonNegativeInteger | read-only | The present current in the PDU's ground phase.
Ideally, this value stays at 0. |
| STR pduInputVoltageUnits | 1.3.6.1.4.1.534.6.6.4.1.1.2.6 | DisplayString | read-only | Indicates whether the pduInputPhaseVoltage readings are
'Vrms Line-Line' or 'Vrms Line-Neutral'. |
| NUM pduInputNumPhases | 1.3.6.1.4.1.534.6.6.4.1.1.2.7 | PositiveInteger | read-only | The number of input phases for this PDU.
This variable indicates the number of rows in the pduInputTable. |
| pduInputTable | 1.3.6.1.4.1.534.6.6.4.1.1.2.8 | | not-accessible | A list of input table entries. The number of entries
is given by the value of pduInputNumPhases. |
| pduInputEntry | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1 | | not-accessible | An entry containing information applicable to a
particular input phase. |
| NUM pduInputPhaseIndex | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.1 | PositiveInteger | not-accessible | The input line identifier. |
| NUM pduInputPhaseVoltage | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.2 | NonNegativeInteger | read-only | The present input voltage for this phase. |
| NUM pduInputPhaseCurrent | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.3 | NonNegativeInteger | read-only | The present input current for this phase. |
| I32 pduInputPhasePercentLoad | 1.3.6.1.4.1.534.6.6.4.1.1.2.8.1.4 | Integer32 | read-only | The percentage of the pdu power capacity presently
being used on this line, normally based on the
ratio of pduInputPhaseCurrent to the rated input current. |
| pduOutput | 1.3.6.1.4.1.534.6.6.4.1.1.3 | | | |
| NUM pduOutputKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.1.3.1 | NonNegativeInteger | read-only | The accumulated kilowatt-hour value for the full PDU system
since the last reset. |
| NUM pduOutputVA | 1.3.6.1.4.1.534.6.6.4.1.1.3.2 | NonNegativeInteger | read-only | The present VA output of the full PDU system. |
| NUM pduOutputPower | 1.3.6.1.4.1.534.6.6.4.1.1.3.3 | NonNegativeInteger | read-only | The present output power of the full PDU system. |
| I32 pduOutputPowerFactor | 1.3.6.1.4.1.534.6.6.4.1.1.3.4 | Integer32 | read-only | The output power factor for the full PDU system.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf. |
| NUM pduNeutralCurrent | 1.3.6.1.4.1.534.6.6.4.1.1.3.5 | NonNegativeInteger | read-only | The present current in the PDU's output neutral phase.
Ideally, this value stays at 0. |
| NUM pduRatedOutputCurrent | 1.3.6.1.4.1.534.6.6.4.1.1.3.6 | PositiveInteger | read-only | The rated current value for one PDU Output phase
at full load (100%). |
| STR pduOutputVoltageUnits | 1.3.6.1.4.1.534.6.6.4.1.1.3.7 | DisplayString | read-only | Indicates whether the pduOutputPhaseVoltage readings are
'Vrms Line-Line' or 'Vrms Line-Neutral'. |
| NUM pduOutputNumPhases | 1.3.6.1.4.1.534.6.6.4.1.1.3.8 | PositiveInteger | read-only | The number of output phases for this PDU.
This variable indicates the number of rows in the pduOutputTable. |
| pduOutputTable | 1.3.6.1.4.1.534.6.6.4.1.1.3.9 | | not-accessible | A list of output table entries. The number of
entries is given by the value of pduOutputNumPhases. |
| pduOutputEntry | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1 | | not-accessible | An entry containing information applicable to a
particular output phase. |
| NUM pduOutputPhaseIndex | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.1 | PositiveInteger | not-accessible | The output line identifier. |
| NUM pduOutputPhaseVoltage | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.2 | NonNegativeInteger | read-only | The present output voltage for this phase. |
| NUM pduOutputPhaseCurrent | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.3 | NonNegativeInteger | read-only | The present output current for this phase. |
| I32 pduOutputPhasePercentLoad | 1.3.6.1.4.1.534.6.6.4.1.1.3.9.1.4 | Integer32 | read-only | The percentage of the pdu power capacity presently
being used on this line, normally based on the
ratio of pduOutputPhaseCurrent to pduRatedOutputCurrent. |
| pduPanel | 1.3.6.1.4.1.534.6.6.4.1.2 | | | |
| panelRatingsTable | 1.3.6.1.4.1.534.6.6.4.1.2.1 | | not-accessible | A sparsely populated (ie, not sequentially numbered)
table of ratings for each panel. The number of
entries is given by the value of pduNumPanels. |
| panelRatingsEntry | 1.3.6.1.4.1.534.6.6.4.1.2.1.1 | | not-accessible | An entry containing information applicable to a
particular output phase. |
| NUM panelNumber | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.1 | PositiveInteger | not-accessible | Index for the Panel Ratings and Meters tables.
Corresponds to the physical panel number in the
PDU system.
There must be a #1. The maximum value is 16.
Panels are not required to be numbered sequentially. |
| NUM panelRatedVoltage | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.2 | PositiveInteger | read-only | The nominal Voltage of this panel (as distributed
to the breakers or subfeeds).
This is either Line-to-Line or Line-to-Neutral,
as indicated in panelVoltageUnits. |
| NUM panelRatedBreakerCurrent | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.3 | PositiveInteger | read-only | The rated current value for one panel (input) phase
at full load (100%). This is set by the panel's
input breaker; if there is no input breaker for this
panel, then this object is not accessible. |
| NUM panelNumPhases | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.4 | PositiveInteger | read-only | The number of lines (phases) for this panel. |
| NUM panelNumBreakers | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.5 | PositiveInteger | read-only | The number of breakers contained in this panel.
This determines the number of rows found in the breaker tables. |
| STR panelVoltageUnits | 1.3.6.1.4.1.534.6.6.4.1.2.1.1.6 | DisplayString | read-only | Indicates whether the panelPhaseVoltage readings are
'Vrms Line-Line' or 'Vrms Line-Neutral'. |
| panelMetersTable | 1.3.6.1.4.1.534.6.6.4.1.2.2 | | not-accessible | A sparsely populated (ie, not sequentially numbered)
table of ratings for each panel. The number of
entries is given by the value of pduNumPanels. |
| panelMetersEntry | 1.3.6.1.4.1.534.6.6.4.1.2.2.1 | | not-accessible | An entry containing meter readings applicable to a
particular panel. |
| NUM panelTotalKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.1 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this panel
since it was commissioned and put into service,
or since the last reset of the system KHW measures. |
| NUM panelMonthlyKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.2 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this panel
since the beginning of this calendar month,
or since the last reset of the system KHW measures. |
| NUM panelYtdKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.3 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this panel
since the beginning of this calendar year (YTD),
or since the last reset of the system KHW measures. |
| NUM panelVA | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.4 | NonNegativeInteger | read-only | The present VA (input) demand of this panel. |
| NUM panelPower | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.5 | NonNegativeInteger | read-only | The present power (input) demand of this panel. |
| I32 panelPowerFactor | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.6 | Integer32 | read-only | The input power factor for this panel.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf. |
| NUM panelNeutralCurrent | 1.3.6.1.4.1.534.6.6.4.1.2.2.1.7 | NonNegativeInteger | read-only | The present neutral phase current for this panel. |
| panelPhaseMetersTable | 1.3.6.1.4.1.534.6.6.4.1.2.3 | | not-accessible | A sparsely populated (ie, not sequentially panel numbered)
table of ratings for each panel. The number of
entries is given by the sum of panelNumPhases for pduNumPanels. |
| panelPhaseMetersEntry | 1.3.6.1.4.1.534.6.6.4.1.2.3.1 | | not-accessible | An entry containing meter readings applicable to a
particular phase of a particular panel. |
| NUM panelPhaseIndex | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.1 | PositiveInteger | not-accessible | The line or phase identifier. |
| NUM panelPhaseVoltage | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.2 | NonNegativeInteger | read-only | The present voltage for this phase. |
| NUM panelPhaseCurrent | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.3 | NonNegativeInteger | read-only | The present current for this phase. |
| I32 panelPhasePercentLoad | 1.3.6.1.4.1.534.6.6.4.1.2.3.1.4 | Integer32 | read-only | The percentage of the panel power capacity presently
being used on this line, normally based on the
ratio of panelPhaseCurrent to the rated phase current. |
| pduBreaker | 1.3.6.1.4.1.534.6.6.4.1.3 | | | |
| breakerRatingsTable | 1.3.6.1.4.1.534.6.6.4.1.3.1 | | not-accessible | A sparsely populated (ie, not sequentially numbered)
table of ratings and fixed values for each breaker.
The number of entries is given by the value of
panelNumBreakers for this panel. |
| breakerRatingsEntry | 1.3.6.1.4.1.534.6.6.4.1.3.1.1 | | not-accessible | An entry containing information applicable to a
particular output phase. |
| NUM breakerNumber | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.1 | PositiveInteger | not-accessible | Index for the Breaker Ratings and Meters tables.
Corresponds to the physical breaker number in the
PDU system.
Breakers are not required to be numbered sequentially. |
| STR breakerName | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.2 | DisplayString | read-only | Name given by the administrator to identify this breaker. |
| NUM breakerRatedCurrent | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.3 | PositiveInteger | read-only | The rated current value of this breaker (for one phase)
at full load (100%). |
| NUM breakerNumPhases | 1.3.6.1.4.1.534.6.6.4.1.3.1.1.4 | PositiveInteger | read-only | The number of lines (phases) for this breaker. |
| breakerMetersTable | 1.3.6.1.4.1.534.6.6.4.1.3.2 | | not-accessible | A sparsely populated (ie, not sequentially numbered)
table of ratings for each breaker. The number of
entries is given by the value of panelNumBreakers
for this panel. |
| breakerMetersEntry | 1.3.6.1.4.1.534.6.6.4.1.3.2.1 | | not-accessible | An entry containing meter readings applicable to a
particular breaker. |
| NUM breakerTotalKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.1 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this breaker
since it was commissioned and put into service,
or since the last reset of the panel KHW measures. |
| NUM breakerMonthlyKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.2 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this breaker
since the beginning of this calendar month,
or since the last reset of the panel KHW measures. |
| NUM breakerYtdKilowattHours | 1.3.6.1.4.1.534.6.6.4.1.3.2.1.3 | NonNegativeInteger | read-only | The accumulated kilowatt-hours for this breaker
since the beginning of this calendar year (YTD),
or since the last reset of the panel KHW measures. |
| breakerPhaseMetersTable | 1.3.6.1.4.1.534.6.6.4.1.3.3 | | not-accessible | A sparsely populated (ie, not sequentially breaker numbered)
table of ratings for each breaker. The number of
entries is given by the sum of breakerNumPhases for
panelNumBreakers for all panels (pduNumPanels). |
| breakerPhaseMetersEntry | 1.3.6.1.4.1.534.6.6.4.1.3.3.1 | | not-accessible | An entry containing meter readings applicable to a particular
phase of a particular breaker on a particular panel. |
| NUM breakerPhaseIndex | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.1 | PositiveInteger | not-accessible | The line or phase identifier. |
| NUM breakerPhaseVA | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.2 | NonNegativeInteger | read-only | The present VA (input) demand of this phase on
this breaker. |
| NUM breakerPhasePower | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.3 | NonNegativeInteger | read-only | The present power (input) demand of phase on
this breaker. |
| I32 breakerPhasePowerFactor | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.4 | Integer32 | read-only | The input power factor for this phase on this breaker.
Varies from -1.00 to 1.00, multiplied by 100.
If negative values are used, they indicate lagging pf. |
| NUM breakerPhaseCurrent | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.5 | NonNegativeInteger | read-only | The present current for this phase of this breaker. |
| I32 breakerPhasePercentLoad | 1.3.6.1.4.1.534.6.6.4.1.3.3.1.6 | Integer32 | read-only | The percentage of the breaker power capacity presently
being used on this line, normally based on the
ratio of breakerPhaseCurrent to the breakerRatedCurrent. |
| eatonPduConformance | 1.3.6.1.4.1.534.6.6.4.2 | | | |
| pduNameplateGroup | 1.3.6.1.4.1.534.6.6.4.2.1 | | | The pduNameplate subgroup objects. |
| pduInputGroup | 1.3.6.1.4.1.534.6.6.4.2.2 | | | The pduInput Meters subgroup objects. |
| pduOutputGroup | 1.3.6.1.4.1.534.6.6.4.2.3 | | | The pduOutput Meters subgroup objects. |
| panelRatingsGroup | 1.3.6.1.4.1.534.6.6.4.2.4 | | | The panelRatings table objects. |
| panelMetersGroup | 1.3.6.1.4.1.534.6.6.4.2.5 | | | The BreakerMeters Table objects. |
| panelPhaseMetersGroup | 1.3.6.1.4.1.534.6.6.4.2.6 | | | The BreakerPhaseMeters Table objects. |
| breakerRatingsGroup | 1.3.6.1.4.1.534.6.6.4.2.7 | | | The breakerRatings table objects. |
| breakerMetersGroup | 1.3.6.1.4.1.534.6.6.4.2.8 | | | The breakerMeters table objects. |
| breakerPhaseMetersGroup | 1.3.6.1.4.1.534.6.6.4.2.9 | | | The breakerPhaseMeters table objects. |
| pdu3phaseCompliance | 1.3.6.1.4.1.534.6.6.4.2.10 | | | The compliance statement for a normal 3-phase PDU, which implements
the full set of objects. |