All MIBs › EPPC-MIB › upsESystemConfigBelowRemainTimeLimit
upsESystemConfigBelowRemainTimeLimit
Module: EPPC-MIB
OID (symbolic): EPPC-MIB::upsESystemConfigBelowRemainTimeLimit
OID (numeric): 1.3.6.1.4.1.935.10.1.1.2.22
Node type: OBJECT-TYPE
Type: NonNegativeInteger
Access: read-write
Description: The UPS batteries backup time(minute) limit for shutdown
What is upsESystemConfigBelowRemainTimeLimit?
Read-write battery-runtime threshold in minutes; when the estimated remaining backup time drops below this, the UPS triggers its low-runtime shutdown event. Set it to match how long connected servers need to gracefully shut down.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.10.1.1.2.22 snmpwalk -v2c -c public <target> EPPC-MIB::upsESystemConfigBelowRemainTimeLimit
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.935.10.1.1.2.22.1 snmpget -v2c -c public <target> EPPC-MIB::upsESystemConfigBelowRemainTimeLimit.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.935.10.1.1.2.22.1 i <value>
Start monitoring Three-phase UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EPPC-MIB::upsESystemConfigBelowRemainTimeLimit OID value, configure state conditions and alerts, and monitor any Three-phase UPS system from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.935 | ppc | EPPC-MIB |
| 1.3.6.1.4.1.935.10 | device | EPPC-MIB |
| 1.3.6.1.4.1.935.10.1 | upsAgent | EPPC-MIB |
| 1.3.6.1.4.1.935.10.1.1 | upsE | EPPC-MIB |
| 1.3.6.1.4.1.935.10.1.1.2 | upsESystemSummary | EPPC-MIB |
| 1.3.6.1.4.1.935.10.1.1.2.22 | upsESystemConfigBelowRemainTimeLimit | EPPC-MIB |