All MIBs › ENLOGIC-PDU-MIB
Organization: Enlogic
Last Updated: 2015-06-18
Category: Domain: Power/UPS, Vendor: Enlogic
Description: Enlogic proprietary MIB for managing intelligent Power Distribution Units (PDUs), including power metering and outlet control.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is ENLOGIC-PDU-MIB?
ENLOGIC-PDU-MIB is Enlogic's proprietary MIB for its intelligent Power Distribution Units (PDUs), placing it in the data-center power/rack infrastructure management space. It exposes PDU nameplate/identity data (unit name, physical location, network configuration) alongside the broader power-metering and outlet-control objects the device supports. It is used to monitor the operational and configuration status of PDU hardware, including device identity, network reachability settings, and (per its broader design) power draw and outlet status, which are the key hardware health indicators for a PDU. No dependency on other standard MIBs is apparent from the available data; it appears to be a self-contained enterprise MIB. It is typically deployed in data-center or server-room racks to track and remotely manage individual PDU units across a facility. Engineers can download the ENLOGIC-PDU-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in ENLOGIC-PDU-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Enlogic intelligent Power Distribution Unit (PDU)
Monitoring Examples
An administrator would walk the pduNamePlateTable (via pduNamePlateEntry/pduNamePlateIndex) to inventory each PDU unit's pduNamePlateName and pduNamePlateLocation, cross-checking pduNamePlateIPAddress, pduNamePlateInetNetMask, and pduNamePlateMACAddress to confirm network reachability. A mismatch or stale pduNamePlateIPAddress compared to DHCP/DNS records would reveal a misconfigured or disconnected PDU before it becomes a power-monitoring blind spot.
What Can Be Monitored
- PDU unit identity/name
- PDU physical location
- PDU IP address and network configuration
- PDU MAC address
- PDU UTC time offset
This MIB depends on
Related MIBs
Imported Objects
From INET-ADDRESS-MIB
| InetAddress | |
| InetAddressType |
From RFC1213-MIB
| sysContact | |
| sysLocation | |
| sysName |
From SNMPv2-CONF
| MODULE-COMPLIANCE | |
| NOTIFICATION-GROUP | |
| OBJECT-GROUP |
From SNMPv2-SMI
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| Unsigned32 | |
| enterprises |
From SNMPv2-TC
| DisplayString | |
| MacAddress | |
| TEXTUAL-CONVENTION | |
| TruthValue |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| enlogic | 1.3.6.1.4.1.38446 | This MIB describes the SNMP functions of the Enlogic PDU. | ||
| pdu | 1.3.6.1.4.1.38446.1 | |||
| pduNamePlate | 1.3.6.1.4.1.38446.1.1 | |||
| I32 pduNamePlateTableSize | 1.3.6.1.4.1.38446.1.1.1 | Integer32 | read-only | The total number of PDUs |
| pduNamePlateTable | 1.3.6.1.4.1.38446.1.1.2 | not-accessible | A table of PDU nameplate data | |
| pduNamePlateEntry | 1.3.6.1.4.1.38446.1.1.2.1 | not-accessible | Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize. | |
| I32 pduNamePlateIndex | 1.3.6.1.4.1.38446.1.1.2.1.1 | Integer32 | not-accessible | The index of the PDU nameplate table entry |
| STR pduNamePlateName | 1.3.6.1.4.1.38446.1.1.2.1.2 | DisplayString | read-only | A user-defined string identifying the PDU |
| STR pduNamePlateLocation | 1.3.6.1.4.1.38446.1.1.2.1.3 | DisplayString | read-only | A user-defined string identifying the location of PDU |
| IPt pduNamePlateInetAddressType | 1.3.6.1.4.1.38446.1.1.2.1.4 | InetAddressType | read-only | The type of address format |
| IP pduNamePlateIPAddress | 1.3.6.1.4.1.38446.1.1.2.1.5 | InetAddress | read-only | The current IP address. A value of 0.0.0.0 indicates an error or an unset option |
| IP pduNamePlateInetNetMask | 1.3.6.1.4.1.38446.1.1.2.1.6 | InetAddress | read-only | The current netmask. A value of 0.0.0.0 indiates an error or an unset option |
| IP pduNamePlateInetGateway | 1.3.6.1.4.1.38446.1.1.2.1.7 | InetAddress | read-only | The current gateway. A value of 0.0.0.0 indicates an error or an unset option |
| MAC pduNamePlateMACAddress | 1.3.6.1.4.1.38446.1.1.2.1.8 | MacAddress | read-only | The assigned MAC address for the PDU |
| STR pduNamePlateUTCTimeOffset | 1.3.6.1.4.1.38446.1.1.2.1.9 | DisplayString | read-only | The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone |
| STR pduNamePlateModelNumber | 1.3.6.1.4.1.38446.1.1.2.1.10 | DisplayString | read-only | The PDU model number |
| STR pduNamePlateSerialNumber | 1.3.6.1.4.1.38446.1.1.2.1.11 | DisplayString | read-only | The PDU serial number |
| STR pduNamePlateDateofManufacture | 1.3.6.1.4.1.38446.1.1.2.1.12 | DisplayString | read-only | The date the PDU was manufactured in mm/dd/yyyy format |
| STR pduNamePlateFirmwareVersion | 1.3.6.1.4.1.38446.1.1.2.1.13 | DisplayString | read-only | The PDU firmware version |
| STR pduNamePlateFirmwareVersionTimeStamp | 1.3.6.1.4.1.38446.1.1.2.1.14 | DisplayString | read-only | Timestamp of when the PDU firmware was last updated |
| INT pduNamePlateType | 1.3.6.1.4.1.38446.1.1.2.1.15 | INTEGER | read-only | The type of Unit, PDU or Inline Meter |
| pduUnit | 1.3.6.1.4.1.38446.1.2 | |||
| I32 pduUnitTableSize | 1.3.6.1.4.1.38446.1.2.1 | Integer32 | read-only | The number of units. |
| pduUnitConfigTable | 1.3.6.1.4.1.38446.1.2.2 | not-accessible | A table of PDU configuration data | |
| pduUnitConfigEntry | 1.3.6.1.4.1.38446.1.2.2.1 | not-accessible | Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize | |
| I32 pduUnitConfigIndex | 1.3.6.1.4.1.38446.1.2.2.1.1 | Integer32 | not-accessible | The index of the PDU Unit Config Entry |
| STR pduUnitConfigName | 1.3.6.1.4.1.38446.1.2.2.1.2 | DisplayString | read-write | A user-defined string identifying the PDU |
| STR pduUnitConfigLocation | 1.3.6.1.4.1.38446.1.2.2.1.3 | DisplayString | read-write | A user-defined string identifying the location of the PDU |
| INT pduUnitConfigDisplayOrientation | 1.3.6.1.4.1.38446.1.2.2.1.4 | INTEGER | read-write | Indicates the intended physical orientation of the oLED display displayNormal (1) indicates normal orientation. displayReverse (2) indicates upside down orientation |
| U32 pduUnitConfigColdstartDelay | 1.3.6.1.4.1.38446.1.2.2.1.5 | Unsigned32 | read-write | The amount of time, specified in seconds, between when power is provided to the PDU and when the PDU start providing basic master power to the outlets |
| INT pduUnitConfigGlobalOutletStateOnStartup | 1.3.6.1.4.1.38446.1.2.2.1.6 | INTEGER | read-write | The outlet state on device startup; applies to all outlets unless overridden at the outlet level |
| U32 pduUnitConfigLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.2.2.1.7 | Unsigned32 | read-write | User-defined lower critical unit active power alarm threshold measured in Watts |
| U32 pduUnitConfigLowerWarningThreshold | 1.3.6.1.4.1.38446.1.2.2.1.8 | Unsigned32 | read-write | User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts |
| U32 pduUnitConfigUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.2.2.1.9 | Unsigned32 | read-write | User-defined upper critical unit active power alarm threshold measured in Watts |
| U32 pduUnitConfigUpperWarningThreshold | 1.3.6.1.4.1.38446.1.2.2.1.10 | Unsigned32 | read-write | User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts |
| U32 pduUnitConfigAlarmResetThreshold | 1.3.6.1.4.1.38446.1.2.2.1.11 | Unsigned32 | read-write | The hysteresis used for deassertions in Watts |
| U32 pduUnitConfigAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.2.2.1.12 | Unsigned32 | read-write | The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduUnitConfigEnabledThresholds | 1.3.6.1.4.1.38446.1.2.2.1.13 | Bits | read-write | A bit string indicating which alarm thresholds are enabled |
| INT pduUnitConfigPeakPowerReset | 1.3.6.1.4.1.38446.1.2.2.1.14 | INTEGER | read-write | Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value. |
| INT pduUnitConfigEnergyReset | 1.3.6.1.4.1.38446.1.2.2.1.15 | INTEGER | read-write | Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail. |
| INT pduUnitConfigOutletPeakPowerReset | 1.3.6.1.4.1.38446.1.2.2.1.16 | INTEGER | read-write | Setting this OID to reset (2) will cause the outlet peak power meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail. |
| INT pduUnitConfigOutletEnergyReset | 1.3.6.1.4.1.38446.1.2.2.1.17 | INTEGER | read-write | Setting this OID to reset (2) will cause the outlet energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail. |
| INT pduUnitConfigUsb | 1.3.6.1.4.1.38446.1.2.2.1.18 | INTEGER | read-write | Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port. |
| INT pduUnitConfigSsh | 1.3.6.1.4.1.38446.1.2.2.1.19 | INTEGER | read-write | Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection. |
| INT pduUnitConfigResetNetworkManagementCard | 1.3.6.1.4.1.38446.1.2.2.1.20 | INTEGER | read-write | Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC. |
| INT pduUnitConfigDaisyChainState | 1.3.6.1.4.1.38446.1.2.2.1.21 | INTEGER | read-write | Setting this OID to daisychain(0) will enable daisychain mode. |
| pduUnitPropertiesTable | 1.3.6.1.4.1.38446.1.2.3 | not-accessible | A table of PDU properties | |
| pduUnitPropertiesEntry | 1.3.6.1.4.1.38446.1.2.3.1 | not-accessible | A unit properties entry containing objects for a particular unit. | |
| I32 pduUnitPropertiesIndex | 1.3.6.1.4.1.38446.1.2.3.1.1 | Integer32 | not-accessible | The index of the PDU properties table entry |
| STR pduUnitPropertiesName | 1.3.6.1.4.1.38446.1.2.3.1.2 | DisplayString | read-only | A user-defined string identifying the PDU |
| I32 pduUnitPropertiesOutletCount | 1.3.6.1.4.1.38446.1.2.3.1.3 | Integer32 | read-only | The total number of outlets on the PDU |
| I32 pduUnitPropertiesSwitchedOutletCount | 1.3.6.1.4.1.38446.1.2.3.1.4 | Integer32 | read-only | The total number of switched outlets on the PDU |
| I32 pduUnitPropertiesMeteredOutletCount | 1.3.6.1.4.1.38446.1.2.3.1.5 | Integer32 | read-only | The total number of metered outlets on the PDU |
| I32 pduUnitPropertiesInputPhaseCount | 1.3.6.1.4.1.38446.1.2.3.1.6 | Integer32 | read-only | The total number of phases on the PDU |
| I32 pduUnitPropertiesCircuitBreakerCount | 1.3.6.1.4.1.38446.1.2.3.1.7 | Integer32 | read-only | The total number of circuit breaker on the PDU |
| I32 pduUnitPropertiesMaxExternalSensorCount | 1.3.6.1.4.1.38446.1.2.3.1.8 | Integer32 | read-only | The maximum number of external sensors that can be connected to the PDU |
| I32 pduUnitPropertiesConnExternalSensorCount | 1.3.6.1.4.1.38446.1.2.3.1.9 | Integer32 | read-only | The current number of external sensors connected to the PDU |
| STR pduUnitPropertiesRatedVoltage | 1.3.6.1.4.1.38446.1.2.3.1.10 | DisplayString | read-only | The PDU voltage rating in Volts |
| STR pduUnitPropertiesRatedMaxCurrent | 1.3.6.1.4.1.38446.1.2.3.1.11 | DisplayString | read-only | The PDU current rating in Amps |
| STR pduUnitPropertiesRatedFrequency | 1.3.6.1.4.1.38446.1.2.3.1.12 | DisplayString | read-only | The PDU frequency rating in Hz |
| STR pduUnitPropertiesRatedPower | 1.3.6.1.4.1.38446.1.2.3.1.13 | DisplayString | read-only | The PDU VA (VoltAmps) rating. |
| INT pduUnitPropertiesOrientation | 1.3.6.1.4.1.38446.1.2.3.1.14 | INTEGER | read-only | The PDU orientation |
| INT pduUnitPropertiesOutletLayout | 1.3.6.1.4.1.38446.1.2.3.1.15 | INTEGER | read-only | The outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9): |
| INT pduUnitPropertiesDaisyChainMemberType | 1.3.6.1.4.1.38446.1.2.3.1.16 | INTEGER | read-only | The daisy-chain member type |
| I32 pduUnitPropertiesServerCount | 1.3.6.1.4.1.38446.1.2.3.1.17 | Integer32 | read-only | The number of servers |
| pduUnitStatusTable | 1.3.6.1.4.1.38446.1.2.4 | not-accessible | A table of PDU status information | |
| pduUnitStatusEntry | 1.3.6.1.4.1.38446.1.2.4.1 | not-accessible | Status information from the PDU being queried | |
| I32 pduUnitStatusIndex | 1.3.6.1.4.1.38446.1.2.4.1.1 | Integer32 | not-accessible | The index of the PDU status table entry |
| STR pduUnitStatusName | 1.3.6.1.4.1.38446.1.2.4.1.2 | DisplayString | read-only | A user-defined string identifying the PDU |
| INT pduUnitStatusLoadState | 1.3.6.1.4.1.38446.1.2.4.1.3 | INTEGER | read-only | Returns the present load status of the PDU based on Active Power. |
| I32 pduUnitStatusActivePower | 1.3.6.1.4.1.38446.1.2.4.1.4 | Integer32 | read-only | Returns power consumption, in Watts(W), of the PDU being queried. |
| I32 pduUnitStatusApparentPower | 1.3.6.1.4.1.38446.1.2.4.1.5 | Integer32 | read-only | Returns power consumption, in Volt-Amps(VA) of the PDU load being queried. |
| I32 pduUnitStatusPeakPower | 1.3.6.1.4.1.38446.1.2.4.1.6 | Integer32 | read-only | Returns peak power consumption, in Watts(W), of the PDU being queried. |
| STR pduUnitStatusPeakPowerTimestamp | 1.3.6.1.4.1.38446.1.2.4.1.7 | DisplayString | read-only | Indicates the date and time that peak power consumption occurred |
| STR pduUnitStatusPeakPowerStartTime | 1.3.6.1.4.1.38446.1.2.4.1.8 | DisplayString | read-only | Indicates the date and time of the last device peak power reset |
| I32 pduUnitStatusEnergy | 1.3.6.1.4.1.38446.1.2.4.1.9 | Integer32 | read-only | Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime. |
| I32 pduUnitStatusResettableEnergy | 1.3.6.1.4.1.38446.1.2.4.1.10 | Integer32 | read-only | A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh). |
| STR pduUnitStatusEnergyStartTime | 1.3.6.1.4.1.38446.1.2.4.1.11 | DisplayString | read-only | Indicates the date and time of the last device energy meter reset |
| STR pduUnitStatusOutletsEnergyStartTime | 1.3.6.1.4.1.38446.1.2.4.1.12 | DisplayString | read-only | Indicates the date and time of the last outlets energy meter reset |
| pduInputPhase | 1.3.6.1.4.1.38446.1.3 | |||
| I32 pduInputPhaseTableSize | 1.3.6.1.4.1.38446.1.3.1 | Integer32 | read-only | The number of PDU Input Phases |
| pduInputPhaseConfigTable | 1.3.6.1.4.1.38446.1.3.2 | not-accessible | A table of PDU Input Phase configuration data | |
| pduInputPhaseConfigEntry | 1.3.6.1.4.1.38446.1.3.2.1 | not-accessible | An input phase entry containing objects for a particular input phase. | |
| I32 pduInputPhaseConfigIndex | 1.3.6.1.4.1.38446.1.3.2.1.1 | Integer32 | not-accessible | The index of the PDU Input Phase configuration table entry |
| I32 pduInputPhaseConfigCount | 1.3.6.1.4.1.38446.1.3.2.1.2 | Integer32 | read-only | The total number of Input Phases |
| INT pduInputPhaseConfigOverloadRestriction | 1.3.6.1.4.1.38446.1.3.2.1.3 | INTEGER | read-write | This OID controls the behavior of a Switched PDU Input Phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Input Phase to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Input Phase to turn on if the pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail. |
| U32 pduInputPhaseConfigCurrentLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.3.2.1.4 | Unsigned32 | read-write | User-defined lower critical input phase current alarm threshold in hundredths of Amps(A). |
| U32 pduInputPhaseConfigCurrentLowerWarningThreshold | 1.3.6.1.4.1.38446.1.3.2.1.5 | Unsigned32 | read-write | User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). |
| U32 pduInputPhaseConfigCurrentUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.3.2.1.6 | Unsigned32 | read-write | User-defined upper critical input phase current alarm threshold in hundredths of Amps(A). |
| U32 pduInputPhaseConfigCurrentUpperWarningThreshold | 1.3.6.1.4.1.38446.1.3.2.1.7 | Unsigned32 | read-write | User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A). |
| U32 pduInputPhaseConfigVoltageLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.3.2.1.8 | Unsigned32 | read-write | User-defined lower critical input phase voltage alarm threshold in Volts(V). |
| U32 pduInputPhaseConfigVoltageLowerWarningThreshold | 1.3.6.1.4.1.38446.1.3.2.1.9 | Unsigned32 | read-write | User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V). |
| U32 pduInputPhaseConfigVoltageUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.3.2.1.10 | Unsigned32 | read-write | User-defined upper critical input phase voltage alarm threshold in Volts(V). |
| U32 pduInputPhaseConfigVoltageUpperWarningThreshold | 1.3.6.1.4.1.38446.1.3.2.1.11 | Unsigned32 | read-write | User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V). |
| U32 pduInputPhaseConfigCurrentAlarmResetThreshold | 1.3.6.1.4.1.38446.1.3.2.1.12 | Unsigned32 | read-write | The hysteresis used for current alarm deassertions in hundredths of Amps(A). |
| I32 pduInputPhaseConfigCurrentAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.3.2.1.13 | Integer32 | read-write | The delay measured in samples before a current state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduInputPhaseConfigCurrentEnabledThresholds | 1.3.6.1.4.1.38446.1.3.2.1.14 | Bits | read-write | A bit string indicating which current alarm thresholds are enabled. |
| U32 pduInputPhaseConfigVoltageAlarmResetThreshold | 1.3.6.1.4.1.38446.1.3.2.1.15 | Unsigned32 | read-write | The hysteresis used for voltage alarm deassertions in Volts(V). |
| I32 pduInputPhaseConfigVoltageAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.3.2.1.16 | Integer32 | read-write | The delay measured in samples before a voltage state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduInputPhaseConfigVoltageEnabledThresholds | 1.3.6.1.4.1.38446.1.3.2.1.17 | Bits | read-write | A bit string indicating which voltage alarm thresholds are enabled. |
| pduInputPhasePropertiesTable | 1.3.6.1.4.1.38446.1.3.3 | not-accessible | A table of PDU Input Phase properties | |
| pduInputPhasePropertiesEntry | 1.3.6.1.4.1.38446.1.3.3.1 | not-accessible | An input phase properties entry containing objects for a particular input phase. | |
| I32 pduInputPhasePropertiesIndex | 1.3.6.1.4.1.38446.1.3.3.1.1 | Integer32 | not-accessible | The index of the PDU Input Phase status entry |
| I32 pduInputPhasePropertiesCount | 1.3.6.1.4.1.38446.1.3.3.1.2 | Integer32 | read-only | The numeric Input Phase ID |
| pduInputPhaseStatusTable | 1.3.6.1.4.1.38446.1.3.4 | not-accessible | A table of PDU Input Phase status data | |
| pduInputPhaseStatusEntry | 1.3.6.1.4.1.38446.1.3.4.1 | not-accessible | An input phase status entry containing objects for a particular input phase. | |
| I32 pduInputPhaseStatusIndex | 1.3.6.1.4.1.38446.1.3.4.1.1 | Integer32 | not-accessible | The index of the PDU Input Phase status entry |
| I32 pduInputPhaseStatusCount | 1.3.6.1.4.1.38446.1.3.4.1.2 | Integer32 | read-only | The numeric Input Phase ID |
| INT pduInputPhaseStatusCurrentState | 1.3.6.1.4.1.38446.1.3.4.1.3 | INTEGER | read-only | Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton. |
| INT pduInputPhaseStatusVoltageState | 1.3.6.1.4.1.38446.1.3.4.1.4 | INTEGER | read-only | Indicates the present voltage status of the PDU Input Phase being queried |
| I32 pduInputPhaseStatusCurrent | 1.3.6.1.4.1.38446.1.3.4.1.5 | Integer32 | read-only | Returns the current draw, in hundredths of Amps(A), of the load on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values. |
| I32 pduInputPhaseStatusVoltage | 1.3.6.1.4.1.38446.1.3.4.1.6 | Integer32 | read-only | Returns the voltage, in Volts(V), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values. |
| I32 pduInputPhaseStatusActivePower | 1.3.6.1.4.1.38446.1.3.4.1.7 | Integer32 | read-only | Returns power consumption, in Watts(W), consumed on the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values. |
| I32 pduInputPhaseStatusApparentPower | 1.3.6.1.4.1.38446.1.3.4.1.8 | Integer32 | read-only | Returns power consumption, in Volt-Amps(VA), of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values. |
| I32 pduInputPhaseStatusPowerFactor | 1.3.6.1.4.1.38446.1.3.4.1.9 | Integer32 | read-only | Returns the ratio of active to apparent power of the PDU Phase/Line being queried. Nodes with pduInputPhaseStatusIndex from 1 to 3 indicate Y connection Phase values or Delta connection Line values, and nodes with pduInputPhaseStatusIndex from 4 to 6 indicate Delta connection Phase values. |
| pduCircuitBreaker | 1.3.6.1.4.1.38446.1.4 | |||
| I32 pduCircuitBreakerTableSize | 1.3.6.1.4.1.38446.1.4.1 | Integer32 | read-only | The number of PDU Circuit Breakers |
| pduCircuitBreakerConfigTable | 1.3.6.1.4.1.38446.1.4.2 | not-accessible | A table of PDU Circuit Breaker configuration data | |
| pduCircuitBreakerConfigEntry | 1.3.6.1.4.1.38446.1.4.2.1 | not-accessible | A circuit breaker configuration entry containing objects for a particular circuit breaker. | |
| I32 pduCircuitBreakerConfigIndex | 1.3.6.1.4.1.38446.1.4.2.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker configuration table entry |
| I32 pduCircuitBreakerConfigCount | 1.3.6.1.4.1.38446.1.4.2.1.2 | Integer32 | read-only | The number of circuit breakers on the PDU |
| STR pduCircuitBreakerName | 1.3.6.1.4.1.38446.1.4.2.1.3 | DisplayString | read-only | The label of the circuit breaker |
| INT pduCircuitBreakerConfigOverloadRestriction | 1.3.6.1.4.1.38446.1.4.2.1.4 | INTEGER | read-write | This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail. |
| U32 pduCircuitBreakerConfigLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.4.2.1.5 | Unsigned32 | read-write | User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A). |
| U32 pduCircuitBreakerConfigLowerWarningThreshold | 1.3.6.1.4.1.38446.1.4.2.1.6 | Unsigned32 | read-write | User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A). |
| U32 pduCircuitBreakerConfigUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.4.2.1.7 | Unsigned32 | read-write | User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A). |
| U32 pduCircuitBreakerConfigUpperWarningThreshold | 1.3.6.1.4.1.38446.1.4.2.1.8 | Unsigned32 | read-write | User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A). |
| U32 pduCircuitBreakerConfigAlarmResetThreshold | 1.3.6.1.4.1.38446.1.4.2.1.9 | Unsigned32 | read-write | The hysteresis used for deassertions in hundredths of Amps(A). |
| U32 pduCircuitBreakerConfigAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.4.2.1.10 | Unsigned32 | read-write | The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduCircuitBreakerConfigEnabledThresholds | 1.3.6.1.4.1.38446.1.4.2.1.11 | Bits | read-write | A bit string indicating which alarm thresholds are enabled. |
| pduCircuitBreakerPropertiesTable | 1.3.6.1.4.1.38446.1.4.3 | not-accessible | A table of PDU circuit breaker properties | |
| pduCircuitBreakerPropertiesEntry | 1.3.6.1.4.1.38446.1.4.3.1 | not-accessible | A circuit breaker properties entry containing objects for a particular circuit breaker. | |
| I32 pduCircuitBreakerPropertiesIndex | 1.3.6.1.4.1.38446.1.4.3.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker properties table entry |
| I32 pduCircuitBreakerPropertiesCount | 1.3.6.1.4.1.38446.1.4.3.1.2 | Integer32 | read-only | The number of Circuit Breakers |
| INT pduCircuitBreakerPropertiesInputLayout | 1.3.6.1.4.1.38446.1.4.3.1.3 | INTEGER | read-only | This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1. |
| pduCircuitBreakerStatusTable | 1.3.6.1.4.1.38446.1.4.4 | not-accessible | A table of PDU circuit breaker status data | |
| pduCircuitBreakerStatusEntry | 1.3.6.1.4.1.38446.1.4.4.1 | not-accessible | A circuit breaker status entry containing objects for a particular circuit breaker. | |
| I32 pduCircuitBreakerStatusIndex | 1.3.6.1.4.1.38446.1.4.4.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker status table entry |
| I32 pduCircuitBreakerStatusCount | 1.3.6.1.4.1.38446.1.4.4.1.2 | Integer32 | read-only | The number of Circuit Breakers |
| STR pduCircuitBreakerLabel | 1.3.6.1.4.1.38446.1.4.4.1.3 | DisplayString | read-only | The label on the PDU identifying the circuit breaker |
| INT pduCircuitBreakerStatusLoadState | 1.3.6.1.4.1.38446.1.4.4.1.4 | INTEGER | read-only | Indicates the present load status of the PDU Circuit Breaker being queried |
| I32 pduCircuitBreakerStatusCurrent | 1.3.6.1.4.1.38446.1.4.4.1.5 | Integer32 | read-only | Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried. |
| pduOutlet | 1.3.6.1.4.1.38446.1.5 | |||
| I32 pduOutletSwitchedTableSize | 1.3.6.1.4.1.38446.1.5.1 | Integer32 | read-only | The number of PDU Outlets |
| pduOutletSwitchedConfigTable | 1.3.6.1.4.1.38446.1.5.2 | not-accessible | A table of PDU Switched Outlet configuration data | |
| pduOutletSwitchedConfigEntry | 1.3.6.1.4.1.38446.1.5.2.1 | not-accessible | An outlet configuration entry containing objects for a particular outlet. | |
| I32 pduOutletSwitchedConfigIndex | 1.3.6.1.4.1.38446.1.5.2.1.1 | Integer32 | not-accessible | The index of the PDU Switched Outlet configuration table entry |
| STR pduOutletSwitchedName | 1.3.6.1.4.1.38446.1.5.2.1.2 | DisplayString | read-write | The user-defined name for the Switched Outlet |
| INT pduOutletSwitchedStateOnStartup | 1.3.6.1.4.1.38446.1.5.2.1.3 | INTEGER | read-write | The outlet state on device startup; overrides the global value pduUnitConfigGlobalOutletStateOnStartup. |
| I32 pduOutletSwitchedConfigPowerOnTime | 1.3.6.1.4.1.38446.1.5.2.1.4 | Integer32 | read-write | The amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing power |
| I32 pduOutletSwitchedConfigPowerOffTime | 1.3.6.1.4.1.38446.1.5.2.1.5 | Integer32 | read-write | The amount of time, in seconds, this outlet will delay powering off |
| I32 pduOutletSwitchedConfigRebootDuration | 1.3.6.1.4.1.38446.1.5.2.1.6 | Integer32 | read-write | The amount of time, in seconds, this outlet will remain in powered off state before returning to power on state during a reboot action. |
| pduOutletSwitchedPropertiesTable | 1.3.6.1.4.1.38446.1.5.3 | not-accessible | A table of PDU Switched Outlet properties | |
| pduOutletSwitchedPropertiesEntry | 1.3.6.1.4.1.38446.1.5.3.1 | not-accessible | An outlet properties entry containing objects for a particular outlet. | |
| I32 pduOutletSwitchedPropertiesIndex | 1.3.6.1.4.1.38446.1.5.3.1.1 | Integer32 | not-accessible | The index of the PDU Switched Outlet properties table entry |
| I32 pduOutletSwitchedPropertiesNumber | 1.3.6.1.4.1.38446.1.5.3.1.2 | Integer32 | read-only | The numeric Switched Outlet ID |
| STR pduOutletSwitchedPropertiesName | 1.3.6.1.4.1.38446.1.5.3.1.3 | DisplayString | read-only | The user-defined switched outlet ID string |
| INT pduOutletSwitchedPropertiesInputPhaseLayout | 1.3.6.1.4.1.38446.1.5.3.1.4 | INTEGER | read-only | This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Switched Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Switched Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Switched Outlet are connected from Phase 3 to Phase1. |
| I32 pduOutletSwitchedPropertiesCircuitBreaker | 1.3.6.1.4.1.38446.1.5.3.1.5 | Integer32 | read-only | The numeric Circuit Breaker ID |
| pduOutletSwitchedStatusTable | 1.3.6.1.4.1.38446.1.5.4 | not-accessible | A table of PDU Switched Outlet status data | |
| pduOutletSwitchedStatusEntry | 1.3.6.1.4.1.38446.1.5.4.1 | not-accessible | Status data from the PDU Switched Outlet being queried | |
| I32 pduOutletSwitchedStatusIndex | 1.3.6.1.4.1.38446.1.5.4.1.1 | Integer32 | not-accessible | The index of the PDU Switched Outlet status table entry |
| I32 pduOutletSwitchedStatusNumber | 1.3.6.1.4.1.38446.1.5.4.1.2 | Integer32 | read-only | The numeric Switched Outlet ID |
| STR pduOutletSwitchedStatusName | 1.3.6.1.4.1.38446.1.5.4.1.3 | DisplayString | read-only | The user-defined switched outlet ID string |
| INT pduOutletSwitchedStatusState | 1.3.6.1.4.1.38446.1.5.4.1.4 | INTEGER | read-only | Indicates the present switch state of the PDU switched outlet being queried |
| pduOutletSwitchedControlTable | 1.3.6.1.4.1.38446.1.5.5 | not-accessible | A table of PDU Switched Outlet status data | |
| pduOutletSwitchedControlEntry | 1.3.6.1.4.1.38446.1.5.5.1 | not-accessible | Status data from the PDU Switched Outlet being queried | |
| I32 pduOutletSwitchedControlIndex | 1.3.6.1.4.1.38446.1.5.5.1.1 | Integer32 | not-accessible | The index to the PDU switched outlet control data table entry |
| I32 pduOutletSwitchedControlNumber | 1.3.6.1.4.1.38446.1.5.5.1.2 | Integer32 | read-only | The numeric Switched Outlet ID |
| STR pduOutletSwitchedControlName | 1.3.6.1.4.1.38446.1.5.5.1.3 | DisplayString | read-only | The user-defined switched outlet ID string |
| INT pduOutletSwitchedControlCommand | 1.3.6.1.4.1.38446.1.5.5.1.4 | INTEGER | read-write | Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command. |
| I32 pduOutletMeteredTableSize | 1.3.6.1.4.1.38446.1.5.6 | Integer32 | read-only | The number of PDU Outlets |
| pduOutletMeteredConfigTable | 1.3.6.1.4.1.38446.1.5.7 | not-accessible | A table of PDU Metered Outlet configuration data | |
| pduOutletMeteredConfigEntry | 1.3.6.1.4.1.38446.1.5.7.1 | not-accessible | An outlet configuration entry containing objects for a particular outlet. | |
| I32 pduOutletMeteredConfigIndex | 1.3.6.1.4.1.38446.1.5.7.1.1 | Integer32 | not-accessible | The index of the PDU Metered Outlet configuration table entry |
| STR pduOutletMeteredName | 1.3.6.1.4.1.38446.1.5.7.1.2 | DisplayString | read-write | The user-defined name for the Metered Outlet |
| U32 pduOutletMeteredConfigLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.5.7.1.3 | Unsigned32 | read-write | User-defined lower critical outlet active power alarm threshold in Watts(W). |
| U32 pduOutletMeteredConfigLowerWarningThreshold | 1.3.6.1.4.1.38446.1.5.7.1.4 | Unsigned32 | read-write | User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W). |
| U32 pduOutletMeteredConfigUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.5.7.1.5 | Unsigned32 | read-write | User-defined upper critical outlet active power alarm threshold in Watts(W). |
| U32 pduOutletMeteredConfigUpperWarningThreshold | 1.3.6.1.4.1.38446.1.5.7.1.6 | Unsigned32 | read-write | User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W). |
| U32 pduOutletMeteredConfigAlarmResetThreshold | 1.3.6.1.4.1.38446.1.5.7.1.7 | Unsigned32 | read-write | The hysteresis used for deassertions in Watts(W). |
| U32 pduOutletMeteredConfigAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.5.7.1.8 | Unsigned32 | read-write | The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduOutletMeteredConfigEnabledThresholds | 1.3.6.1.4.1.38446.1.5.7.1.9 | Bits | read-write | A bit string indicating which alarm thresholds are enabled. |
| pduOutletMeteredPropertiesTable | 1.3.6.1.4.1.38446.1.5.8 | not-accessible | A table of PDU Metered Outlet properties | |
| pduOutletMeteredPropertiesEntry | 1.3.6.1.4.1.38446.1.5.8.1 | not-accessible | Configuration data from the PDU Metered Outlet being queried | |
| I32 pduOutletMeteredPropertiesIndex | 1.3.6.1.4.1.38446.1.5.8.1.1 | Integer32 | not-accessible | The index of the PDU Metered Outlet properties table entry |
| I32 pduOutletMeteredPropertiesNumber | 1.3.6.1.4.1.38446.1.5.8.1.2 | Integer32 | read-only | The numeric Metered Outlet ID |
| STR pduOutletMeteredPropertiesName | 1.3.6.1.4.1.38446.1.5.8.1.3 | DisplayString | read-only | The user-defined Metered outlet ID string |
| INT pduOutletMeteredPropertiesInputPhaseLayout | 1.3.6.1.4.1.38446.1.5.8.1.4 | INTEGER | read-only | This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to Metered Outlet are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to Metered Outlet are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to Metered Outlet are connected from Phase 3 to Phase1. |
| I32 pduOutletMeteredPropertiesCircuitBreaker | 1.3.6.1.4.1.38446.1.5.8.1.5 | Integer32 | read-only | The numeric Circuit Breaker ID |
| I32 pduOutletMeteredPropertiesPowerRating | 1.3.6.1.4.1.38446.1.5.8.1.6 | Integer32 | read-only | Maximum power rating of the PDU metered outlet |
| pduOutletMeteredStatusTable | 1.3.6.1.4.1.38446.1.5.9 | not-accessible | A table of PDU Metered Outlet status data | |
| pduOutletMeteredStatusEntry | 1.3.6.1.4.1.38446.1.5.9.1 | not-accessible | Status data from the PDU Metered Outlet being queried | |
| I32 pduOutletMeteredStatusIndex | 1.3.6.1.4.1.38446.1.5.9.1.1 | Integer32 | not-accessible | The index of the PDU Metered Outlet status table entry |
| I32 pduOutletMeteredStatusNumber | 1.3.6.1.4.1.38446.1.5.9.1.2 | Integer32 | read-only | The numeric Metered Outlet ID |
| STR pduOutletMeteredStatusName | 1.3.6.1.4.1.38446.1.5.9.1.3 | DisplayString | read-only | The user-defined Metered outlet ID string |
| INT pduOutletMeteredStatusLoadState | 1.3.6.1.4.1.38446.1.5.9.1.4 | INTEGER | read-only | Returns the present load status of the PDU metered outlet being queried. |
| I32 pduOutletMeteredStatusCurrent | 1.3.6.1.4.1.38446.1.5.9.1.5 | Integer32 | read-only | Returns the current draw, in hundredths of Amps(A), of the load on the PDU outlet being queried. |
| I32 pduOutletMeteredStatusActivePower | 1.3.6.1.4.1.38446.1.5.9.1.6 | Integer32 | read-only | Returns the power draw, in Watts(W), of the load on the PDU outlet being queried. |
| I32 pduOutletMeteredStatusPowerFactor | 1.3.6.1.4.1.38446.1.5.9.1.7 | Integer32 | read-only | Returns the ratio of active to apparent power of the PDU Outlet being queried |
| I32 pduOutletMeteredStatusPeakPower | 1.3.6.1.4.1.38446.1.5.9.1.8 | Integer32 | read-only | Returns peak power consumption, in Watts(W), of the Rack PDU outlet being queried. |
| STR pduOutletMeteredStatusPeakPowerTimeStamp | 1.3.6.1.4.1.38446.1.5.9.1.9 | DisplayString | read-only | Indicates the date and time that this metered outlet's peak power consumption occurred |
| STR pduOutletMeteredStatusPeakPowerStartTime | 1.3.6.1.4.1.38446.1.5.9.1.10 | DisplayString | read-only | Indicates the start date and time that this metered outlet began recording peak power observations |
| I32 pduOutletMeteredStatusResettableEnergy | 1.3.6.1.4.1.38446.1.5.9.1.11 | Integer32 | read-only | A user resettable energy meter measuring outlet load energy consumption in tenths of Kilowatt-Hours(kWh). |
| pduExternalSensor | 1.3.6.1.4.1.38446.1.6 | |||
| I32 pduExternalSensorTableSize | 1.3.6.1.4.1.38446.1.6.1 | Integer32 | read-only | The total number of External Sensors |
| pduExternalSensorNamePlateTable | 1.3.6.1.4.1.38446.1.6.2 | not-accessible | A table of PDU ExternalSensorNamePlate data | |
| pduExternalSensorNamePlateEntry | 1.3.6.1.4.1.38446.1.6.2.1 | not-accessible | External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of pduExternalSensorNamePlateTableSize. | |
| I32 pduExternalSensorNamePlateIndex | 1.3.6.1.4.1.38446.1.6.2.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor status table entry |
| STR pduExternalSensorNamePlateName | 1.3.6.1.4.1.38446.1.6.2.1.2 | DisplayString | read-write | A user-defined string identifying the external sensor |
| STR pduExternalSensorNamePlateDescription | 1.3.6.1.4.1.38446.1.6.2.1.3 | DisplayString | read-write | A user-defined description of the external sensor |
| STR pduExternalSensorNamePlateLocation | 1.3.6.1.4.1.38446.1.6.2.1.4 | DisplayString | read-write | A user-defined string identifying the location of the PDU |
| STR pduExternalSensorNamePlateSerialNumber | 1.3.6.1.4.1.38446.1.6.2.1.5 | DisplayString | read-only | The serial number of the external sensor being queried |
| INT pduExternalSensorNamePlateType | 1.3.6.1.4.1.38446.1.6.2.1.6 | INTEGER | read-only | The type of external sensor. |
| INT pduExternalSensorNamePlateUnits | 1.3.6.1.4.1.38446.1.6.2.1.7 | INTEGER | read-only | The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors. |
| I32 pduExternalSensorNamePlateIdentifier | 1.3.6.1.4.1.38446.1.6.2.1.8 | Integer32 | read-only | Unique identifier of the external sensor. |
| pduExternalSensorConfigTable | 1.3.6.1.4.1.38446.1.6.3 | not-accessible | A table of PDU External Sensor configuration data | |
| pduExternalSensorConfigEntry | 1.3.6.1.4.1.38446.1.6.3.1 | not-accessible | Configuration data from the PDU External Sensor being queried | |
| I32 pduExternalSensorConfigIndex | 1.3.6.1.4.1.38446.1.6.3.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor configuration table entry |
| U32 pduExternalSensorConfigLowerCriticalThreshold | 1.3.6.1.4.1.38446.1.6.3.1.2 | Unsigned32 | read-write | User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits. |
| U32 pduExternalSensorConfigLowerWarningThreshold | 1.3.6.1.4.1.38446.1.6.3.1.3 | Unsigned32 | read-write | User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits. |
| U32 pduExternalSensorConfigUpperCriticalThreshold | 1.3.6.1.4.1.38446.1.6.3.1.4 | Unsigned32 | read-write | User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits. |
| U32 pduExternalSensorConfigUpperWarningThreshold | 1.3.6.1.4.1.38446.1.6.3.1.5 | Unsigned32 | read-write | User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits. |
| U32 pduExternalSensorConfigAlarmResetThreshold | 1.3.6.1.4.1.38446.1.6.3.1.6 | Unsigned32 | read-write | The hysteresis used for deassertions. |
| U32 pduExternalSensorConfigAlarmStateChangeDelay | 1.3.6.1.4.1.38446.1.6.3.1.7 | Unsigned32 | read-write | The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported. |
| BIT pduExternalSensorConfigEnabledThresholds | 1.3.6.1.4.1.38446.1.6.3.1.8 | Bits | read-write | A bit string indicating which alarm thresholds are enabled. |
| INT pduExternalSensorConfigAlarmState | 1.3.6.1.4.1.38446.1.6.3.1.9 | INTEGER | read-write | User defined alarm state of external sensor |
| pduExternalSensorStatusTable | 1.3.6.1.4.1.38446.1.6.4 | not-accessible | A table of PDU External Sensor status data | |
| pduExternalSensorStatusEntry | 1.3.6.1.4.1.38446.1.6.4.1 | not-accessible | Status data from the PDU External Sensor being queried | |
| I32 pduExternalSensorStatusIndex | 1.3.6.1.4.1.38446.1.6.4.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor status table entry |
| STR pduExternalSensorStatusName | 1.3.6.1.4.1.38446.1.6.4.1.2 | DisplayString | read-only | The user-defined name for the External Sensor |
| INT pduExternalSensorStatusAisle | 1.3.6.1.4.1.38446.1.6.4.1.3 | INTEGER | read-write | Indicates whether the external sensor is in a hot or cold aisle |
| INT pduExternalSensorStatusCommStatus | 1.3.6.1.4.1.38446.1.6.4.1.4 | INTEGER | read-only | The communications status of the sensor |
| INT pduExternalSensorStatusState | 1.3.6.1.4.1.38446.1.6.4.1.5 | INTEGER | read-only | This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold. |
| I32 pduExternalSensorStatusValue | 1.3.6.1.4.1.38446.1.6.4.1.6 | Integer32 | read-only | Sensor reading in pduExternalSensorConfigUnits value. |
| STR pduExternalSensorStatusTimeStamp | 1.3.6.1.4.1.38446.1.6.4.1.7 | DisplayString | read-only | The sensor reading timestamp. |
| I32 pduExternalSensorStatusHighPrecisionValue | 1.3.6.1.4.1.38446.1.6.4.1.8 | Integer32 | read-only | Temperature sensor reading in tenths of pduExternalSensorConfigUnits value. This OID is applied to temperature sensor only |
| pduServerPing | 1.3.6.1.4.1.38446.1.7 | |||
| I32 pduServerPingTableSize | 1.3.6.1.4.1.38446.1.7.1 | Integer32 | read-only | The total number of Servers |
| pduServerPingTable | 1.3.6.1.4.1.38446.1.7.2 | not-accessible | A table of Server Ping data | |
| pduServerPingEntry | 1.3.6.1.4.1.38446.1.7.2.1 | not-accessible | Server Ping data from the server being queried. The number of entries equals the value of pduServerPingTableSize. | |
| I32 pduServerPingIndex | 1.3.6.1.4.1.38446.1.7.2.1.1 | Integer32 | not-accessible | The index of the PDU pduServerPing table entry |
| STR pduServerPingServerIPAddress | 1.3.6.1.4.1.38446.1.7.2.1.2 | DisplayString | read-only | The IP Address/host name of the server |
| INT pduServerPingEnabled | 1.3.6.1.4.1.38446.1.7.2.1.3 | INTEGER | read-write | Is ping enabled for this server? |
| pduSmartCabinet | 1.3.6.1.4.1.38446.1.8 | |||
| I32 pduUnitSmartCabinetTableSize | 1.3.6.1.4.1.38446.1.8.1 | Integer32 | read-only | The total number of Smart Cabinet Configuration |
| pduUnitSmartCabinetTable | 1.3.6.1.4.1.38446.1.8.2 | not-accessible | A table of Smart Cabinet information | |
| pduUnitSmartCabinetEntry | 1.3.6.1.4.1.38446.1.8.2.1 | not-accessible | Information of Smart Cabinet | |
| I32 pduUnitSmartCabinetIndex | 1.3.6.1.4.1.38446.1.8.2.1.1 | Integer32 | not-accessible | The index of the PDU Smart Cabinet table entry |
| STR pduUnitSmartCabinetCardUserName | 1.3.6.1.4.1.38446.1.8.2.1.2 | DisplayString | read-only | User name of ID card |
| I32 pduUnitSmartCabinetCardID | 1.3.6.1.4.1.38446.1.8.2.1.3 | Integer32 | read-only | Card ID. |
| STR pduUnitSmartCabinetTimestamp | 1.3.6.1.4.1.38446.1.8.2.1.4 | DisplayString | read-only | Indicates the date and time of information update |
| INT pduUnitSmartCabinetDoor | 1.3.6.1.4.1.38446.1.8.2.1.5 | INTEGER | read-only | Aisle of Smart Cabinet. |
| pduUnitSmartCabinetControl | 1.3.6.1.4.1.38446.1.8.3 | |||
| STR pduUnitSmartCabinetControlUserName | 1.3.6.1.4.1.38446.1.8.3.1 | DisplayString | read-write | User name of ID card |
| I32 pduUnitSmartCabinetControlCardID | 1.3.6.1.4.1.38446.1.8.3.2 | Integer32 | read-write | Card ID. |
| STR pduUnitSmartCabinetControlTimestamp | 1.3.6.1.4.1.38446.1.8.3.3 | DisplayString | read-write | Indicates the date and time of information update |
| INT pduUnitSmartCabinetControlDoor | 1.3.6.1.4.1.38446.1.8.3.4 | INTEGER | read-write | Aisle of Smart Cabinet. |
| INT pduUnitSmartCabinetCardIDEdit | 1.3.6.1.4.1.38446.1.8.3.5 | INTEGER | read-write | Smart Cabinet edit CardID |
| INT pduUnitSmartCabinetColdAisleLockState | 1.3.6.1.4.1.38446.1.8.3.6 | INTEGER | read-write | Smart Cabinet ColdAisle lock state |
| INT pduUnitSmartCabinetHotAisleLockState | 1.3.6.1.4.1.38446.1.8.3.7 | INTEGER | read-write | Smart Cabinet HotAisle lock state |
| pduTraps | 1.3.6.1.4.1.38446.1.9 | |||
| trapsInfo | 1.3.6.1.4.1.38446.1.9.1 | |||
| trapsInfoTable | 1.3.6.1.4.1.38446.1.9.1.1 | not-accessible | A list of Trap Information entries. The number of entries are given by the value of pduUnitTableSize. | |
| trapsInfoEntry | 1.3.6.1.4.1.38446.1.9.1.1.1 | not-accessible | An entry containing objects used in traps | |
| I32 trapsInfoIndex | 1.3.6.1.4.1.38446.1.9.1.1.1.1 | Integer32 | not-accessible | The index of the traps table entry |
| STR userName | 1.3.6.1.4.1.38446.1.9.1.1.1.2 | DisplayString | read-only | The user currently logged in. |
| STR userUpdated | 1.3.6.1.4.1.38446.1.9.1.1.1.3 | DisplayString | read-only | The user added, deleted, or modified. |
| STR firmwareVersion | 1.3.6.1.4.1.38446.1.9.1.1.1.4 | DisplayString | read-only | The version of Firmware. |
| STR roleUpdated | 1.3.6.1.4.1.38446.1.9.1.1.1.5 | DisplayString | read-only | The role added, deleted, or modified. |
| STR smtpRecipients | 1.3.6.1.4.1.38446.1.9.1.1.1.6 | DisplayString | read-only | Comma separated list of SMTP recipients |
| STR smtpServer | 1.3.6.1.4.1.38446.1.9.1.1.1.7 | DisplayString | read-only | The IP address/host name of the SMTP server |
| I32 pduIndex | 1.3.6.1.4.1.38446.1.9.1.2 | Integer32 | accessible-for-notify | A unique value for PDU. Its value ranges between 1 and the value of PDU count |
| I32 externalSensorIndex | 1.3.6.1.4.1.38446.1.9.1.3 | Integer32 | accessible-for-notify | A unique value for each sensor. Its value ranges between 1 and the value of external sensor count. |
| INT serverPing | 1.3.6.1.4.1.38446.1.9.1.4 | INTEGER | accessible-for-notify | Whether server ping has been enabled or disabled and whether the server is reachable or not reachable |
| INT usbDevice | 1.3.6.1.4.1.38446.1.9.1.5 | INTEGER | accessible-for-notify | Whether a USB device has been connected or disconnected |
| STR errorDescription | 1.3.6.1.4.1.38446.1.9.1.6 | DisplayString | accessible-for-notify | Description of the Error |
| INT daisyChain | 1.3.6.1.4.1.38446.1.9.1.7 | INTEGER | accessible-for-notify | Whether a daisy chain member has been connected or disconnected |
| INT systemCommunication | 1.3.6.1.4.1.38446.1.9.1.8 | INTEGER | accessible-for-notify | Whether the Network management card has lost contact with daisy a chain member. |
| NTF networkCardStart | 1.3.6.1.4.1.38446.1.9.2 | The network card has started | ||
| NTF networkCardReset | 1.3.6.1.4.1.38446.1.9.3 | The network card was reset via the web or command line interface. | ||
| NTF userLogin | 1.3.6.1.4.1.38446.1.9.4 | A user logged in | ||
| NTF userLogoff | 1.3.6.1.4.1.38446.1.9.5 | A user logged off | ||
| NTF userAuthenticationFailed | 1.3.6.1.4.1.38446.1.9.6 | A user authentication attempt failed. | ||
| NTF userSessionTimeout | 1.3.6.1.4.1.38446.1.9.7 | A user session timed out | ||
| NTF userAdded | 1.3.6.1.4.1.38446.1.9.8 | A user account was added to system. | ||
| NTF userModified | 1.3.6.1.4.1.38446.1.9.9 | A user account was modified. | ||
| NTF userDeleted | 1.3.6.1.4.1.38446.1.9.10 | A user account was deleted. | ||
| NTF roleAdded | 1.3.6.1.4.1.38446.1.9.11 | A user role was added. | ||
| NTF roleModified | 1.3.6.1.4.1.38446.1.9.12 | A user role was modified. | ||
| NTF roleDeleted | 1.3.6.1.4.1.38446.1.9.13 | A user role was deleted. | ||
| NTF firmwareUpdateStarted | 1.3.6.1.4.1.38446.1.9.14 | A firmware update has started. | ||
| NTF firmwareUpdateCompleted | 1.3.6.1.4.1.38446.1.9.15 | The firmware update has completed. | ||
| NTF userBlocked | 1.3.6.1.4.1.38446.1.9.16 | A user is blocked. | ||
| NTF outletControl | 1.3.6.1.4.1.38446.1.9.17 | Outlet control operation applied. | ||
| NTF userPasswordChange | 1.3.6.1.4.1.38446.1.9.18 | A user password was changed. | ||
| NTF passwordSettingsChange | 1.3.6.1.4.1.38446.1.9.19 | One or more password policy settings were changed. | ||
| NTF logFileCleared | 1.3.6.1.4.1.38446.1.9.21 | The log file has been cleared. | ||
| NTF pduConfigurationFileImported | 1.3.6.1.4.1.38446.1.9.22 | PDU configuration file was imported. | ||
| NTF pduConfigurationFileExported | 1.3.6.1.4.1.38446.1.9.23 | PDU configuration file was exported | ||
| NTF pduUnitActivePowerStateChange | 1.3.6.1.4.1.38446.1.9.24 | PDU unit active power state changes. | ||
| NTF pduInputphaseVoltageStateChange | 1.3.6.1.4.1.38446.1.9.25 | PDU input phase voltage state changes. | ||
| NTF pduInputphaseCurrentStateChange | 1.3.6.1.4.1.38446.1.9.26 | PDU input phase Current state changes. | ||
| NTF pduCircuitBreakerCurrentStateChange | 1.3.6.1.4.1.38446.1.9.27 | PDU Circuit Breaker Current state changes. | ||
| NTF pduOutletActivePowerStateChange | 1.3.6.1.4.1.38446.1.9.28 | PDU Metered Outlet Active Power state changes. | ||
| NTF pduExternalSensorStateChange | 1.3.6.1.4.1.38446.1.9.29 | PDU External Sensor state changes. | ||
| NTF smtpTransmissionFailure | 1.3.6.1.4.1.38446.1.9.30 | SMTP message transmission failed. | ||
| NTF ldapError | 1.3.6.1.4.1.38446.1.9.31 | A LDAP error occurred | ||
| NTF firmwareUpdateFailed | 1.3.6.1.4.1.38446.1.9.32 | A firmware update has failed. | ||
| NTF serverPingState | 1.3.6.1.4.1.38446.1.9.33 | The Ping feature has been enabled. | ||
| NTF bootloaderState | 1.3.6.1.4.1.38446.1.9.34 | Enter into Bootloader mode | ||
| NTF daisyChainState | 1.3.6.1.4.1.38446.1.9.35 | A daisy chain member has been connected or disconnected. | ||
| NTF systemInternalCommunicationLost | 1.3.6.1.4.1.38446.1.9.36 | Network management card has lost contaction with internal boards. | ||
| NTF SmartCabinetLockUnlocked | 1.3.6.1.4.1.38446.1.9.37 | The Cabinet lock is unlocked. | ||
| NTF SmartCabinetLockLocked | 1.3.6.1.4.1.38446.1.9.38 | The Cabinet lock is locked | ||
| NTF SmartCabinetSwapCard | 1.3.6.1.4.1.38446.1.9.39 | Card is swapped | ||
| NTF SmartCabinetLockerLockDoorOpen | 1.3.6.1.4.1.38446.1.9.40 | Locker locked but door open | ||
| NTF SmartCabinetLockerUnlockDoorClose | 1.3.6.1.4.1.38446.1.9.41 | Locker unlocked but door close | ||
| NTF systemReboot | 1.3.6.1.4.1.38446.1.9.50 | System has rebooted | ||
| esp | 1.3.6.1.4.1.38446.2 | |||
| espNamePlate | 1.3.6.1.4.1.38446.2.1 | |||
| espNamePlateTable | 1.3.6.1.4.1.38446.2.1.2 | not-accessible | A table of es PDU nameplate data | |
| espNamePlateEntry | 1.3.6.1.4.1.38446.2.1.2.1 | not-accessible | Nameplate data from the PDU being queried. The numbers of entries equals the value of espNamePlateTableSize. | |
| I32 espNamePlateIndex | 1.3.6.1.4.1.38446.2.1.2.1.1 | Integer32 | not-accessible | The index of the es PDU nameplate table entry |
| STR espNamePlateName | 1.3.6.1.4.1.38446.2.1.2.1.2 | DisplayString | read-only | A user-defined string identifying the es PDU |
| STR espNamePlateLocation | 1.3.6.1.4.1.38446.2.1.2.1.3 | DisplayString | read-only | A user-defined string identifying the location of PDU |
| IPt espNamePlateInetAddressType | 1.3.6.1.4.1.38446.2.1.2.1.4 | InetAddressType | read-only | The type of address format |
| IP espNamePlateIPAddress | 1.3.6.1.4.1.38446.2.1.2.1.5 | InetAddress | read-only | The current IP address. A value of 0.0.0.0 indicates an error or an unset option |
| IP espNamePlateInetNetMask | 1.3.6.1.4.1.38446.2.1.2.1.6 | InetAddress | read-only | The current netmask. A value of 0.0.0.0 indiates an error or an unset option |
| IP espNamePlateInetGateway | 1.3.6.1.4.1.38446.2.1.2.1.7 | InetAddress | read-only | The current gateway. A value of 0.0.0.0 indicates an error or an unset option |
| MAC espNamePlateMACAddress | 1.3.6.1.4.1.38446.2.1.2.1.8 | MacAddress | read-only | The assigned MAC address for the PDU |
| STR espNamePlateUTCTimeOffset | 1.3.6.1.4.1.38446.2.1.2.1.9 | DisplayString | read-only | The difference in hours and minutes from Coordinated Universal Time(UTC) for the time used in a particular time zone |
| STR espNamePlateModelNumber | 1.3.6.1.4.1.38446.2.1.2.1.10 | DisplayString | read-only | The PDU model number |
| STR espNamePlateSerialNumber | 1.3.6.1.4.1.38446.2.1.2.1.11 | DisplayString | read-only | The PDU serial number |
| STR espNamePlateDateofManufacture | 1.3.6.1.4.1.38446.2.1.2.1.12 | DisplayString | read-only | The date the PDU was manufactured in mm/dd/yyyy format |
| STR espNamePlateFirmwareVersion | 1.3.6.1.4.1.38446.2.1.2.1.13 | DisplayString | read-only | The PDU firmware version |
| STR espNamePlateFirmwareVersionTimeStamp | 1.3.6.1.4.1.38446.2.1.2.1.14 | DisplayString | read-only | Timestamp of when the PDU firmware was last updated |
| INT espNamePlateType | 1.3.6.1.4.1.38446.2.1.2.1.15 | INTEGER | read-only | The type of Unit, PDU or Inline Meter |
| espUnit | 1.3.6.1.4.1.38446.2.2 | |||
| espUnitConfigTable | 1.3.6.1.4.1.38446.2.2.2 | not-accessible | A table of PDU configuration data | |
| espUnitConfigEntry | 1.3.6.1.4.1.38446.2.2.2.1 | not-accessible | Configuration data from the PDU being queried. The number of entries equals the value of espUnitTableSize | |
| I32 espUnitConfigIndex | 1.3.6.1.4.1.38446.2.2.2.1.1 | Integer32 | not-accessible | The index of the PDU Unit Config Entry |
| STR espUnitConfigName | 1.3.6.1.4.1.38446.2.2.2.1.2 | DisplayString | read-write | A user-defined string identifying the PDU |
| STR espUnitConfigLocation | 1.3.6.1.4.1.38446.2.2.2.1.3 | DisplayString | read-write | A user-defined string identifying the location of the PDU |
| INT espUnitConfigEnergyReset | 1.3.6.1.4.1.38446.2.2.2.1.15 | INTEGER | read-write | Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. Models that do not support this feature will respond to this OID with a value of notSupported (3). Attempts to set this OID in these models will fail. |
| INT espUnitConfigResetNetworkManagementCard | 1.3.6.1.4.1.38446.2.2.2.1.20 | INTEGER | read-write | Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC. |
| espUnitPropertiesTable | 1.3.6.1.4.1.38446.2.2.3 | not-accessible | A table of PDU properties | |
| espUnitPropertiesEntry | 1.3.6.1.4.1.38446.2.2.3.1 | not-accessible | A unit properties entry containing objects for a particular unit. | |
| I32 espUnitPropertiesIndex | 1.3.6.1.4.1.38446.2.2.3.1.1 | Integer32 | not-accessible | The index of the PDU properties table entry |
| STR espUnitPropertiesName | 1.3.6.1.4.1.38446.2.2.3.1.2 | DisplayString | read-only | A user-defined string identifying the PDU |
| I32 espUnitPropertiesOutletCount | 1.3.6.1.4.1.38446.2.2.3.1.3 | Integer32 | read-only | The total number of outlets on the PDU |
| I32 espUnitPropertiesSwitchedOutletCount | 1.3.6.1.4.1.38446.2.2.3.1.4 | Integer32 | read-only | The total number of switched outlets on the PDU |
| I32 espUnitPropertiesMeteredOutletCount | 1.3.6.1.4.1.38446.2.2.3.1.5 | Integer32 | read-only | The total number of metered outlets on the PDU |
| I32 espUnitPropertiesInputPhaseCount | 1.3.6.1.4.1.38446.2.2.3.1.6 | Integer32 | read-only | The total number of phases on the PDU |
| I32 espUnitPropertiesCircuitBreakerCount | 1.3.6.1.4.1.38446.2.2.3.1.7 | Integer32 | read-only | The total number of circuit breaker on the PDU |
| I32 espUnitPropertiesMaxExternalSensorCount | 1.3.6.1.4.1.38446.2.2.3.1.8 | Integer32 | read-only | The maximum number of external sensors that can be connected to the PDU |
| I32 espUnitPropertiesConnExternalSensorCount | 1.3.6.1.4.1.38446.2.2.3.1.9 | Integer32 | read-only | The current number of external sensors connected to the PDU |
| STR espUnitPropertiesRatedVoltage | 1.3.6.1.4.1.38446.2.2.3.1.10 | DisplayString | read-only | The PDU voltage rating in Volts |
| STR espUnitPropertiesRatedMaxCurrent | 1.3.6.1.4.1.38446.2.2.3.1.11 | DisplayString | read-only | The PDU current rating in Amps |
| STR espUnitPropertiesRatedFrequency | 1.3.6.1.4.1.38446.2.2.3.1.12 | DisplayString | read-only | The PDU frequency rating in Hz |
| STR espUnitPropertiesRatedPower | 1.3.6.1.4.1.38446.2.2.3.1.13 | DisplayString | read-only | The PDU VA (VoltAmps) rating. |
| espUnitStatusTable | 1.3.6.1.4.1.38446.2.2.4 | not-accessible | A table of PDU status information | |
| espUnitStatusEntry | 1.3.6.1.4.1.38446.2.2.4.1 | not-accessible | Status information from the PDU being queried | |
| I32 espUnitStatusIndex | 1.3.6.1.4.1.38446.2.2.4.1.1 | Integer32 | not-accessible | The index of the PDU status table entry |
| STR espUnitStatusName | 1.3.6.1.4.1.38446.2.2.4.1.2 | DisplayString | read-only | A user-defined string identifying the PDU |
| INT espUnitStatusLoadState | 1.3.6.1.4.1.38446.2.2.4.1.3 | INTEGER | read-only | Returns the present load status of the PDU based on Active Power. |
| I32 espUnitStatusActivePower | 1.3.6.1.4.1.38446.2.2.4.1.4 | Integer32 | read-only | Returns power consumption, in Watts(W), of the PDU being queried. |
| I32 espUnitStatusApparentPower | 1.3.6.1.4.1.38446.2.2.4.1.5 | Integer32 | read-only | Returns power consumption, in Volt-Amps(VA) of the PDU load being queried. |
| I32 espUnitStatusEnergy | 1.3.6.1.4.1.38446.2.2.4.1.9 | Integer32 | read-only | Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime. |
| I32 espUnitStatusResettableEnergy | 1.3.6.1.4.1.38446.2.2.4.1.10 | Integer32 | read-only | A user resettable energy meter measuring PDU energy consumption in tenths of kilowatt-hours(kWh). |
| STR espUnitStatusEnergyStartTime | 1.3.6.1.4.1.38446.2.2.4.1.11 | DisplayString | read-only | Indicates the date and time of the last device energy meter reset |
| espInputPhase | 1.3.6.1.4.1.38446.2.3 | |||
| espInputPhaseConfigTable | 1.3.6.1.4.1.38446.2.3.2 | not-accessible | A table of PDU Input Phase configuration data | |
| espInputPhaseConfigEntry | 1.3.6.1.4.1.38446.2.3.2.1 | not-accessible | An input phase entry containing objects for a particular input phase. | |
| I32 espInputPhaseConfigIndex | 1.3.6.1.4.1.38446.2.3.2.1.1 | Integer32 | not-accessible | The index of the PDU Input Phase configuration table entry |
| I32 espInputPhaseConfigCount | 1.3.6.1.4.1.38446.2.3.2.1.2 | Integer32 | read-only | The total number of Input Phases |
| espInputPhaseStatusTable | 1.3.6.1.4.1.38446.2.3.4 | not-accessible | A table of PDU Input Phase status data | |
| espInputPhaseStatusEntry | 1.3.6.1.4.1.38446.2.3.4.1 | not-accessible | An input phase status entry containing objects for a particular input phase. | |
| I32 espInputPhaseStatusIndex | 1.3.6.1.4.1.38446.2.3.4.1.1 | Integer32 | not-accessible | The index of the PDU Input Phase status entry |
| I32 espInputPhaseStatusCount | 1.3.6.1.4.1.38446.2.3.4.1.2 | Integer32 | read-only | The numeric Input Phase ID |
| INT espInputPhaseStatusCurrentState | 1.3.6.1.4.1.38446.2.3.4.1.3 | INTEGER | read-only | Indicates the present current status of the PDU Input Phase being queried |
| INT espInputPhaseStatusVoltageState | 1.3.6.1.4.1.38446.2.3.4.1.4 | INTEGER | read-only | Indicates the present voltage status of the PDU Input Phase being queried |
| I32 espInputPhaseStatusCurrent | 1.3.6.1.4.1.38446.2.3.4.1.5 | Integer32 | read-only | Returns the current draw, in hundredths of Amps(A), of the load on the PDU Input Phase being queried. |
| I32 espInputPhaseStatusVoltage | 1.3.6.1.4.1.38446.2.3.4.1.6 | Integer32 | read-only | Returns the voltage, in Volts(V), of the PDU Input Phase being queried. |
| I32 espInputPhaseStatusActivePower | 1.3.6.1.4.1.38446.2.3.4.1.7 | Integer32 | read-only | Returns power consumption, in Watts(W), consumed on the PDU Input Phase being queried. |
| I32 espInputPhaseStatusApparentPower | 1.3.6.1.4.1.38446.2.3.4.1.8 | Integer32 | read-only | Returns power consumption, in Volt-Amps(VA), of the PDU Input Phase being queried. |
| I32 espInputPhaseStatusPowerFactor | 1.3.6.1.4.1.38446.2.3.4.1.9 | Integer32 | read-only | Returns the ratio of active to apparent power of the PDU Input Phase being queried. |
| espCircuitBreaker | 1.3.6.1.4.1.38446.2.4 | |||
| espCircuitBreakerConfigTable | 1.3.6.1.4.1.38446.2.4.2 | not-accessible | A table of PDU Circuit Breaker configuration data | |
| espCircuitBreakerConfigEntry | 1.3.6.1.4.1.38446.2.4.2.1 | not-accessible | A circuit breaker configuration entry containing objects for a particular circuit breaker. | |
| I32 espCircuitBreakerConfigIndex | 1.3.6.1.4.1.38446.2.4.2.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker configuration table entry |
| I32 espCircuitBreakerConfigCount | 1.3.6.1.4.1.38446.2.4.2.1.2 | Integer32 | read-only | The number of circuit breakers on the PDU |
| STR espCircuitBreakerName | 1.3.6.1.4.1.38446.2.4.2.1.3 | DisplayString | read-only | The label of the circuit breaker |
| espCircuitBreakerPropertiesTable | 1.3.6.1.4.1.38446.2.4.3 | not-accessible | A table of PDU circuit breaker properties | |
| espCircuitBreakerPropertiesEntry | 1.3.6.1.4.1.38446.2.4.3.1 | not-accessible | A circuit breaker properties entry containing objects for a particular circuit breaker. | |
| I32 espCircuitBreakerPropertiesIndex | 1.3.6.1.4.1.38446.2.4.3.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker properties table entry |
| I32 espCircuitBreakerPropertiesCount | 1.3.6.1.4.1.38446.2.4.3.1.2 | Integer32 | read-only | The number of Circuit Breakers |
| INT espCircuitBreakerPropertiesInputLayout | 1.3.6.1.4.1.38446.2.4.3.1.3 | INTEGER | read-only | This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that outlets attached to circuit breaker are connected from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicates that outlets attached to circuit breaker are connected from Phase 2 to Neutral. seqPhase3ToNeutral(3) indicates that outlets attached to circuit breaker are connected from Phase 3 to Neutral. seqPhase1ToPhase2(4) indicates that outlets attached to circuit breaker are connected from Phase 1 to Phase2. seqPhase2ToPhase3(5) indicates that outlets attached to circuit breaker are connected from Phase 2 to Phase3. seqPhase3ToPhase1(6) indicates that outlets attached to circuit breaker are connected from Phase 3 to Phase1. |
| espCircuitBreakerStatusTable | 1.3.6.1.4.1.38446.2.4.4 | not-accessible | A table of PDU circuit breaker status data | |
| espCircuitBreakerStatusEntry | 1.3.6.1.4.1.38446.2.4.4.1 | not-accessible | A circuit breaker status entry containing objects for a particular circuit breaker. | |
| I32 espCircuitBreakerStatusIndex | 1.3.6.1.4.1.38446.2.4.4.1.1 | Integer32 | not-accessible | The index of the PDU Circuit Breaker status table entry |
| I32 espCircuitBreakerStatusCount | 1.3.6.1.4.1.38446.2.4.4.1.2 | Integer32 | read-only | The number of Circuit Breakers |
| STR espCircuitBreakerLabel | 1.3.6.1.4.1.38446.2.4.4.1.3 | DisplayString | read-only | The label on the PDU identifying the circuit breaker |
| INT espCircuitBreakerStatusLoadState | 1.3.6.1.4.1.38446.2.4.4.1.4 | INTEGER | read-only | Indicates the present load status of the PDU Circuit Breaker being queried |
| I32 espCircuitBreakerStatusCurrent | 1.3.6.1.4.1.38446.2.4.4.1.5 | Integer32 | read-only | Returns the current draw, in hundredths of Amps(A), of the load on the PDU Circuit Breaker being queried. |
| espExternalSensor | 1.3.6.1.4.1.38446.2.6 | |||
| espExternalSensorNamePlateTable | 1.3.6.1.4.1.38446.2.6.2 | not-accessible | A table of PDU ExternalSensorNamePlate data | |
| espExternalSensorNamePlateEntry | 1.3.6.1.4.1.38446.2.6.2.1 | not-accessible | External Sensor Name Plate data from the external sensor being queried. The number of entries equals the value of espExternalSensorNamePlateTableSize. | |
| I32 espExternalSensorNamePlateIndex | 1.3.6.1.4.1.38446.2.6.2.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor status table entry |
| STR espExternalSensorNamePlateName | 1.3.6.1.4.1.38446.2.6.2.1.2 | DisplayString | read-only | A user-defined string identifying the external sensor |
| STR espExternalSensorNamePlateSerialNumber | 1.3.6.1.4.1.38446.2.6.2.1.5 | DisplayString | read-only | The serial number of the external sensor being queried |
| INT espExternalSensorNamePlateType | 1.3.6.1.4.1.38446.2.6.2.1.6 | INTEGER | read-only | The type of external sensor. |
| INT espExternalSensorNamePlateUnits | 1.3.6.1.4.1.38446.2.6.2.1.7 | INTEGER | read-only | The base units the external sensor is measured in. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors. |
| espExternalSensorConfigTable | 1.3.6.1.4.1.38446.2.6.3 | not-accessible | A table of PDU External Sensor configuration data | |
| espExternalSensorConfigEntry | 1.3.6.1.4.1.38446.2.6.3.1 | not-accessible | Configuration data from the PDU External Sensor being queried | |
| I32 espExternalSensorConfigIndex | 1.3.6.1.4.1.38446.2.6.3.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor configuration table entry |
| INT espExternalSensorConfigAlarmState | 1.3.6.1.4.1.38446.2.6.3.1.9 | INTEGER | read-write | User defined alarm state of external sensor |
| espExternalSensorStatusTable | 1.3.6.1.4.1.38446.2.6.4 | not-accessible | A table of PDU External Sensor status data | |
| espExternalSensorStatusEntry | 1.3.6.1.4.1.38446.2.6.4.1 | not-accessible | Status data from the PDU External Sensor being queried | |
| I32 espExternalSensorStatusIndex | 1.3.6.1.4.1.38446.2.6.4.1.1 | Integer32 | not-accessible | The index of the PDU External Sensor status table entry |
| STR espExternalSensorStatusName | 1.3.6.1.4.1.38446.2.6.4.1.2 | DisplayString | read-only | The user-defined name for the External Sensor |
| INT espExternalSensorStatusAisle | 1.3.6.1.4.1.38446.2.6.4.1.3 | INTEGER | read-write | Indicates whether the external sensor is in a hot or cold aisle |
| INT espExternalSensorStatusCommStatus | 1.3.6.1.4.1.38446.2.6.4.1.4 | INTEGER | read-only | The communications status of the sensor |
| INT espExternalSensorStatusState | 1.3.6.1.4.1.38446.2.6.4.1.5 | INTEGER | read-only | This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold. |
| I32 espExternalSensorStatusValue | 1.3.6.1.4.1.38446.2.6.4.1.6 | Integer32 | read-only | Sensor reading in espExternalSensorConfigUnits value. |
| I32 espExternalSensorStatusHighPrecisionValue | 1.3.6.1.4.1.38446.2.6.4.1.8 | Integer32 | read-only | Temperature sensor reading in tenths of espExternalSensorConfigUnits value. This OID is applied to temperature sensor only |
| espTraps | 1.3.6.1.4.1.38446.2.9 | |||
| I32 espTrapsInfoIndex | 1.3.6.1.4.1.38446.2.9.1 | Integer32 | not-accessible | The index of the traps table entry |
| STR espUserName | 1.3.6.1.4.1.38446.2.9.2 | DisplayString | read-only | The user currently logged in. |
| STR espFirmwareVersion | 1.3.6.1.4.1.38446.2.9.4 | DisplayString | read-only | The version of Firmware. |
| I32 espIndex | 1.3.6.1.4.1.38446.2.9.5 | Integer32 | accessible-for-notify | A unique value for PDU. Its value ranges between 1 and the value of PDU count |
| I32 espExternalSensorIndex | 1.3.6.1.4.1.38446.2.9.6 | Integer32 | accessible-for-notify | A unique value for each sensor. Its value ranges between 1 and the value of external sensor count. |
| STR espErrorDescription | 1.3.6.1.4.1.38446.2.9.7 | DisplayString | accessible-for-notify | Description of the Error |
| NTF espNetworkCardStart | 1.3.6.1.4.1.38446.2.9.8 | The network card has started | ||
| NTF espNetworkCardReset | 1.3.6.1.4.1.38446.2.9.9 | The network card was reset via the web or command line interface. | ||
| NTF espFirmwareUpdateCompleted | 1.3.6.1.4.1.38446.2.9.10 | The firmware update has completed. | ||
| NTF espUserPasswordChange | 1.3.6.1.4.1.38446.2.9.11 | A user password was changed. | ||
| NTF espLogFileCleared | 1.3.6.1.4.1.38446.2.9.12 | The log file has been cleared. | ||
| NTF espConfigurationFileExported | 1.3.6.1.4.1.38446.2.9.13 | PDU configuration file was exported | ||
| NTF espUnitActivePowerStateChange | 1.3.6.1.4.1.38446.2.9.14 | PDU unit active power state changes. | ||
| NTF espInputphaseVoltageStateChange | 1.3.6.1.4.1.38446.2.9.15 | PDU input phase voltage state changes. | ||
| NTF espInputphaseCurrentStateChange | 1.3.6.1.4.1.38446.2.9.16 | PDU input phase Current state changes. | ||
| NTF espCircuitBreakerCurrentStateChange | 1.3.6.1.4.1.38446.2.9.17 | PDU Circuit Breaker Current state changes. | ||
| NTF espExternalSensorStateChange | 1.3.6.1.4.1.38446.2.9.18 | PDU External Sensor state changes. | ||
| NTF espConfigurationFileImported | 1.3.6.1.4.1.38446.2.9.19 | PDU configuration file was imported | ||
| NTF espNetworkUp | 1.3.6.1.4.1.38446.2.9.20 | PDU Network is up |
RFC description
Monitors power distribution units with outlet control, environmental sensors, and smart cabinet management.
Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.