All MIBs › ENLOGIC-PDU-MIB › pduOutletSwitchedControlCommand
pduOutletSwitchedControlCommand
Module: ENLOGIC-PDU-MIB
OID (symbolic): ENLOGIC-PDU-MIB::pduOutletSwitchedControlCommand
OID (numeric): 1.3.6.1.4.1.38446.1.5.5.1.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Getting this variable will return the outlet state. If the outlet is on, the immediateOn (2) value will be returned. If the outlet is off, the immediateOff (1) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (7) value will be returned. If the outletUnknown condition should occur, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to immediateOn (2) will immediately turn the outlet on. Setting this variable to immediateOff (1) will immediately turn the outlet off. Setting this variable to immediateReboot (5) will cause the Switched PDU to perform an immediateOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform an immediateOn command. Setting this variable to delayedOn (4) will turn the outlet on after the pduOutletSwitchedConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (3) will turn the outlet off after the pduOutletSwitchedConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched PDU to perform a delayedOff command, wait the pduOutletSwitchedConfigRebootDuration OID time, and then perform a delayedOn command.
What is pduOutletSwitchedControlCommand?
Reads back the outlet's current state (immediateOff(1), immediateOn(2), or outletUnknown(7)) and, when set, issues a power command: immediateOn/Off switch the outlet right away, delayedOn/Off apply after the configured power-on/off time, and immediateReboot/delayedReboot cycle it off then back on after pduOutletSwitchedConfigRebootDuration. An admin sets this to immediateReboot(5) to remotely power-cycle a hung server without walking to the rack.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.38446.1.5.5.1.4 snmpwalk -v2c -c public <target> ENLOGIC-PDU-MIB::pduOutletSwitchedControlCommand
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.38446.1.5.5.1.4.1 snmpget -v2c -c public <target> ENLOGIC-PDU-MIB::pduOutletSwitchedControlCommand.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.38446.1.5.5.1.4.1 i <value>
Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ENLOGIC-PDU-MIB::pduOutletSwitchedControlCommand OID value, configure state conditions and alerts, and monitor any Enlogic intelligent Power Distribution Unit (PDU) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.38446 | enlogic | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1 | pdu | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.5 | pduOutlet | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.5.5 | pduOutletSwitchedControlTable | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.5.5.1 | pduOutletSwitchedControlEntry | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.5.5.1.4 | pduOutletSwitchedControlCommand | ENLOGIC-PDU-MIB |