All MIBs › ENLOGIC-PDU-MIB › pduCircuitBreakerConfigOverloadRestriction
pduCircuitBreakerConfigOverloadRestriction
Module: ENLOGIC-PDU-MIB
OID (symbolic): ENLOGIC-PDU-MIB::pduCircuitBreakerConfigOverloadRestriction
OID (numeric): 1.3.6.1.4.1.38446.1.4.2.1.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: This OID controls the behavior of a Switched PDU Circuit Breaker when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding Circuit Breaker to turn on. Setting this OID to restrictOnUpperWarning (2) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded. Setting this OID to restrictOnUpperCritical (3) will not allow outlets on the corresponding Circuit Breaker to turn on if the pduCircuitBreakerConfigUpperCriticalThreshold OID is exceeded. Models that do not support this feature will respond to this OID with a value of notSupported (4). Attempts to set this OID in these models will fail.
What is pduCircuitBreakerConfigOverloadRestriction?
Controls whether additional outlets behind this breaker may be switched on when it is near overload: alwaysAllowTurnOn(1) never blocks, restrictOnUpperWarning(2) blocks once the breaker's warning current threshold is exceeded, restrictOnUpperCritical(3) blocks only at the critical threshold. Admins set this to prevent operators from remotely turning on an outlet that would trip a breaker that is already heavily loaded.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.38446.1.4.2.1.4 snmpwalk -v2c -c public <target> ENLOGIC-PDU-MIB::pduCircuitBreakerConfigOverloadRestriction
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.38446.1.4.2.1.4.1 snmpget -v2c -c public <target> ENLOGIC-PDU-MIB::pduCircuitBreakerConfigOverloadRestriction.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.38446.1.4.2.1.4.1 i <value>
Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ENLOGIC-PDU-MIB::pduCircuitBreakerConfigOverloadRestriction OID value, configure state conditions and alerts, and monitor any Enlogic intelligent Power Distribution Unit (PDU) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.38446 | enlogic | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1 | pdu | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.4 | pduCircuitBreaker | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.4.2 | pduCircuitBreakerConfigTable | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.4.2.1 | pduCircuitBreakerConfigEntry | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.4.2.1.4 | pduCircuitBreakerConfigOverloadRestriction | ENLOGIC-PDU-MIB |