All MIBs › ENLOGIC-PDU-MIB › pduExternalSensorStatusState
pduExternalSensorStatusState
Module: ENLOGIC-PDU-MIB
OID (symbolic): ENLOGIC-PDU-MIB::pduExternalSensorStatusState
OID (numeric): 1.3.6.1.4.1.38446.1.6.4.1.5
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: This OID reports the current state of the sensor. A notPresent (0) response indicates that no sensor is attached. An alarmed (1) response indicates that the sensor is present and its measured reading indicates alarmed. A normal (2) response indicates that the sensor is present and its measured reading lies within all thresholds. A belowLowerCritical (3) response indicates that the sensor is present and its measured reading lies below the lower critical threshold. A belowLowerWarning (4) response indicates that the sensor is present and its measured reading lies below the lower warning threshold. An aboveUpperWarning (5) response indicates that the sensor is present and its measured reading lies above the upper warning threshold. An aboveUpperCritical (6) response indicates that the sensor is present and its measured reading lies above the upper critical threshold.
What is pduExternalSensorStatusState?
The sensor's current alarm state: notPresent(0), alarmed(1), normal(2), belowLowerCritical(3), belowLowerWarning(4), aboveUpperWarning(5), or aboveUpperCritical(6). This single field is what most monitoring dashboards poll to decide whether a given environmental sensor needs attention right now.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.38446.1.6.4.1.5 snmpwalk -v2c -c public <target> ENLOGIC-PDU-MIB::pduExternalSensorStatusState
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.38446.1.6.4.1.5.1 snmpget -v2c -c public <target> ENLOGIC-PDU-MIB::pduExternalSensorStatusState.1
Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ENLOGIC-PDU-MIB::pduExternalSensorStatusState OID value, configure state conditions and alerts, and monitor any Enlogic intelligent Power Distribution Unit (PDU) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.38446 | enlogic | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1 | pdu | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.6 | pduExternalSensor | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.6.4 | pduExternalSensorStatusTable | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.6.4.1 | pduExternalSensorStatusEntry | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.6.4.1.5 | pduExternalSensorStatusState | ENLOGIC-PDU-MIB |