All MIBs › ENLOGIC-PDU-MIB › pduUnitPropertiesOutletLayout
pduUnitPropertiesOutletLayout
Module: ENLOGIC-PDU-MIB
OID (symbolic): ENLOGIC-PDU-MIB::pduUnitPropertiesOutletLayout
OID (numeric): 1.3.6.1.4.1.38446.1.2.3.1.15
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The outlet layout for the PDU. Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseToPhase(2) indicates outlet layout as follows: 1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,... seqPhToNeu21PhToPh(3) indicates outlet layout as follows: 1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,... seqPhToPhGrouped(4) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1. seqPhToNGrouped(5) indicates outlet layout as follows: This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N. seqPToN1516PToPGrouped(6) indicates outlet layout as follows: This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2, Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1. seqPhToPh2xGrouped(7) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3, Group 4:2-3, Group 5:3-1, Group 6:3-1. seqPhToN2xGrouped(8) indicates outlet layout as follows: This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N, Group 4:2-N, Group 5:3-N, Group 6:3-N. seqNotApplicable(9):
What is pduUnitPropertiesOutletLayout?
Describes how the PDU's numbered outlets map to phases or phase-pairs, selecting one of nine documented wiring patterns (e.g. seqPhaseToNeutral(1) numbers outlets 1,2,3 across phases 1-N,2-N,3-N in rotation). Admins read it to correctly interpret per-outlet phase balancing when deciding where to plug in new equipment.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.38446.1.2.3.1.15 snmpwalk -v2c -c public <target> ENLOGIC-PDU-MIB::pduUnitPropertiesOutletLayout
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.38446.1.2.3.1.15.1 snmpget -v2c -c public <target> ENLOGIC-PDU-MIB::pduUnitPropertiesOutletLayout.1
Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ENLOGIC-PDU-MIB::pduUnitPropertiesOutletLayout OID value, configure state conditions and alerts, and monitor any Enlogic intelligent Power Distribution Unit (PDU) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.38446 | enlogic | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1 | pdu | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.2 | pduUnit | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.2.3 | pduUnitPropertiesTable | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.2.3.1 | pduUnitPropertiesEntry | ENLOGIC-PDU-MIB |
| 1.3.6.1.4.1.38446.1.2.3.1.15 | pduUnitPropertiesOutletLayout | ENLOGIC-PDU-MIB |