ENLOGIC-PDU-MIB :: pduOutletSwitchedConfigPowerOnTime

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › ENLOGIC-PDU-MIB › pduOutletSwitchedConfigPowerOnTime

pduOutletSwitchedConfigPowerOnTime

Module: ENLOGIC-PDU-MIB

OID (symbolic): ENLOGIC-PDU-MIB::pduOutletSwitchedConfigPowerOnTime

OID (numeric): 1.3.6.1.4.1.38446.1.5.2.1.4

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: The amount of delay, in seconds, between when power is provided to outlets the outlet and when this outlet starts providing power

What is pduOutletSwitchedConfigPowerOnTime?

The delay, in seconds, this outlet waits after power is restored before it actually turns on. Admins stagger pduOutletSwitchedConfigPowerOnTime values across outlets, e.g. 5s, 10s, 15s, to avoid a simultaneous inrush-current surge when recovering from an outage.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.38446.1.5.2.1.4
snmpwalk -v2c -c public <target> ENLOGIC-PDU-MIB::pduOutletSwitchedConfigPowerOnTime

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.38446.1.5.2.1.4.1
snmpget -v2c -c public <target> ENLOGIC-PDU-MIB::pduOutletSwitchedConfigPowerOnTime.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.38446.1.5.2.1.4.1 i <value>

Start monitoring Enlogic intelligent Power Distribution Unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ENLOGIC-PDU-MIB::pduOutletSwitchedConfigPowerOnTime OID value, configure state conditions and alerts, and monitor any Enlogic intelligent Power Distribution Unit (PDU) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.38446enlogicENLOGIC-PDU-MIB
1.3.6.1.4.1.38446.1pduENLOGIC-PDU-MIB
1.3.6.1.4.1.38446.1.5pduOutletENLOGIC-PDU-MIB
1.3.6.1.4.1.38446.1.5.2pduOutletSwitchedConfigTableENLOGIC-PDU-MIB
1.3.6.1.4.1.38446.1.5.2.1pduOutletSwitchedConfigEntryENLOGIC-PDU-MIB
1.3.6.1.4.1.38446.1.5.2.1.4pduOutletSwitchedConfigPowerOnTimeENLOGIC-PDU-MIB