EATON-EPDU-MIB :: inputCurrentThUpperWarning

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › EATON-EPDU-MIB › inputCurrentThUpperWarning

inputCurrentThUpperWarning

Module: EATON-EPDU-MIB

OID (symbolic): EATON-EPDU-MIB::inputCurrentThUpperWarning

OID (numeric): 1.3.6.1.4.1.534.6.6.7.3.3.1.8

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Upper warning threshold. Units are milliamps. A negative value indicates that this object is not available.

What is inputCurrentThUpperWarning?

Read-write threshold in milliamps (-1 to 100000) above which input current triggers a high-warning condition; negative means unavailable. Admins set this below the breaker's rated capacity so they get an early alert before a circuit trips from overload.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.3.3.1.8
snmpwalk -v2c -c public <target> EATON-EPDU-MIB::inputCurrentThUpperWarning

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.3.3.1.8.1
snmpget -v2c -c public <target> EATON-EPDU-MIB::inputCurrentThUpperWarning.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.534.6.6.7.3.3.1.8.1 i <value>

Start monitoring Eaton ePDU rack power distribution unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-MIB::inputCurrentThUpperWarning OID value, configure state conditions and alerts, and monitor any Eaton ePDU rack power distribution unit from a single console.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.6productsEATON-OIDS
1.3.6.1.4.1.534.6.6pduAgentEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.6.6.7eatonEpduEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.3inputsEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.3.3inputCurrentTableEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.3.3.1inputCurrentEntryEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.3.3.1.8inputCurrentThUpperWarningEATON-EPDU-MIB