All MIBs › EATON-EPDU-MIB › inputTotalVA
inputTotalVA
Module: EATON-EPDU-MIB
OID (symbolic): EATON-EPDU-MIB::inputTotalVA
OID (numeric): 1.3.6.1.4.1.534.6.6.7.3.5.1.3
Node type: OBJECT-TYPE
Type: Integer32
Access: read-only
Description: An input VA value. Units are VA. A negative value indicates that this object is not available.
What is inputTotalVA?
Read-only integer giving the combined apparent power (VA) across all phases/legs of this input; a negative value means unavailable. Admins use this total, rather than the per-phase inputVA, to see the overall load on the whole input feed.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.3.5.1.3 snmpwalk -v2c -c public <target> EATON-EPDU-MIB::inputTotalVA
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.3.5.1.3.1 snmpget -v2c -c public <target> EATON-EPDU-MIB::inputTotalVA.1
Start monitoring Eaton ePDU rack power distribution unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-MIB::inputTotalVA OID value, configure state conditions and alerts, and monitor any Eaton ePDU rack power distribution unit from a single console.
OID Breakdown
Upper-level ancestors (9 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.534 | eaton | EATON-OIDS |
| 1.3.6.1.4.1.534.6 | products | EATON-OIDS |
| 1.3.6.1.4.1.534.6.6 | pduAgent | EATON-OIDS |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.534.6.6.7 | eatonEpdu | EATON-EPDU-MIB |
| 1.3.6.1.4.1.534.6.6.7.3 | inputs | EATON-EPDU-MIB |
| 1.3.6.1.4.1.534.6.6.7.3.5 | inputTotalPowerTable | EATON-EPDU-MIB |
| 1.3.6.1.4.1.534.6.6.7.3.5.1 | inputTotalPowerEntry | EATON-EPDU-MIB |
| 1.3.6.1.4.1.534.6.6.7.3.5.1.3 | inputTotalVA | EATON-EPDU-MIB |