EATON-EPDU-MIB :: groupVoltage

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › EATON-EPDU-MIB › groupVoltage

groupVoltage

Module: EATON-EPDU-MIB

OID (symbolic): EATON-EPDU-MIB::groupVoltage

OID (numeric): 1.3.6.1.4.1.534.6.6.7.5.3.1.3

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: Units are millivolts.

What is groupVoltage?

Read-only integer giving this group's measured voltage in millivolts. Admins divide by 1000 to get volts when reading this alongside groupVoltageMeasType to know which phase/leg it represents.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.5.3.1.3
snmpwalk -v2c -c public <target> EATON-EPDU-MIB::groupVoltage

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.6.6.7.5.3.1.3.1
snmpget -v2c -c public <target> EATON-EPDU-MIB::groupVoltage.1

Start monitoring Eaton ePDU rack power distribution unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-MIB::groupVoltage OID value, configure state conditions and alerts, and monitor any Eaton ePDU rack power distribution unit from a single console.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.6productsEATON-OIDS
1.3.6.1.4.1.534.6.6pduAgentEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.6.6.7eatonEpduEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.5groupsEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.5.3groupVoltageTableEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.5.3.1groupVoltageEntryEATON-EPDU-MIB
1.3.6.1.4.1.534.6.6.7.5.3.1.3groupVoltageEATON-EPDU-MIB