All MIBs › LIEBERT-SITENET-INTEGRATOR-MIB
Category: Domain: Environmental Monitoring, Domain: Power/UPS, Vendor: Liebert
Description: Defines objects for the Liebert SiteNet Integrator network management system for centralized monitoring of data center power and cooling.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is LIEBERT-SITENET-INTEGRATOR-MIB?
LIEBERT-SITENET-INTEGRATOR-MIB is a Liebert (Emerson/Vertiv) vendor-specific MIB that models the environmental monitoring capabilities of the SiteNet Integrator agent, a data-center facility monitoring product distinct from Liebert's separate UPS MIB branch. It exposes identification objects (envIdentManufacturer, envIdentModel, envIdentSoftwareVersion), digital input sensor state and polarity (envDigInput1State through envDigInput8, each with a Label and TrapEnabled flag), controllable relay outputs (envRelays), audible/receptacle outputs, alarm state (envAlarms), and dedicated temperature (envTemperatureSensors) and humidity (envHumiditySensors) sensor branches. This makes it useful for monitoring physical facility conditions around IT equipment — open doors, water leak detectors, smoke sensors, or generic dry-contact alarms wired into the digital inputs, plus ambient temperature and humidity trending in the data center or equipment room. It depends on the physical Liebert SiteNet Integrator hardware unit being cabled to the site's sensors and relays, and is typically deployed alongside Liebert UPS monitoring in the same facility. Administrators can download the LIEBERT-SITENET-INTEGRATOR-MIB file to load it into their MIB browser for SNMP monitoring of these facility sensors.
IPNetwork Monitor allows you to monitor SNMP objects defined in LIEBERT-SITENET-INTEGRATOR-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Liebert (Emerson/Vertiv) SiteNet Integrator environmental monitoring unit
Monitoring Examples
An operator polls envDigInput1State through envDigInput8State to confirm all door/leak/smoke contact sensors read normal, and checks envTemperatureSensors and envHumiditySensors for out-of-range readings; a digital input flipping to its alarm state combined with envDigInput#TrapEnabled being true would trigger a notification indicating a physical facility fault such as a water leak or open cabinet door.
What Can Be Monitored
- digital input sensor state and polarity
- relay output control state
- audible alarm/receptacle output state
- temperature sensor readings
- humidity sensor readings
- environmental alarm status
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Counter | |
| enterprises |
From RFC1213-MIB
| DisplayString |
From RFC1253-MIB
| TruthValue |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| emerson | 1.3.6.1.4.1.476 | |||
| liebertCorp | 1.3.6.1.4.1.476.1 | |||
| liebertUps | 1.3.6.1.4.1.476.1.1 | |||
| liebertEnvironment | 1.3.6.1.4.1.476.1.2 | |||
| leExtensions | 1.3.6.1.4.1.476.1.2.1 | |||
| leSiteNet01 | 1.3.6.1.4.1.476.1.2.1.1 | |||
| envMIB | 1.3.6.1.4.1.476.1.2.1.1.1 | |||
| envIdent | 1.3.6.1.4.1.476.1.2.1.1.1.1 | |||
| STR envIdentManufacturer | 1.3.6.1.4.1.476.1.2.1.1.1.1.1 | DisplayString | read-only | The Environmental Control Unit manufacturer. |
| STR envIdentModel | 1.3.6.1.4.1.476.1.2.1.1.1.1.2 | DisplayString | read-write | The Environmental Control Unit Model designation. |
| STR envIdentSoftwareVersion | 1.3.6.1.4.1.476.1.2.1.1.1.1.3 | DisplayString | read-only | The Environmental SNMP Agent software version. |
| OID envIdentSpecific | 1.3.6.1.4.1.476.1.2.1.1.1.1.4 | OBJECT IDENTIFIER | read-only | A reference to MIB definitions specific to the particular Environmental Unit being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value. |
| envDigitalInputs | 1.3.6.1.4.1.476.1.2.1.1.1.2 | |||
| envDigInput1 | 1.3.6.1.4.1.476.1.2.1.1.1.2.1 | |||
| INT envDigInput1State | 1.3.6.1.4.1.476.1.2.1.1.1.2.1.1 | INTEGER | read-only | The state of Digital Input Number 1. When the envDigInput1Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput1Polarity is set to activeHigh(1) and the input on Digital Input Number 1 is asserted, this variable returns true(1). When the envDigInput1Polarity is set to activeLow(2) and the input on Digital Input 1 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput1Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.1.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 1. The text string is stored in non-volatile memory. |
| INT envDigInput1Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.1.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 1. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 1 is being deasserted and return true(1) if Digital Input Number 1 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 1 is being asserted and return true(1) if Digital Input Number 1 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput1TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.1.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 1. When envDigInput1TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput1TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput2 | 1.3.6.1.4.1.476.1.2.1.1.1.2.2 | |||
| INT envDigInput2State | 1.3.6.1.4.1.476.1.2.1.1.1.2.2.1 | INTEGER | read-only | The state of Digital Input Number 2. When the envDigInput2Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput2Polarity is set to activeHigh(1) and the input on Digital Input Number 2 is asserted, this variable returns true(1). When the envDigInput2Polarity is set to activeLow(2) and the input on Digital Input 2 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput2Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.2.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 2. The text string is stored in non-volatile memory. |
| INT envDigInput2Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.2.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 2. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 2 is being deasserted and return true(1) if Digital Input Number 2 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 2 is being asserted and return true(1) if Digital Input Number 2 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput2TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.2.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 2. When envDigInput2TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput2TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput3 | 1.3.6.1.4.1.476.1.2.1.1.1.2.3 | |||
| INT envDigInput3State | 1.3.6.1.4.1.476.1.2.1.1.1.2.3.1 | INTEGER | read-only | The state of Digital Input Number 3. When the envDigInput3Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput3Polarity is set to activeHigh(1) and the input on Digital Input Number 3 is asserted, this variable returns true(1). When the envDigInput3Polarity is set to activeLow(2) and the input on Digital Input 3 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput3Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.3.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 3. The text string is stored in non-volatile memory. |
| INT envDigInput3Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.3.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 3. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 3 is being deasserted and return true(1) if Digital Input Number 3 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 3 is being asserted and return true(1) if Digital Input Number 3 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput3TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.3.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 3. When envDigInput3TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput3TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput4 | 1.3.6.1.4.1.476.1.2.1.1.1.2.4 | |||
| INT envDigInput4State | 1.3.6.1.4.1.476.1.2.1.1.1.2.4.1 | INTEGER | read-only | The state of Digital Input Number 4. When the envDigInput4Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput4Polarity is set to activeHigh(1) and the input on Digital Input Number 4 is asserted, this variable returns true(1). When the envDigInput4Polarity is set to activeLow(2) and the input on Digital Input 4 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput4Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.4.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 4. The text string is stored in non-volatile memory. |
| INT envDigInput4Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.4.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 4. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 4 is being deasserted and return true(1) if Digital Input Number 4 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 4 is being asserted and return true(1) if Digital Input Number 4 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput4TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.4.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 4. When envDigInput4TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput4TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput5 | 1.3.6.1.4.1.476.1.2.1.1.1.2.5 | |||
| INT envDigInput5State | 1.3.6.1.4.1.476.1.2.1.1.1.2.5.1 | INTEGER | read-only | The state of Digital Input Number 5. When the envDigInput5Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput5Polarity is set to activeHigh(1) and the input on Digital Input Number 5 is asserted, this variable returns true(1). When the envDigInput5Polarity is set to activeLow(2) and the input on Digital Input 5 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput5Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.5.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 5. The text string is stored in non-volatile memory. |
| INT envDigInput5Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.5.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 5. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 5 is being deasserted and return true(1) if Digital Input Number 5 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 5 is being asserted and return true(1) if Digital Input Number 5 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput5TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.5.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 5. When envDigInput5TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput5TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput6 | 1.3.6.1.4.1.476.1.2.1.1.1.2.6 | |||
| INT envDigInput6State | 1.3.6.1.4.1.476.1.2.1.1.1.2.6.1 | INTEGER | read-only | The state of Digital Input Number 6. When the envDigInput6Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput6Polarity is set to activeHigh(1) and the input on Digital Input Number 6 is asserted, this variable returns true(1). When the envDigInput6Polarity is set to activeLow(2) and the input on Digital Input 6 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput6Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.6.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 6. The text string is stored in non-volatile memory. |
| INT envDigInput6Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.6.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 6. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 6 is being deasserted and return true(1) if Digital Input Number 6 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 6 is being asserted and return true(1) if Digital Input Number 6 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput6TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.6.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 6. When envDigInput6TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput6TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput7 | 1.3.6.1.4.1.476.1.2.1.1.1.2.7 | |||
| INT envDigInput7State | 1.3.6.1.4.1.476.1.2.1.1.1.2.7.1 | INTEGER | read-only | The state of Digital Input Number 7. When the envDigInput7Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput7Polarity is set to activeHigh(1) and the input on Digital Input Number 7 is asserted, this variable returns true(1). When the envDigInput7Polarity is set to activeLow(2) and the input on Digital Input 7 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput7Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.7.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 7. The text string is stored in non-volatile memory. |
| INT envDigInput7Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.7.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 7. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 7 is being deasserted and return true(1) if Digital Input Number 7 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 7 is being asserted and return true(1) if Digital Input Number 7 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput7TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.7.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 7. When envDigInput7TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput7TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput8 | 1.3.6.1.4.1.476.1.2.1.1.1.2.8 | |||
| INT envDigInput8State | 1.3.6.1.4.1.476.1.2.1.1.1.2.8.1 | INTEGER | read-only | The state of Digital Input Number 8. When the envDigInput8Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput8Polarity is set to activeHigh(1) and the input on Digital Input Number 8 is asserted, this variable returns true(1). When the envDigInput8Polarity is set to activeLow(2) and the input on Digital Input 8 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput8Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.8.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 8. The text string is stored in non-volatile memory. |
| INT envDigInput8Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.8.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 8. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 8 is being deasserted and return true(1) if Digital Input Number 8 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 8 is being asserted and return true(1) if Digital Input Number 8 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput8TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.8.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 8. When envDigInput8TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput8TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput9 | 1.3.6.1.4.1.476.1.2.1.1.1.2.9 | |||
| INT envDigInput9State | 1.3.6.1.4.1.476.1.2.1.1.1.2.9.1 | INTEGER | read-only | The state of Digital Input Number 9. When the envDigInput9Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput9Polarity is set to activeHigh(1) and the input on Digital Input Number 9 is asserted, this variable returns true(1). When the envDigInput9Polarity is set to activeLow(2) and the input on Digital Input 9 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput9Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.9.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 9. The text string is stored in non-volatile memory. |
| INT envDigInput9Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.9.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 9. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 9 is being deasserted and return true(1) if Digital Input Number 9 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 9 is being asserted and return true(1) if Digital Input Number 9 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput9TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.9.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 9. When envDigInput9TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput9TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envDigInput10 | 1.3.6.1.4.1.476.1.2.1.1.1.2.10 | |||
| INT envDigInput10State | 1.3.6.1.4.1.476.1.2.1.1.1.2.10.1 | INTEGER | read-only | The state of Digital Input Number 10. When the envDigInput10Polarity is set to notDefined(3) this variable returns notInstalled(3). When the envDigInput10Polarity is set to activeHigh(1) and the input on Digital Input Number 10 is asserted, this variable returns true(1). When the envDigInput10Polarity is set to activeLow(2) and the input on Digital Input 10 is deasserted, this variable returns true(1). In all other cases, this variable returns false(2). |
| STR envDigInput10Label | 1.3.6.1.4.1.476.1.2.1.1.1.2.10.2 | DisplayString | read-write | A user-defined text string associated with Digital Input Number 10. The text string is stored in non-volatile memory. |
| INT envDigInput10Polarity | 1.3.6.1.4.1.476.1.2.1.1.1.2.10.3 | INTEGER | read-write | The Polarity to be associated with the State variable for Digital Input Number 10. It controls the value returned by the State variable. When Polarity is set to notDefined(3), State will return notInstalled(3). When Polarity is set to activeHigh(1), State will return false(2) if Digital Input Number 10 is being deasserted and return true(1) if Digital Input Number 10 is being asserted. When Polarity is set to activeLow(2), State will return false(2) if Digital Input Number 10 is being asserted and return true(1) if Digital Input Number 10 is being deasserted. Polarity is stored in non-volatile memory. |
| T/F envDigInput10TrapEnabled | 1.3.6.1.4.1.476.1.2.1.1.1.2.10.4 | TruthValue | read-write | A TRAP may be associated with the State variable for Digital Input Number 10. When envDigInput10TrapEnabled is set to true(1), a TRAP message will be generated when State is true(1). When envDigInput10TrapEnabled is set to false(2), a TRAP message will not be generated regardless of the value of State. TrapEnabled is stored in non-volatile memory. |
| envRelays | 1.3.6.1.4.1.476.1.2.1.1.1.3 | |||
| envRelay1 | 1.3.6.1.4.1.476.1.2.1.1.1.3.1 | |||
| INT envRelay1State | 1.3.6.1.4.1.476.1.2.1.1.1.3.1.1 | INTEGER | read-write | The state of Output Relay Number 1. When State is set to on(1) Output Relay Number 1 is activated and the normally open contacts are closed. When State is set to off(2) Output Relay Number 1 is deactivated and the normally closed contacts are closed. |
| STR envRelay1Label | 1.3.6.1.4.1.476.1.2.1.1.1.3.1.2 | DisplayString | read-write | A user-defined text string associated with Output Relay Number 1. The text string is stored in non-volatile memory. |
| INT envRelay1Control | 1.3.6.1.4.1.476.1.2.1.1.1.3.1.3 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envRelay2 | 1.3.6.1.4.1.476.1.2.1.1.1.3.2 | |||
| INT envRelay2State | 1.3.6.1.4.1.476.1.2.1.1.1.3.2.1 | INTEGER | read-write | The state of Output Relay Number 2. When State is set to on(1) Output Relay Number 2 is activated and the normally open contacts are closed. When State is set to off(2) Output Relay Number 2 is deactivated and the normally closed contacts are closed. |
| STR envRelay2Label | 1.3.6.1.4.1.476.1.2.1.1.1.3.2.2 | DisplayString | read-write | A user-defined text string associated with Output Relay Number 2. The text string is stored in non-volatile memory. |
| INT envRelay2Control | 1.3.6.1.4.1.476.1.2.1.1.1.3.2.3 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envOutputs | 1.3.6.1.4.1.476.1.2.1.1.1.4 | |||
| envAudible | 1.3.6.1.4.1.476.1.2.1.1.1.4.1 | |||
| INT envAudibleState | 1.3.6.1.4.1.476.1.2.1.1.1.4.1.1 | INTEGER | read-write | The state of the Audible Output. When State is set to on(1) the Audible will be sounded. When State is set to off(2) the Audible is muted. |
| INT envAudibleControl | 1.3.6.1.4.1.476.1.2.1.1.1.4.1.2 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envLED1 | 1.3.6.1.4.1.476.1.2.1.1.1.4.2 | |||
| INT envLED1State | 1.3.6.1.4.1.476.1.2.1.1.1.4.2.1 | INTEGER | read-write | The state of Output LED Number 1. When State is set to on(1) LED Number 1 will be lighted. When State is set to off(2) LED Number 1 will not be lighted. |
| STR envLED1Label | 1.3.6.1.4.1.476.1.2.1.1.1.4.2.2 | DisplayString | read-write | A user-defined text string associated with Output LED Number 1. The text string is stored in non-volatile memory. |
| INT envLED1Control | 1.3.6.1.4.1.476.1.2.1.1.1.4.2.3 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envLED2 | 1.3.6.1.4.1.476.1.2.1.1.1.4.3 | |||
| INT envLED2State | 1.3.6.1.4.1.476.1.2.1.1.1.4.3.1 | INTEGER | read-write | The state of Output LED Number 2. When State is set to on(1) LED Number 2 will be lighted. When State is set to off(2) LED Number 2 will not be lighted. |
| STR envLED2Label | 1.3.6.1.4.1.476.1.2.1.1.1.4.3.2 | DisplayString | read-write | A user-defined text string associated with Output LED Number 2. The text string is stored in non-volatile memory. |
| INT envLED2Control | 1.3.6.1.4.1.476.1.2.1.1.1.4.3.3 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envLED3 | 1.3.6.1.4.1.476.1.2.1.1.1.4.4 | |||
| INT envLED3State | 1.3.6.1.4.1.476.1.2.1.1.1.4.4.1 | INTEGER | read-write | The state of Output LED Number 3. When State is set to on(1) LED Number 3 will be lighted. When State is set to off(2) LED Number 3 will not be lighted. |
| STR envLED3Label | 1.3.6.1.4.1.476.1.2.1.1.1.4.4.2 | DisplayString | read-write | A user-defined text string associated with Output LED Number 3. The text string is stored in non-volatile memory. |
| INT envLED3Control | 1.3.6.1.4.1.476.1.2.1.1.1.4.4.3 | INTEGER | read-write | If Control value is 0 then this output may be directly controlled by the SNMP Manager. When Control contains any of the following values, or a value resulting from the sum of any of these values the Agent will activate the output when the any of the associated conditions is sensed and de-activate the output when all conditions clear. DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 The Control variable is stored in non-volatile memory. |
| envReceptacles | 1.3.6.1.4.1.476.1.2.1.1.1.5 | |||
| envReceptacle1 | 1.3.6.1.4.1.476.1.2.1.1.1.5.1 | |||
| INT envReceptacle1State | 1.3.6.1.4.1.476.1.2.1.1.1.5.1.1 | INTEGER | read-write | The state of the Receptacle Number 1. When State is set to on(1) power will be live on Receptacle Number 1. When State is set to off(2) no power is available from Receptacle Number 1. |
| STR envReceptacle1Label | 1.3.6.1.4.1.476.1.2.1.1.1.5.1.2 | DisplayString | read-write | A user-defined text string associated with Receptacle Number 1. The text string is stored in non-volatile memory. |
| envReceptacle2 | 1.3.6.1.4.1.476.1.2.1.1.1.5.2 | |||
| INT envReceptacle2State | 1.3.6.1.4.1.476.1.2.1.1.1.5.2.1 | INTEGER | read-write | The state of the Receptacle Number 2. When State is set to on(1) power will be live on Receptacle Number 2. When State is set to off(2) no power is available from Receptacle Number 2. |
| STR envReceptacle2Label | 1.3.6.1.4.1.476.1.2.1.1.1.5.2.2 | DisplayString | read-write | A user-defined text string associated with Receptacle Number 2. The text string is stored in non-volatile memory. |
| envReceptacle3 | 1.3.6.1.4.1.476.1.2.1.1.1.5.3 | |||
| INT envReceptacle3State | 1.3.6.1.4.1.476.1.2.1.1.1.5.3.1 | INTEGER | read-write | The state of the Receptacle Number 3. When State is set to on(1) power will be live on Receptacle Number 3. When State is set to off(2) no power is available from Receptacle Number 3. |
| STR envReceptacle3Label | 1.3.6.1.4.1.476.1.2.1.1.1.5.3.2 | DisplayString | read-write | A user-defined text string associated with Receptacle Number 3. The text string is stored in non-volatile memory. |
| envReceptacle4 | 1.3.6.1.4.1.476.1.2.1.1.1.5.4 | |||
| INT envReceptacle4State | 1.3.6.1.4.1.476.1.2.1.1.1.5.4.1 | INTEGER | read-write | The state of the Receptacle Number 4. When State is set to on(1) power will be live on Receptacle Number 4. When State is set to off(2) no power is available from Receptacle Number 4. |
| STR envReceptacle4Label | 1.3.6.1.4.1.476.1.2.1.1.1.5.4.2 | DisplayString | read-write | A user-defined text string associated with Receptacle Number 4. The text string is stored in non-volatile memory. |
| envAlarms | 1.3.6.1.4.1.476.1.2.1.1.1.6 | |||
| INT envSummaryAlarm | 1.3.6.1.4.1.476.1.2.1.1.1.6.1 | INTEGER | read-only | The envSummaryAlarm varible will be 0 when no Digital Inputs are true and no other alarm conditions exist. When alarms are active or Digital Inputs are true the value of envSummaryAlarm indicates which alarms and inputs are active as a sum of the values listed below: DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288 |
| envTemperatureSensors | 1.3.6.1.4.1.476.1.2.1.1.1.7 | |||
| envTemperature1 | 1.3.6.1.4.1.476.1.2.1.1.1.7.1 | |||
| INT envTemperature1State | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.1 | INTEGER | read-write | The state of use of Temperature Input Number 1. When a sensor is connected to Temperature Input 1 set State to installed(2) to indicate that the value of envTemperature1F and envTemperature1C are valid. When no sensor is connected to Temperature Input 1 set State to notInstalled(1) to indicate that the value of envTemperature1F and envTemperature1C may not be valid. This variable is stored in non-volatile memory. |
| INT envTemperature1F | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.2 | INTEGER | read-only | The temperature for sensor 1 in degrees Fahrenheit. |
| INT envTemperature1C | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.3 | INTEGER | read-only | The temperature for sensor 1 in degrees Centigrade. |
| STR envTemperature1Label | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.4 | DisplayString | read-write | A user-defined text string associated with Temperature Input Number 1. The text string is stored in non-volatile memory. |
| INT envTemperature1OffsetF | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.5 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature1F variable. The value of OffsetF is added to the value from Temperature Sensor Number 1 to obtain the value of the envTemperature1F variable. When this variable is changed the envTemperature1OffsetC variable may also be effected. The OffsetF variable is stored in non-volatile memory. |
| INT envTemperature1OffsetC | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.6 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature1C variable. The value of OffsetC is added to the value from Temperature Sensor Number 1 to obtain the value of the envTemperature1C variable. When this variable is changed the envTemperature1OffsetF variable may also be effected. The OffsetC variable is stored in in non-volatile memory. |
| INT envTemp1HighLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.7 | INTEGER | read-write | When envTemperature1F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 1. The HighLimitF variable is stored in non-volatile memory. |
| INT envTemp1HighLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.8 | INTEGER | read-write | When envTemperature1C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 1. The HighLimitC variable is stored in non-volatile memory. |
| INT envTemp1LowLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.9 | INTEGER | read-write | When envTemperature1F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 1. The LowLimitF variable is stored in non-volatile memory. |
| INT envTemp1LowLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.1.10 | INTEGER | read-write | When envTemperature1C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 1. The LowLimitC variable is stored in non-volatile memory. |
| envTemperature2 | 1.3.6.1.4.1.476.1.2.1.1.1.7.2 | |||
| INT envTemperature2State | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.1 | INTEGER | read-write | The state of use of Temperature Input Number 2. When a sensor is connected to Temperature Input 2 set State to installed(2) to indicate that the value of envTemperature2F and envTemperature2C are valid. When no sensor is connected to Temperature Input 2 set State to notInstalled(1) to indicate that the value of envTemperature2F and envTemperature2C may not be valid. This variable is stored in non-volatile memory. |
| INT envTemperature2F | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.2 | INTEGER | read-only | The temperature for sensor 2 in degrees Fahrenheit. |
| INT envTemperature2C | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.3 | INTEGER | read-only | The temperature for sensor 2 in degrees Centigrade. |
| STR envTemperature2Label | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.4 | DisplayString | read-write | A user-defined text string associated with Temperature Input Number 2. The text string is stored in non-volatile memory. |
| INT envTemperature2OffsetF | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.5 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature2F variable. The value of OffsetF is added to the value from Temperature Sensor Number 2 to obtain the value of the envTemperature2F variable. When this variable is changed the envTemperature2OffsetC variable may also be effected. The OffsetF variable is stored in non-volatile memory. |
| INT envTemperature2OffsetC | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.6 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature2C variable. The value of OffsetC is added to the value from Temperature Sensor Number 2 to obtain the value of the envTemperature2C variable. When this variable is changed the envTemperature2OffsetF variable may also be effected. The OffsetC variable is stored in in non-volatile memory. |
| INT envTemp2HighLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.7 | INTEGER | read-write | When envTemperature2F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 2. The HighLimitF variable is stored in non-volatile memory. |
| INT envTemp2HighLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.8 | INTEGER | read-write | When envTemperature2C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 2. The HighLimitC variable is stored in non-volatile memory. |
| INT envTemp2LowLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.9 | INTEGER | read-write | When envTemperature2F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 2. The LowLimitF variable is stored in non-volatile memory. |
| INT envTemp2LowLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.2.10 | INTEGER | read-write | When envTemperature2C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 2. The LowLimitC variable is stored in non-volatile memory. |
| envTemperature3 | 1.3.6.1.4.1.476.1.2.1.1.1.7.3 | |||
| INT envTemperature3State | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.1 | INTEGER | read-write | The state of use of Temperature Input Number 3. When a water temperature sensor is connected to Temperature Input 3 set State to waterSensorInstalled(3), when and air temperature sensor is connected set State to airSensorInstalled(2). When no sensor is connected to Temperature Input 3 set State to notInstalled(1) to indicate that the value of envTemperature3F and envTemperature3C may not be valid. This variable is stored in non-volatile memory. |
| INT envTemperature3F | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.2 | INTEGER | read-only | The temperature for sensor 3 in degrees Fahrenheit. |
| INT envTemperature3C | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.3 | INTEGER | read-only | The temperature for sensor 3 in degrees Centigrade. |
| STR envTemperature3Label | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.4 | DisplayString | read-write | A user-defined text string associated with Temperature Input Number 3. The text string is stored in non-volatile memory. |
| INT envTemperature3OffsetF | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.5 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature3F variable. The value of OffsetF is added to the value from Temperature Sensor Number 3 to obtain the value of the envTemperature3F variable. When this variable is changed the envTemperature3OffsetF variable may also be effected. The OffsetF variable is stored in in non-volatile memory. |
| INT envTemperature3OffsetC | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.6 | INTEGER | read-write | A temperature correction Offset associated with the envTemperature3C variable. The value of OffsetC is added to the value from Temperature Sensor Number 3 to obtain the value of the envTemperature3C variable. When this variable is changed the envTemperature3OffsetF variable may also be effected. The OffsetC variable is stored in in non-volatile memory. |
| INT envTemp3HighLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.7 | INTEGER | read-write | When envTemperature3F reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 3. The HighLimitF variable is stored in non-volatile memory. |
| INT envTemp3HighLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.8 | INTEGER | read-write | When envTemperature3C reaches or exceeds this value a trap will be generated signifying a high temperature condition at temperature sensor 3. The HighLimitC variable is stored in non-volatile memory. |
| INT envTemp3LowLimitF | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.9 | INTEGER | read-write | When envTemperature3F reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 3. The LowLimitF variable is stored in non-volatile memory. |
| INT envTemp3LowLimitC | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.10 | INTEGER | read-write | When envTemperature3C reaches or goes below this value a trap will be generated signifying a low temperature condition at temperature sensor 3. The LowLimitC variable is stored in non-volatile memory. |
| INT envTemp3Calibrate | 1.3.6.1.4.1.476.1.2.1.1.1.7.3.11 | INTEGER | read-write | A temperature Offset correction routine associated with Temperature Sensor Number 3. When Calibrate is set to on(1) and State is set to waterSensorInstalled(3) the agent runs a self calibration routine which automatically adjusts the OffsetF and OffsetC variables. |
| envHumiditySensors | 1.3.6.1.4.1.476.1.2.1.1.1.8 | |||
| envHumidity1 | 1.3.6.1.4.1.476.1.2.1.1.1.8.1 | |||
| INT envHumidity1State | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.1 | INTEGER | read-write | The state of use of Humidity Input Number 1. When a sensor is connected to Humidity Input 1 set State to installed(2) to indicate that the value of envHumidity1RH is valid. When no sensor is connected to Humidity Input 1 set State to notInstalled(1) to indicate that the value of envHumidity1RH may not be valid. This variable is stored in non-volatile memory. |
| INT envHumidity1RH | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.2 | INTEGER | read-only | The humidity for sensor 1 in percent RH. |
| STR envHumidity1Label | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.3 | DisplayString | read-write | A user-defined text string associated with Humidity Input Number 1. The text string is stored in non-volatile memory. |
| INT envHumidity1Offset | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.4 | INTEGER | read-write | A humidity correction Offset associated with the envHumidity1RH variable. The value of Offset is added to the value from Humidity Sensor Number 1 to obtain the value of the envHumidity1RH variable. The Offset variable is stored in non-volatile memory. |
| INT envHumidity1HighLimit | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.5 | INTEGER | read-write | When envHumidity1RH reaches or exceeds this value a trap will be generated signifying a high humidity condition at humidity sensor 1. The HighLimit variable is stored in non-volatile memory. |
| INT envHumidity1LowLimit | 1.3.6.1.4.1.476.1.2.1.1.1.8.1.6 | INTEGER | read-write | When envHumidity1RH reaches or goes below this value a trap will be generated signifying a low humidity condition at humidity sensor 1. The LowLimit variable is stored in non-volatile memory. |
| envHumidity2 | 1.3.6.1.4.1.476.1.2.1.1.1.8.2 | |||
| INT envHumidity2State | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.1 | INTEGER | read-write | The state of use of Humidity Input Number 2. When a sensor is connected to Humidity Input 2 set State to installed(2) to indicate that the value of envHumidity2RH is valid. When no sensor is connected to Humidity Input 2 set State to notInstalled(1) to indicate that the value of envHumidity2RH may not be valid. This variable is stored in non-volatile memory. |
| INT envHumidity2RH | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.2 | INTEGER | read-only | The humidity for sensor 2 in percent RH. |
| STR envHumidity2Label | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.3 | DisplayString | read-write | A user-defined text string associated with Humidity Input Number 2. The text string is stored in non-volatile memory. |
| INT envHumidity2Offset | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.4 | INTEGER | read-write | A humidity correction Offset associated with the envHumidity2RH variable. The value of Offset is added to the value from Humidity Sensor Number 2 to obtain the value of the envHumidity2RH variable. The Offset variable is stored in non-volatile memory. |
| INT envHumidity2HighLimit | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.5 | INTEGER | read-write | When envHumidity2RH reaches or exceeds this value a trap will be generated signifying a high humidity condition at humidity sensor 2. The HighLimit variable is stored in non-volatile memory. |
| INT envHumidity2LowLimit | 1.3.6.1.4.1.476.1.2.1.1.1.8.2.6 | INTEGER | read-write | When envHumidity2RH reaches or goes below this value a trap will be generated signifying a low humidity condition at humidity sensor 2. The LowLimit variable is stored in non-volatile memory. |
| envTraps | 1.3.6.1.4.1.476.1.2.1.1.1.11 | |||
| NTF envSummaryAlarmTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.1 | An envSummaryAlarmTrap is generated each time a digital input State variable changes to true(1) or whenever a temperature or humidity goes above the HighLimit or below the LowLimit. | ||
| NTF envDigInput1TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.2 | An envDigInput1TrueTrap signifies that envDigitalInput1State has changed from false(2) to true(1). This trap is not generated if envDigInput1TrapEnabled is not true(1). | ||
| NTF envDigInput1FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.3 | An envDigInput1FalseTrap signifies that envDigitalInput1State has changed from true(1) to false(2). This trap is not generated if envDigInput1TrapEnabled is not true(1). | ||
| NTF envDigInput2TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.4 | An envDigInput2TrueTrap signifies that envDigitalInput2State has changed from false(2) to true(1). This trap is not generated if envDigInput2TrapEnabled is not true(1). | ||
| NTF envDigInput2FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.5 | An envDigInput2FalseTrap signifies that envDigitalInput2State has changed from true(1) to false(2). This trap is not generated if envDigInput2TrapEnabled is not true(1). | ||
| NTF envDigInput3TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.6 | An envDigInput3TrueTrap signifies that envDigitalInput3State has changed from false(2) to true(1). This trap is not generated if envDigInput3TrapEnabled is not true(1). | ||
| NTF envDigInput3FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.7 | An envDigInput3FalseTrap signifies that envDigitalInput3State has changed from true(1) to false(2). This trap is not generated if envDigInput3TrapEnabled is not true(1). | ||
| NTF envDigInput4TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.8 | An envDigInput4TrueTrap signifies that envDigitalInput4State has changed from false(2) to true(1). This trap is not generated if envDigInput4TrapEnabled is not true(1). | ||
| NTF envDigInput4FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.9 | An envDigInput4FalseTrap signifies that envDigitalInput4State has changed from true(1) to false(2). This trap is not generated if envDigInput4TrapEnabled is not true(1). | ||
| NTF envDigInput5TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.10 | An envDigInput5TrueTrap signifies that envDigitalInput5State has changed from false(2) to true(1). This trap is not generated if envDigInput5TrapEnabled is not true(1). | ||
| NTF envDigInput5FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.11 | An envDigInput5FalseTrap signifies that envDigitalInput5State has changed from true(1) to false(2). This trap is not generated if envDigInput5TrapEnabled is not true(1). | ||
| NTF envDigInput6TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.12 | An envDigInput6TrueTrap signifies that envDigitalInput6State has changed from false(2) to true(1). This trap is not generated if envDigInput6TrapEnabled is not true(1). | ||
| NTF envDigInput6FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.13 | An envDigInput6FalseTrap signifies that envDigitalInput6State has changed from true(1) to false(2). This trap is not generated if envDigInput6TrapEnabled is not true(1). | ||
| NTF envDigInput7TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.14 | An envDigInput7TrueTrap signifies that envDigitalInput7State has changed from false(2) to true(1). This trap is not generated if envDigInput7TrapEnabled is not true(1). | ||
| NTF envDigInput7FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.15 | An envDigInput7FalseTrap signifies that envDigitalInput7State has changed from true(1) to false(2). This trap is not generated if envDigInput7TrapEnabled is not true(1). | ||
| NTF envDigInput8TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.16 | An envDigInput8TrueTrap signifies that envDigitalInput8State has changed from false(2) to true(1). This trap is not generated if envDigInput8TrapEnabled is not true(1). | ||
| NTF envDigInput8FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.17 | An envDigInput8FalseTrap signifies that envDigitalInput8State has changed from true(1) to false(2). This trap is not generated if envDigInput8TrapEnabled is not true(1). | ||
| NTF envDigInput9TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.18 | An envDigInput9TrueTrap signifies that envDigitalInput9State has changed from false(2) to true(1). This trap is not generated if envDigInput9TrapEnabled is not true(1). | ||
| NTF envDigInput9FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.19 | An envDigInput9FalseTrap signifies that envDigitalInput9State has changed from true(1) to false(2). This trap is not generated if envDigInput9TrapEnabled is not true(1). | ||
| NTF envDigInput10TrueTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.20 | An envDigInput10TrueTrap signifies that envDigitalInput10State has changed from false(2) to true(1). This trap is not generated if envDigInput10TrapEnabled is not true(1). | ||
| NTF envDigInput10FalseTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.21 | An envDigInput10FalseTrap signifies that envDigitalInput10State has changed from true(1) to false(2). This trap is not generated if envDigInput10TrapEnabled is not true(1). | ||
| NTF envTemperature1HighTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.22 | An envTemperature1HighTrap signifies that the sensor reading has gone above the HighLimit value. | ||
| NTF envTemperature1LowTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.23 | An envTemperature1LowTrap signifies that the sensor reading has gone below the LowLimit value. | ||
| NTF envTemperature1NormalTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.24 | An envTemperature1NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit. | ||
| NTF envTemperature2HighTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.25 | An envTemperature2HighTrap signifies that the sensor reading has gone above the HighLimit value. | ||
| NTF envTemperature2LowTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.26 | An envTemperature2LowTrap signifies that the sensor reading has gone below the LowLimit value. | ||
| NTF envTemperature2NormalTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.27 | An envTemperature2NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit. | ||
| NTF envTemperature3HighTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.28 | An envTemperature3HighTrap signifies that the sensor reading has gone above the HighLimit value. | ||
| NTF envTemperature3LowTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.29 | An envTemperature3LowTrap signifies that the sensor reading has gone below the LowLimit value. | ||
| NTF envTemperature3NormalTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.30 | An envTemperature3NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit. | ||
| NTF envHumidity1HighTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.31 | An envHumidity1HighTrap signifies that the sensor reading has gone above the HighLimit value. | ||
| NTF envHumidity1LowTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.32 | An envHumidity1LowTrap signifies that the sensor reading has gone below the LowLimit value. | ||
| NTF envHumidity1NormalTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.33 | An envHumidity1NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit. | ||
| NTF envHumidity2HighTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.34 | An envHumidity2HighTrap signifies that the sensor reading has gone above the HighLimit value. | ||
| NTF envHumidity2LowTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.35 | An envHumidity2LowTrap signifies that the sensor reading has gone below the LowLimit value. | ||
| NTF envHumidity2NormalTrap | 1.3.6.1.4.1.476.1.2.1.1.1.11.0.36 | An envHumidity2NormalTrap signifies that the sensor reading has return to the range bounded by HighLimit and LowLimit. | ||
| leExperimental | 1.3.6.1.4.1.476.1.2.2 | |||
| lePrivate | 1.3.6.1.4.1.476.1.2.3 |
RFC description
Defines objects for the Liebert SiteNet Integrator SNMP agent managing environmental control units.
Start monitoring Liebert (Emerson/Vertiv) SiteNet Integrator environmental monitoring unit with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.