All MIBs › WebGraph-OLD-Thermo-Hygrometer-US-MIB
Category: Power and Environmental Monitoring
Description: Monitors legacy WebGraph thermo-hygrometer temperature and relative humidity sensor values and alarm thresholds.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is WebGraph-OLD-Thermo-Hygrometer-US-MIB?
This is a proprietary MIB for a legacy WebGraph networked thermo-hygrometer appliance that measures ambient temperature and relative humidity, typically used for server room or rack environmental monitoring. It exposes hardware sensor readings via per-sensor tables covering both raw temperature values and a binary (threshold-crossed) temperature indicator, along with device session/configuration objects like a control password and configuration-mode flag. As an environmental monitoring device, its entire purpose is hardware status monitoring: current temperature and humidity readings and threshold-alarm states directly indicate whether the monitored environment, such as a data closet or equipment cabinet, is within safe operating range. It has no apparent dependency on other standard MIBs, being a small self-contained proprietary schema, and it is explicitly marked "OLD," indicating it is a superseded legacy version of the vendor's current thermo-hygrometer MIB. It is deployed on legacy WebGraph environmental sensor units placed in server rooms, telecom closets, or equipment cabinets for temperature/humidity monitoring. Engineers can download the WebGraph-OLD-Thermo-Hygrometer-US-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in WebGraph-OLD-Thermo-Hygrometer-US-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Wiesemann & Theis (W&T) Web-Thermo-Hygrometer networked environmental sensor
Monitoring Examples
An operator would poll wtWebGraphThermHygroSensorTable/wtWebGraphThermHygroSensorEntry to enumerate configured sensors by wtWebGraphThermHygroSensorNo, then read wtWebGraphThermHygroTempValueTable's wtWebGraphThermHygroTempValue for the current temperature on each sensor. A value crossing into the alarm state reported by wtWebGraphThermHygroBinaryTempValueTable's wtWebGraphThermHygroBinaryTempValue would flag that a monitored room or rack has exceeded its configured high-temperature threshold, signaling a possible HVAC failure.
What Can Be Monitored
- current temperature reading per sensor
- relative humidity reading per sensor
- binary (threshold-crossed) temperature alarm state
- sensor count/index
- device session/config-mode status
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| IpAddress | |
| NetworkAddress | |
| TimeTicks | |
| enterprises |
From RFC1213-MIB
| DisplayString | |
| PhysAddress |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| wut | 1.3.6.1.4.1.5040 | |||
| wtComServer | 1.3.6.1.4.1.5040.1 | |||
| wtWebio | 1.3.6.1.4.1.5040.1.2 | |||
| wtWebGraphThermHygro | 1.3.6.1.4.1.5040.1.2.9 | |||
| NTF wtWebGraphThermHygroAlert1 | 1.3.6.1.4.1.5040.1.2.9.0.31 | This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert2 | 1.3.6.1.4.1.5040.1.2.9.0.32 | This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert3 | 1.3.6.1.4.1.5040.1.2.9.0.33 | This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert4 | 1.3.6.1.4.1.5040.1.2.9.0.34 | This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert5 | 1.3.6.1.4.1.5040.1.2.9.0.35 | This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert6 | 1.3.6.1.4.1.5040.1.2.9.0.36 | This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert7 | 1.3.6.1.4.1.5040.1.2.9.0.37 | This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert8 | 1.3.6.1.4.1.5040.1.2.9.0.38 | This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert9 | 1.3.6.1.4.1.5040.1.2.9.0.91 | This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert10 | 1.3.6.1.4.1.5040.1.2.9.0.92 | This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert11 | 1.3.6.1.4.1.5040.1.2.9.0.93 | This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert12 | 1.3.6.1.4.1.5040.1.2.9.0.94 | This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert13 | 1.3.6.1.4.1.5040.1.2.9.0.95 | This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert14 | 1.3.6.1.4.1.5040.1.2.9.0.96 | This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert15 | 1.3.6.1.4.1.5040.1.2.9.0.97 | This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlert16 | 1.3.6.1.4.1.5040.1.2.9.0.98 | This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphThermHygroAlertDiag | 1.3.6.1.4.1.5040.1.2.9.0.110 | This SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| wtWebGraphThermHygroTemp | 1.3.6.1.4.1.5040.1.2.9.1 | |||
| INT wtWebGraphThermHygroSensors | 1.3.6.1.4.1.5040.1.2.9.1.1 | INTEGER | read-only | Number of sensors |
| wtWebGraphThermHygroSensorTable | 1.3.6.1.4.1.5040.1.2.9.1.2 | not-accessible | List of sensors. | |
| wtWebGraphThermHygroSensorEntry | 1.3.6.1.4.1.5040.1.2.9.1.2.1 | not-accessible | List of sensor numbers. | |
| INT wtWebGraphThermHygroSensorNo | 1.3.6.1.4.1.5040.1.2.9.1.2.1.1 | INTEGER | read-only | Sensor number. |
| wtWebGraphThermHygroTempValueTable | 1.3.6.1.4.1.5040.1.2.9.1.3 | not-accessible | List of measurement values corresponding to the channel numbers. | |
| wtWebGraphThermHygroTempValueEntry | 1.3.6.1.4.1.5040.1.2.9.1.3.1 | not-accessible | Measurement values of the sensors. | |
| OCT wtWebGraphThermHygroTempValue | 1.3.6.1.4.1.5040.1.2.9.1.3.1.1 | OCTET STRING | read-only | Measurement value of the sensor, ASCII, 5 characters in length. |
| wtWebGraphThermHygroBinaryTempValueTable | 1.3.6.1.4.1.5040.1.2.9.1.4 | not-accessible | List of binary measurement values corresponding to the channel numbers. | |
| wtWebGraphThermHygroBinaryTempValueEntry | 1.3.6.1.4.1.5040.1.2.9.1.4.1 | not-accessible | Binary measurement values of the sensors. | |
| INT wtWebGraphThermHygroBinaryTempValue | 1.3.6.1.4.1.5040.1.2.9.1.4.1.1 | INTEGER | read-only | Binary measurement value of the sensor in 1/10 degrees Celsius or 1/10 per cent, signed number, 0x4FFF6 indicates an invalid measured value. |
| wtWebGraphThermHygroSessCntrl | 1.3.6.1.4.1.5040.1.2.9.2 | |||
| OCT wtWebGraphThermHygroSessCntrlPassword | 1.3.6.1.4.1.5040.1.2.9.2.1 | OCTET STRING | read-write | Entering this password opens a session which is ended by writing a 1 to wtWebGraphThermHygroSessCntrlLogout. When read this variable provides a string of length zero. |
| INT wtWebGraphThermHygroSessCntrlConfigMode | 1.3.6.1.4.1.5040.1.2.9.2.2 | INTEGER | read-only | When the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read. |
| INT wtWebGraphThermHygroSessCntrlLogout | 1.3.6.1.4.1.5040.1.2.9.2.3 | INTEGER | read-write | If the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0. |
| OCT wtWebGraphThermHygroSessCntrlAdminPassword | 1.3.6.1.4.1.5040.1.2.9.2.4 | OCTET STRING | read-write | This password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public. |
| OCT wtWebGraphThermHygroSessCntrlConfigPassword | 1.3.6.1.4.1.5040.1.2.9.2.5 | OCTET STRING | read-write | This password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer. |
| wtWebGraphThermHygroConfig | 1.3.6.1.4.1.5040.1.2.9.3 | |||
| wtWebGraphThermHygroDevice | 1.3.6.1.4.1.5040.1.2.9.3.1 | |||
| wtWebGraphThermHygroText | 1.3.6.1.4.1.5040.1.2.9.3.1.1 | |||
| OCT wtWebGraphThermHygroDeviceName | 1.3.6.1.4.1.5040.1.2.9.3.1.1.1 | OCTET STRING | read-write | Name of the Webio, which is user definable. |
| OCT wtWebGraphThermHygroDeviceText | 1.3.6.1.4.1.5040.1.2.9.3.1.1.2 | OCTET STRING | read-write | Description of the Webio, which is user definable. |
| OCT wtWebGraphThermHygroDeviceLocation | 1.3.6.1.4.1.5040.1.2.9.3.1.1.3 | OCTET STRING | read-write | Description of the location of the Webio, which is user definable. |
| OCT wtWebGraphThermHygroDeviceContact | 1.3.6.1.4.1.5040.1.2.9.3.1.1.4 | OCTET STRING | read-write | Contact address of the system operator of the Webio, which is user definable. |
| wtWebGraphThermHygroTimeDate | 1.3.6.1.4.1.5040.1.2.9.3.1.2 | |||
| wtWebGraphThermHygroTimeZone | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1 | |||
| INT wtWebGraphThermHygroTzOffsetHrs | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.1 | INTEGER | read-write | Offset hours for the time zone (winter time) with respect to UTC. |
| INT wtWebGraphThermHygroTzOffsetMin | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.2 | INTEGER | read-write | Offset minutes for the time zone (winter time) with respect to UTC. |
| OCT wtWebGraphThermHygroTzEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.3 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezone |
| INT wtWebGraphThermHygroStTzOffsetHrs | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.4 | INTEGER | read-write | Offset hours of the time zone (summer time) with respect to UTC. |
| INT wtWebGraphThermHygroStTzOffsetMin | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.5 | INTEGER | read-write | Offset minutes of the time zone (summer time) with respect to UTC. |
| OCT wtWebGraphThermHygroStTzEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.6 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertime |
| INT wtWebGraphThermHygroStTzStartMonth | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.7 | INTEGER | read-write | Month in which the change is made from winter time to summer time. |
| INT wtWebGraphThermHygroStTzStartMode | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.8 | INTEGER | read-write | Mode of the day of the week for which the change is made from winter time to summer time. |
| INT wtWebGraphThermHygroStTzStartWday | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.9 | INTEGER | read-write | Day of the week on which the change is made from winter time to summer time |
| INT wtWebGraphThermHygroStTzStartHrs | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.10 | INTEGER | read-write | Hour in which the time zone is changed from winter to summer time with respect to UTC. |
| INT wtWebGraphThermHygroStTzStartMin | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.11 | INTEGER | read-write | Minute in which the time zone is changed from winter to summer time with respect to UTC. |
| INT wtWebGraphThermHygroStTzStopMonth | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.12 | INTEGER | read-write | Month in which the change is made from summer time to winter time. |
| INT wtWebGraphThermHygroStTzStopMode | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.13 | INTEGER | read-write | Mode of the week day on which the change is made from summer time to winter time. |
| INT wtWebGraphThermHygroStTzStopWday | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.14 | INTEGER | read-write | Day of the week on which the change is made from summer time to winter time. |
| INT wtWebGraphThermHygroStTzStopHrs | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.15 | INTEGER | read-write | Hour at which the time zone is changed from summer to winter time with respect to UTC. |
| INT wtWebGraphThermHygroStTzStopMin | 1.3.6.1.4.1.5040.1.2.9.3.1.2.1.16 | INTEGER | read-write | Minute at which the time zone is changed from summer to winter time with respect to UTC. |
| wtWebGraphThermHygroTimeServer | 1.3.6.1.4.1.5040.1.2.9.3.1.2.2 | |||
| OCT wtWebGraphThermHygroTimeServer1 | 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.1 | OCTET STRING | read-write | IP address or name of the 1st time server in ASCII |
| OCT wtWebGraphThermHygroTimeServer2 | 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.2 | OCTET STRING | read-write | IP address or name of the 2nd time server in ASCII |
| OCT wtWebGraphThermHygroTsEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.3 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Server |
| INT wtWebGraphThermHygroTsSyncTime | 1.3.6.1.4.1.5040.1.2.9.3.1.2.2.4 | INTEGER | read-write | Daily synchronisation time with the time server (hour: 0-23). |
| wtWebGraphThermHygroDeviceClock | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3 | |||
| INT wtWebGraphThermHygroClockHrs | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.1 | INTEGER | read-write | Clock hours taking into account the time zone settings. |
| INT wtWebGraphThermHygroClockMin | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.2 | INTEGER | read-write | Clock minutes taking into account the time zone settings. |
| INT wtWebGraphThermHygroClockDay | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.3 | INTEGER | read-write | Date: Day of the month, taking into account the time zone settings. |
| INT wtWebGraphThermHygroClockMonth | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.4 | INTEGER | read-write | Date: Month, taking into account the time zone settings. |
| INT wtWebGraphThermHygroClockYear | 1.3.6.1.4.1.5040.1.2.9.3.1.2.3.5 | INTEGER | read-write | Date: Year, taking into account the time zone settings. |
| wtWebGraphThermHygroBasic | 1.3.6.1.4.1.5040.1.2.9.3.1.3 | |||
| wtWebGraphThermHygroNetwork | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1 | |||
| IP wtWebGraphThermHygroIpAddress | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.1 | IpAddress | read-write | IP address of the Webio |
| IP wtWebGraphThermHygroSubnetMask | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.2 | IpAddress | read-write | Subnet mask of the Webio |
| IP wtWebGraphThermHygroGateway | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.3 | IpAddress | read-write | Gateway of the Webio |
| OCT wtWebGraphThermHygroDnsServer1 | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.4 | OCTET STRING | read-write | IP address of the 1st DNS server in ASCII |
| OCT wtWebGraphThermHygroDnsServer2 | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.5 | OCTET STRING | read-write | IP address of the 2nd DNS server in ASCII |
| OCT wtWebGraphThermHygroAddConfig | 1.3.6.1.4.1.5040.1.2.9.3.1.3.1.6 | OCTET STRING | read-write | Additional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: BOOTP disable |
| wtWebGraphThermHygroHTTP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.2 | |||
| OCT wtWebGraphThermHygroStartup | 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.1 | OCTET STRING | read-write | Binary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: Index.htm Bit 2: Home.htm Bit 3: User.htm Only one page may be selected at a time. |
| OCT wtWebGraphThermHygroGetHeaderEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.2 | OCTET STRING | read-write | If this bit is set, every answer of a short form GET question will be lead by the IP-address and name of the device: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : GET Header enable |
| INT wtWebGraphThermHygroHttpPort | 1.3.6.1.4.1.5040.1.2.9.3.1.3.2.3 | INTEGER | read-write | Definition of the standard HTML port (Default: 80). |
| wtWebGraphThermHygroMail | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3 | |||
| OCT wtWebGraphThermHygroMailAdName | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.1 | OCTET STRING | read-write | Device name for mail administration. |
| OCT wtWebGraphThermHygroMailReply | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.2 | OCTET STRING | read-write | Reply address for the mail server. |
| OCT wtWebGraphThermHygroMailServer | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.3 | OCTET STRING | read-write | Name or IP address of the mail server. |
| OCT wtWebioAn1MailEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.4 | OCTET STRING | read-write | Set this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enable |
| OCT wtWebGraphThermHygroMailAuthentication | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.5 | OCTET STRING | read-write | Selection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authentication |
| OCT wtWebGraphThermHygroMailAuthUser | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.6 | OCTET STRING | read-write | Name of the user to be authenticated. |
| OCT wtWebGraphThermHygroMailAuthPassword | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.7 | OCTET STRING | read-write | Authentication password. |
| OCT wtWebGraphThermHygroMailPop3Server | 1.3.6.1.4.1.5040.1.2.9.3.1.3.3.8 | OCTET STRING | read-write | Name or Ip-address of the POP3 Servers. |
| wtWebGraphThermHygroSNMP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4 | |||
| OCT wtWebGraphThermHygroSnmpCommunityStringRead | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.1 | OCTET STRING | read-write | Community string read only |
| OCT wtWebGraphThermHygroSnmpCommunityStringReadWrite | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.2 | OCTET STRING | read-write | Community string read / write |
| OCT wtWebGraphThermHygroSystemTrapManagerIP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.3 | OCTET STRING | read-write | Name or IP address of the TCP server which accepts the system trap. |
| OCT wtWebGraphThermHygroSystemTrapEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.4 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unused |
| OCT wtWebGraphThermHygroSnmpEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.5 | OCTET STRING | read-write | Set bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enable |
| OCT wtWebGraphThermHygroSnmpCommunityStringTrap | 1.3.6.1.4.1.5040.1.2.9.3.1.3.4.6 | OCTET STRING | read-write | Community string send within traps. |
| wtWebGraphThermHygroUDP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.5 | |||
| INT wtWebGraphThermHygroUdpPort | 1.3.6.1.4.1.5040.1.2.9.3.1.3.5.1 | INTEGER | read-write | Udp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device. |
| OCT wtWebGraphThermHygroUdpEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.5.2 | OCTET STRING | read-write | Set this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enable |
| wtWebGraphThermHygroSyslog | 1.3.6.1.4.1.5040.1.2.9.3.1.3.6 | |||
| OCT wtWebGraphThermHygroSyslogServerIP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.1 | OCTET STRING | read-write | Name or IP address of the Syslog server, which accepts the Syslog messgaes. |
| INT wtWebGraphThermHygroSyslogServerPort | 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.2 | INTEGER | read-write | Portnumber of the Syslog servers, default 514. |
| OCT wtWebGraphThermHygroSyslogSystemMessagesEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.3 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unused |
| OCT wtWebGraphThermHygroSyslogEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.6.4 | OCTET STRING | read-write | Set bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enable |
| wtWebGraphThermHygroFTP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7 | |||
| OCT wtWebGraphThermHygroFTPServerIP | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.1 | OCTET STRING | read-write | Name or IP address of the FTP server, which accepts the FTP messages. |
| INT wtWebGraphThermHygroFTPServerControlPort | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.2 | INTEGER | read-write | Portnumber of the control port of the FTP server, default 21. |
| OCT wtWebGraphThermHygroFTPUserName | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.3 | OCTET STRING | read-write | FTP Loggin: user name. |
| OCT wtWebGraphThermHygroFTPPassword | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.4 | OCTET STRING | read-write | FTP Loggin: user password. |
| OCT wtWebGraphThermHygroFTPAccount | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.5 | OCTET STRING | read-write | FTP Loggin: name of account. |
| OCT wtWebGraphThermHygroFTPOption | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.6 | OCTET STRING | read-write | Bit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enable |
| OCT wtWebGraphThermHygroFTPEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.3.7.7 | OCTET STRING | read-write | Set Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enable |
| wtWebGraphThermHygroDatalogger | 1.3.6.1.4.1.5040.1.2.9.3.1.4 | |||
| INT wtWebGraphThermHygroLoggerTimebase | 1.3.6.1.4.1.5040.1.2.9.3.1.4.1 | INTEGER | read-write | Time base of the data logger |
| OCT wtWebGraphThermHygroLoggerSensorSel | 1.3.6.1.4.1.5040.1.2.9.3.1.4.2 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
| OCT wtWebGraphThermHygroDisplaySensorSel | 1.3.6.1.4.1.5040.1.2.9.3.1.4.3 | OCTET STRING | read-write | Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
| wtWebGraphThermHygroSensorColorTable | 1.3.6.1.4.1.5040.1.2.9.3.1.4.4 | not-accessible | List of sensor colors for the praphical presentation. | |
| wtWebGraphThermHygroSensorColorEntry | 1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1 | not-accessible | Index numbers of the sensors. | |
| OCT wtWebGraphThermHygroSensorColor | 1.3.6.1.4.1.5040.1.2.9.3.1.4.4.1.1 | OCTET STRING | read-write | Color of the sensors at the praphical presention. |
| OCT wtWebGraphThermHygroAutoScaleEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.4.5 | OCTET STRING | read-write | If bit 0 is set, vertical auto scale is enabled: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Auto Scale enable |
| OCT wtWebGraphThermHygroVerticalUpperLimit | 1.3.6.1.4.1.5040.1.2.9.3.1.4.6 | OCTET STRING | read-write | This value defines the maximum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroVerticalLowerLimit | 1.3.6.1.4.1.5040.1.2.9.3.1.4.7 | OCTET STRING | read-write | This value defines the minimum temperature shown in the graphical presentation, if no auto scaling is selected. Temperature in degrees with maximum 2 decimal places. |
| INT wtWebGraphThermHygroHorizontalZoom | 1.3.6.1.4.1.5040.1.2.9.3.1.4.8 | INTEGER | read-write | Defines the default zoom stage, if no auto scaling is selected. |
| wtWebGraphThermHygroAlarm | 1.3.6.1.4.1.5040.1.2.9.3.1.5 | |||
| INT wtWebGraphThermHygroAlarmCount | 1.3.6.1.4.1.5040.1.2.9.3.1.5.1 | INTEGER | read-only | Number of independent alarms. |
| wtWebGraphThermHygroAlarmIfTable | 1.3.6.1.4.1.5040.1.2.9.3.1.5.2 | not-accessible | List of alarm indices. | |
| wtWebGraphThermHygroAlarmIfEntry | 1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1 | not-accessible | Numbers of the alarms. | |
| INT wtWebGraphThermHygroAlarmNo | 1.3.6.1.4.1.5040.1.2.9.3.1.5.2.1.1 | INTEGER | read-only | Alarm number. |
| wtWebGraphThermHygroAlarmTable | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3 | not-accessible | List of settings depending on the alarm number. | |
| wtWebGraphThermHygroAlarmEntry | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1 | not-accessible | Alarm parameters of the individual alarms. | |
| OCT wtWebGraphThermHygroAlarmTrigger | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.1 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
| OCT wtWebGraphThermHygroAlarmMin | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.2 | OCTET STRING | read-write | Minimum temperature in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmMax | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.3 | OCTET STRING | read-write | Maximum temperature in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmHysteresis | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 | OCTET STRING | read-write | Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) , in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmDelay | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5 | OCTET STRING | read-write | Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). |
| OCT wtWebGraphThermHygroAlarmInterval | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.6 | OCTET STRING | read-write | Send interval for alarm messages. |
| OCT wtWebGraphThermHygroAlarmEnable | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.7 | OCTET STRING | read-write | Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
| OCT wtWebGraphThermHygroAlarmEMailAddr | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.8 | OCTET STRING | read-write | E-Mail address for sending the alarm mail to. |
| OCT wtWebGraphThermHygroAlarmMailSubject | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.9 | OCTET STRING | read-write | Subject line for alarm mail. |
| OCT wtWebGraphThermHygroAlarmMailText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.10 | OCTET STRING | read-write | Alarm mail text: provides the current temperature; n = 1..8. provides the current time. |
| OCT wtWebGraphThermHygroAlarmManagerIP | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.11 | OCTET STRING | read-write | Name or IP address of the SNMP Manager which accepts the trap. |
| OCT wtWebGraphThermHygroAlarmTrapText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.12 | OCTET STRING | read-write | This text is sent in the trap body. |
| OCT wtWebGraphThermHygroAlarmMailOptions | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.13 | OCTET STRING | read-write | Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
| OCT wtWebGraphThermHygroAlarmTcpIpAddr | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.14 | OCTET STRING | read-write | Name or IP address of the TCP server which accepts the trap. |
| INT wtWebGraphThermHygroAlarmTcpPort | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.15 | INTEGER | read-write | Port number of the TCP server which accepts the trap. |
| OCT wtWebGraphThermHygroAlarmTcpText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.16 | OCTET STRING | read-write | This text is sent in the TCP trap body. |
| OCT wtWebGraphThermHygroAlarmClearMailSubject | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.17 | OCTET STRING | read-write | Subject line for alarm clear mail. |
| OCT wtWebGraphThermHygroAlarmClearMailText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.18 | OCTET STRING | read-write | Alarm clear mail text: provides the current temperature; n = 1..8. provides the current time. |
| OCT wtWebGraphThermHygroAlarmClearTrapText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.19 | OCTET STRING | read-write | This text is sent in the trap body. |
| OCT wtWebGraphThermHygroAlarmClearTcpText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.20 | OCTET STRING | read-write | This text is sent in the TCP trap body. |
| OCT wtWebGraphThermHygroAlarmDeltaTemp | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.21 | OCTET STRING | read-write | Maximum rate of change degrees/min with maximum 2 decimal places. Compared with the average of a period of 5 minutes. |
| OCT wtWebGraphThermHygroAlarmRHMin | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.22 | OCTET STRING | read-write | Minimum rel. Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmRHMax | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.23 | OCTET STRING | read-write | Maximum rel.Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmRHHysteresis | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.24 | OCTET STRING | read-write | Hysterese rel. Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmAHMin | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.25 | OCTET STRING | read-write | Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroAlarmAHMax | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.26 | OCTET STRING | read-write | Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. |
| IP wtWebGraphThermHygroAlarmSyslogIpAddr | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.27 | IpAddress | read-write | IP address of the syslog server to which the Webio device should send syslog messages. |
| INT wtWebGraphThermHygroAlarmSyslogPort | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.28 | INTEGER | read-write | Port number of the syslog server to which the Webio device should send syslog messages. |
| OCT wtWebGraphThermHygroAlarmSyslogText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.29 | OCTET STRING | read-write | Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. |
| OCT wtWebGraphThermHygroAlarmSyslogClearText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.30 | OCTET STRING | read-write | Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. |
| OCT wtWebGraphThermHygroAlarmFtpDataPort | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.31 | OCTET STRING | read-write | Local data port: 1..65535 or AUTO: the next free port will be assigned. |
| OCT wtWebGraphThermHygroAlarmFtpFileName | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.32 | OCTET STRING | read-write | Name of the file including path informations. |
| OCT wtWebGraphThermHygroAlarmFtpText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.33 | OCTET STRING | read-write | Message text to store on the FTP server. |
| OCT wtWebGraphThermHygroAlarmFtpClearText | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.34 | OCTET STRING | read-write | Alarm clear message to store on the FTP server. |
| OCT wtWebGraphThermHygroAlarmFtpOptions | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.35 | OCTET STRING | read-write | Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused |
| OCT wtWebGraphThermHygroAlarmTimerCron | 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.36 | OCTET STRING | read-write | This entry contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas - a partition within the allowed range (1-5) - step size within an partition of the allowed range (0-59/2: every second minute). |
| wtWebGraphThermHygroPorts | 1.3.6.1.4.1.5040.1.2.9.3.2 | |||
| wtWebGraphThermHygroPortTable | 1.3.6.1.4.1.5040.1.2.9.3.2.1 | not-accessible | List of settings depending on the sensor number. | |
| wtWebGraphThermHygroPortEntry | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1 | not-accessible | Sensor parameters for the individual sensors. | |
| OCT wtWebGraphThermHygroPortName | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.1 | OCTET STRING | read-write | Name of the sensor. |
| OCT wtWebGraphThermHygroPortText | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.2 | OCTET STRING | read-write | Description of the sensor. |
| OCT wtWebGraphThermHygroPortOffset1 | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.3 | OCTET STRING | read-write | Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. |
| OCT wtWebGraphThermHygroPortTemperature1 | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.4 | OCTET STRING | read-write | Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroPortOffset2 | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.5 | OCTET STRING | read-write | Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. |
| OCT wtWebGraphThermHygroPortTemperature2 | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.6 | OCTET STRING | read-write | Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. |
| OCT wtWebGraphThermHygroPortComment | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.7 | OCTET STRING | read-write | Offset calibration: informations of date, name of operator, reference devices. |
| OCT wtWebGraphThermHygroPortSensorSelect | 1.3.6.1.4.1.5040.1.2.9.3.2.1.1.8 | OCTET STRING | read-write | Binary coded options for sensor 1: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : PT100 Bit 1 : PT1000 (default) Bit 2-7: unused Binary coded options for sensor 2: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : W&T Sensor rel. humidity (default) Bit 1 : Skalar 0-2.5V Bit 2 : Disconnect Bit 3-7: unused |
| wtWebGraphThermHygroManufact | 1.3.6.1.4.1.5040.1.2.9.3.3 | |||
| OCT wtWebGraphThermHygroMfName | 1.3.6.1.4.1.5040.1.2.9.3.3.1 | OCTET STRING | read-write | Manufacturer company name |
| OCT wtWebGraphThermHygroMfAddr | 1.3.6.1.4.1.5040.1.2.9.3.3.2 | OCTET STRING | read-write | Manufacturer address. |
| OCT wtWebGraphThermHygroMfHotline | 1.3.6.1.4.1.5040.1.2.9.3.3.3 | OCTET STRING | read-write | Manufacturer hotline. |
| OCT wtWebGraphThermHygroMfInternet | 1.3.6.1.4.1.5040.1.2.9.3.3.4 | OCTET STRING | read-write | Manufacturer Internet address. |
| OCT wtWebGraphThermHygroMfDeviceTyp | 1.3.6.1.4.1.5040.1.2.9.3.3.5 | OCTET STRING | read-write | Manufacturer device name (model number). |
| OCT wtWebGraphThermHygroMfOrderNo | 1.3.6.1.4.1.5040.1.2.9.3.3.6 | OCTET STRING | read-write | Manufacturer part number. |
| wtWebGraphThermHygroDiag | 1.3.6.1.4.1.5040.1.2.9.4 | |||
| INT wtWebGraphThermHygroDiagErrorCount | 1.3.6.1.4.1.5040.1.2.9.4.1 | INTEGER | read-only | Number of entries in the error memory. |
| OCT wtWebGraphThermHygroDiagBinaryError | 1.3.6.1.4.1.5040.1.2.9.4.2 | OCTET STRING | read-only | Error causes coded bit-by-bit. |
| INT wtWebGraphThermHygroDiagErrorIndex | 1.3.6.1.4.1.5040.1.2.9.4.3 | INTEGER | read-write | The value of this variable is used as an index to read an error massege from wtWebGraphThermHygroDiagErrorMessage. Errors are numbered from 1 to wtWebGraphThermHygroDiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphThermHygroDiagErrorMessage. |
| OCT wtWebGraphThermHygroDiagErrorMessage | 1.3.6.1.4.1.5040.1.2.9.4.4 | OCTET STRING | read-only | Using wtWebGraphThermHygroDiagErrorIndex as an index, the appropriate message is available. |
| INT wtWebGraphThermHygroDiagErrorClear | 1.3.6.1.4.1.5040.1.2.9.4.5 | INTEGER | write-only | Writing 1 into this variable clears all diagnosis messages. |
RFC description
Manages WebGraph temperature and humidity monitoring devices with support for alarms, FTP, syslog, and email notifications.
Start monitoring Wiesemann & Theis networked environmental sensors with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.