All MIBs › WebGraph-Air-Quality-US-MIB
Category: Power and Environmental Monitoring
Description: Monitors WebGraph air quality sensor measurements including CO2 concentration, VOC levels, and environmental conditions.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is WebGraph-Air-Quality-US-MIB?
This is a vendor-specific proprietary MIB from WebGraph, a maker of networked environmental monitoring appliances used to watch conditions in data centers, server rooms, and equipment closets. It exposes air-quality related sensor data (using US unit scaling) including per-sensor identification, measured environmental values, and derived binary alarm states. Although branded 'air quality,' the exposed objects are heavily temperature-value oriented, and the module supports monitoring hardware/environmental status by letting an operator track whether sensor readings have crossed configured thresholds indicating an HVAC or environmental control problem. There is no documented dependency on other MIBs; the objects are rooted entirely under WebGraph's own enterprise MIB tree. It is typically deployed as a small networked sensor appliance placed inside racks or rooms to feed environmental readings into a central monitoring system. Engineers can download the WebGraph-Air-Quality-US-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in WebGraph-Air-Quality-US-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- WebGraph networked environmental/air-quality sensor appliance
Monitoring Examples
An administrator polling the wtWebGraphAirQualitySensorTable/wtWebGraphAirQualitySensorEntry (indexed by wtWebGraphAirQualitySensorNo) can enumerate each attached sensor, then read the corresponding wtWebGraphAirQualityTempValueTable/Entry for the current measured value. The wtWebGraphAirQualityBinaryTempValueTable exposes a threshold-derived alarm bit per sensor, so a transition to the alarm state signals an environmental excursion, such as a server room overheating due to HVAC failure. The wtWebGraphAirQualityTempValuePktTable suggests readings are also delivered in a packetized form for streaming/logging purposes.
What Can Be Monitored
- configured sensor count
- per-sensor temperature/air-quality reading
- binary threshold alarm state
- packetized sensor data stream
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| IpAddress | |
| NetworkAddress | |
| TimeTicks | |
| enterprises |
From RFC1213-MIB
| DisplayString | |
| PhysAddress |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| wut | 1.3.6.1.4.1.5040 | |||
| wtComServer | 1.3.6.1.4.1.5040.1 | |||
| wtWebio | 1.3.6.1.4.1.5040.1.2 | |||
| wtWebGraphAirQuality | 1.3.6.1.4.1.5040.1.2.35 | |||
| NTF wtWebGraphAirQualityAlert1 | 1.3.6.1.4.1.5040.1.2.35.0.31 | This SNMP trap is generated when Alarm 1 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert2 | 1.3.6.1.4.1.5040.1.2.35.0.32 | This SNMP trap is generated when Alarm 2 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert3 | 1.3.6.1.4.1.5040.1.2.35.0.33 | This SNMP trap is generated when Alarm 3 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert4 | 1.3.6.1.4.1.5040.1.2.35.0.34 | This SNMP trap is generated when Alarm 4 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert5 | 1.3.6.1.4.1.5040.1.2.35.0.35 | This SNMP trap is generated when Alarm 5 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert6 | 1.3.6.1.4.1.5040.1.2.35.0.36 | This SNMP trap is generated when Alarm 6 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert7 | 1.3.6.1.4.1.5040.1.2.35.0.37 | This SNMP trap is generated when Alarm 7 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert8 | 1.3.6.1.4.1.5040.1.2.35.0.38 | This SNMP trap is generated when Alarm 8 was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert9 | 1.3.6.1.4.1.5040.1.2.35.0.91 | This SNMP trap is generated when Alarm 1 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert10 | 1.3.6.1.4.1.5040.1.2.35.0.92 | This SNMP trap is generated when Alarm 2 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert11 | 1.3.6.1.4.1.5040.1.2.35.0.93 | This SNMP trap is generated when Alarm 3 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert12 | 1.3.6.1.4.1.5040.1.2.35.0.94 | This SNMP trap is generated when Alarm 4 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert13 | 1.3.6.1.4.1.5040.1.2.35.0.95 | This SNMP trap is generated when Alarm 5 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert14 | 1.3.6.1.4.1.5040.1.2.35.0.96 | This SNMP trap is generated when Alarm 6 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert15 | 1.3.6.1.4.1.5040.1.2.35.0.97 | This SNMP trap is generated when Alarm 7 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlert16 | 1.3.6.1.4.1.5040.1.2.35.0.98 | This SNMP trap is generated when Alarm 8 was cleared, SNMP trap enable is set and SNMP is enabled. | ||
| NTF wtWebGraphAirQualityAlertDiag | 1.3.6.1.4.1.5040.1.2.35.0.110 | This SNMP trap is generated when a diagnosis/error message was triggered, SNMP trap enable is set and SNMP is enabled. | ||
| wtWebGraphAirQualityTemp | 1.3.6.1.4.1.5040.1.2.35.1 | |||
| INT wtWebGraphAirQualitySensors | 1.3.6.1.4.1.5040.1.2.35.1.1 | INTEGER | read-only | Number of sensors |
| wtWebGraphAirQualitySensorTable | 1.3.6.1.4.1.5040.1.2.35.1.2 | not-accessible | List of sensors. | |
| wtWebGraphAirQualitySensorEntry | 1.3.6.1.4.1.5040.1.2.35.1.2.1 | not-accessible | List of sensor numbers. | |
| INT wtWebGraphAirQualitySensorNo | 1.3.6.1.4.1.5040.1.2.35.1.2.1.1 | INTEGER | read-only | Sensor number. |
| wtWebGraphAirQualityTempValueTable | 1.3.6.1.4.1.5040.1.2.35.1.3 | not-accessible | List of measurement values corresponding to the channel numbers. | |
| wtWebGraphAirQualityTempValueEntry | 1.3.6.1.4.1.5040.1.2.35.1.3.1 | not-accessible | Measurement values of the sensors. | |
| OCT wtWebGraphAirQualityTempValue | 1.3.6.1.4.1.5040.1.2.35.1.3.1.1 | OCTET STRING | read-only | Measurement value of the sensor, ASCII, 5 characters in length. |
| wtWebGraphAirQualityBinaryTempValueTable | 1.3.6.1.4.1.5040.1.2.35.1.4 | not-accessible | List of binary measurement values corresponding to the channel numbers. | |
| wtWebGraphAirQualityBinaryTempValueEntry | 1.3.6.1.4.1.5040.1.2.35.1.4.1 | not-accessible | Binary measurement values of the sensors. | |
| INT wtWebGraphAirQualityBinaryTempValue | 1.3.6.1.4.1.5040.1.2.35.1.4.1.1 | INTEGER | read-only | Binary measurement value of the sensor in 1/10 degrees Celsius, 1/10 per cent or 1/10 ppm, signed number, 0x7FFFFFFF indicates an invalid measured value. |
| wtWebGraphAirQualityTempValuePktTable | 1.3.6.1.4.1.5040.1.2.35.1.8 | not-accessible | List of measurement values corresponding to the channel numbers. | |
| wtWebGraphAirQualityTempValuePktEntry | 1.3.6.1.4.1.5040.1.2.35.1.8.1 | not-accessible | Measurement values of the sensors. | |
| OCT wtWebGraphAirQualityTempValuePkt | 1.3.6.1.4.1.5040.1.2.35.1.8.1.1 | OCTET STRING | read-only | Measurement value of the sensor, ASCII, 5 characters in length, delimeter is decimal point. |
| wtWebGraphAirQualitySessCntrl | 1.3.6.1.4.1.5040.1.2.35.2 | |||
| OCT wtWebGraphAirQualitySessCntrlPassword | 1.3.6.1.4.1.5040.1.2.35.2.1 | OCTET STRING | read-write | Entering this password opens a session which is ended by writing a 1 to wtWebGraphAirQualitySessCntrlLogout. When read this variable provides a string of length zero. |
| INT wtWebGraphAirQualitySessCntrlConfigMode | 1.3.6.1.4.1.5040.1.2.35.2.2 | INTEGER | read-only | When the device is in SNMP configuration mode, the value 1 is returned, otherwise 0. If the read value is 0 even though the password was written, the device is already in config mode and the variables can only be read. |
| INT wtWebGraphAirQualitySessCntrlLogout | 1.3.6.1.4.1.5040.1.2.35.2.3 | INTEGER | read-write | If the device is in configuration mode and the session was opened by this SNMP Manager, writing a 1 to this variable will end the session and all parameters are stored. Writing a 2 discards all entries again. When read this variable provides the value 0. |
| OCT wtWebGraphAirQualitySessCntrlAdminPassword | 1.3.6.1.4.1.5040.1.2.35.2.4 | OCTET STRING | read-write | This password protects access to the variables with administrator rights. It can only be changed by the administrator. If no password was assigned, the valid password is public. |
| OCT wtWebGraphAirQualitySessCntrlConfigPassword | 1.3.6.1.4.1.5040.1.2.35.2.5 | OCTET STRING | read-write | This password protects access to the variables with configurator rights. It can be changed by the administrator and by the configurator. If no password was assigned, the valid password is public. When read this variable provides a null-pointer. |
| wtWebGraphAirQualityConfig | 1.3.6.1.4.1.5040.1.2.35.3 | |||
| wtWebGraphAirQualityDevice | 1.3.6.1.4.1.5040.1.2.35.3.1 | |||
| wtWebGraphAirQualityText | 1.3.6.1.4.1.5040.1.2.35.3.1.1 | |||
| OCT wtWebGraphAirQualityDeviceName | 1.3.6.1.4.1.5040.1.2.35.3.1.1.1 | OCTET STRING | read-write | Name of the Webio, which is user definable. |
| OCT wtWebGraphAirQualityDeviceText | 1.3.6.1.4.1.5040.1.2.35.3.1.1.2 | OCTET STRING | read-write | Description of the Webio, which is user definable. |
| OCT wtWebGraphAirQualityDeviceLocation | 1.3.6.1.4.1.5040.1.2.35.3.1.1.3 | OCTET STRING | read-write | Description of the location of the Webio, which is user definable. |
| OCT wtWebGraphAirQualityDeviceContact | 1.3.6.1.4.1.5040.1.2.35.3.1.1.4 | OCTET STRING | read-write | Contact address of the system operator of the Webio, which is user definable. |
| wtWebGraphAirQualityTimeDate | 1.3.6.1.4.1.5040.1.2.35.3.1.2 | |||
| wtWebGraphAirQualityTimeZone | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1 | |||
| INT wtWebGraphAirQualityTzOffsetHrs | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.1 | INTEGER | read-write | Offset hours for the time zone (winter time) with respect to UTC. |
| INT wtWebGraphAirQualityTzOffsetMin | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.2 | INTEGER | read-write | Offset minutes for the time zone (winter time) with respect to UTC. |
| OCT wtWebGraphAirQualityTzEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.3 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Timezone |
| INT wtWebGraphAirQualityStTzOffsetHrs | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.4 | INTEGER | read-write | Offset hours of the time zone (summer time) with respect to UTC. |
| INT wtWebGraphAirQualityStTzOffsetMin | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.5 | INTEGER | read-write | Offset minutes of the time zone (summer time) with respect to UTC. |
| OCT wtWebGraphAirQualityStTzEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.6 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Summertime |
| INT wtWebGraphAirQualityStTzStartMonth | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.7 | INTEGER | read-write | Month in which the change is made from winter time to summer time. |
| INT wtWebGraphAirQualityStTzStartMode | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.8 | INTEGER | read-write | Mode of the day of the week for which the change is made from winter time to summer time. |
| INT wtWebGraphAirQualityStTzStartWday | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.9 | INTEGER | read-write | Day of the week on which the change is made from winter time to summer time |
| INT wtWebGraphAirQualityStTzStartHrs | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.10 | INTEGER | read-write | Hour in which the time zone is changed from winter to summer time with respect to UTC. |
| INT wtWebGraphAirQualityStTzStartMin | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.11 | INTEGER | read-write | Minute in which the time zone is changed from winter to summer time with respect to UTC. |
| INT wtWebGraphAirQualityStTzStopMonth | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.12 | INTEGER | read-write | Month in which the change is made from summer time to winter time. |
| INT wtWebGraphAirQualityStTzStopMode | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.13 | INTEGER | read-write | Mode of the week day on which the change is made from summer time to winter time. |
| INT wtWebGraphAirQualityStTzStopWday | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.14 | INTEGER | read-write | Day of the week on which the change is made from summer time to winter time. |
| INT wtWebGraphAirQualityStTzStopHrs | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.15 | INTEGER | read-write | Hour at which the time zone is changed from summer to winter time with respect to UTC. |
| INT wtWebGraphAirQualityStTzStopMin | 1.3.6.1.4.1.5040.1.2.35.3.1.2.1.16 | INTEGER | read-write | Minute at which the time zone is changed from summer to winter time with respect to UTC. |
| wtWebGraphAirQualityTimeServer | 1.3.6.1.4.1.5040.1.2.35.3.1.2.2 | |||
| OCT wtWebGraphAirQualityTimeServer1 | 1.3.6.1.4.1.5040.1.2.35.3.1.2.2.1 | OCTET STRING | read-write | IP address or name of the 1st time server in ASCII |
| OCT wtWebGraphAirQualityTimeServer2 | 1.3.6.1.4.1.5040.1.2.35.3.1.2.2.2 | OCTET STRING | read-write | IP address or name of the 2nd time server in ASCII |
| OCT wtWebGraphAirQualityTsEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.2.2.3 | OCTET STRING | read-write | Binary coded conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Apply Time Server |
| INT wtWebGraphAirQualityTsSyncTime | 1.3.6.1.4.1.5040.1.2.35.3.1.2.2.4 | INTEGER | read-write | Daily synchronisation time with the time server (hour: 0-23). |
| wtWebGraphAirQualityDeviceClock | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3 | |||
| INT wtWebGraphAirQualityClockHrs | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3.1 | INTEGER | read-write | Clock hours taking into account the time zone settings. |
| INT wtWebGraphAirQualityClockMin | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3.2 | INTEGER | read-write | Clock minutes taking into account the time zone settings. |
| INT wtWebGraphAirQualityClockDay | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3.3 | INTEGER | read-write | Date: Day of the month, taking into account the time zone settings. |
| INT wtWebGraphAirQualityClockMonth | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3.4 | INTEGER | read-write | Date: Month, taking into account the time zone settings. |
| INT wtWebGraphAirQualityClockYear | 1.3.6.1.4.1.5040.1.2.35.3.1.2.3.5 | INTEGER | read-write | Date: Year, taking into account the time zone settings. |
| wtWebGraphAirQualityBasic | 1.3.6.1.4.1.5040.1.2.35.3.1.3 | |||
| wtWebGraphAirQualityNetwork | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1 | |||
| IP wtWebGraphAirQualityIpAddress | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.1 | IpAddress | read-write | IP address of the Webio |
| IP wtWebGraphAirQualitySubnetMask | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.2 | IpAddress | read-write | Subnet mask of the Webio |
| IP wtWebGraphAirQualityGateway | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.3 | IpAddress | read-write | Gateway of the Webio |
| OCT wtWebGraphAirQualityDnsServer1 | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.4 | OCTET STRING | read-write | IP address of the 1st DNS server in ASCII |
| OCT wtWebGraphAirQualityDnsServer2 | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.5 | OCTET STRING | read-write | IP address of the 2nd DNS server in ASCII |
| OCT wtWebGraphAirQualityAddConfig | 1.3.6.1.4.1.5040.1.2.35.3.1.3.1.6 | OCTET STRING | read-write | Additional configuration (1=ON): Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1: DHCP disable Bit 0: BOOTP disable |
| wtWebGraphAirQualityHTTP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.2 | |||
| OCT wtWebGraphAirQualityStartup | 1.3.6.1.4.1.5040.1.2.35.3.1.3.2.1 | OCTET STRING | read-write | Binary coded start page: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 3: smart.htm Bit 2: user.htm Bit 1: home.htm Bit 0: index.htm Only one page may be selected at a time. |
| OCT wtWebGraphAirQualityGetHeaderEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.2.2 | OCTET STRING | read-write | If these bits are set, every answer of a short form GET question will be lead by the IP-address and name of the device and/or a HTTP header: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-6: unused Bit 1 : GET HTTP enable Bit 0 : GET Header enable |
| INT wtWebGraphAirQualityHttpPort | 1.3.6.1.4.1.5040.1.2.35.3.1.3.2.3 | INTEGER | read-write | Definition of the standard HTML port (Default: 80). |
| wtWebGraphAirQualityMail | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3 | |||
| OCT wtWebGraphAirQualityMailAdName | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.1 | OCTET STRING | read-write | Device name for mail administration. |
| OCT wtWebGraphAirQualityMailReply | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.2 | OCTET STRING | read-write | Reply address for the mail server. |
| OCT wtWebGraphAirQualityMailServer | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.3 | OCTET STRING | read-write | Name or IP address of the mail server. |
| OCT wtWebioAn1MailEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.4 | OCTET STRING | read-write | Set this bit to enable the sending of mails: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Mail enable |
| OCT wtWebGraphAirQualityMailAuthentication | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.5 | OCTET STRING | read-write | Selection of the authentication modi: The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : POP3 before SMTP Bit 1 : ESMTP, authentication Bit 0 : SMTP, no authentication |
| OCT wtWebGraphAirQualityMailAuthUser | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.6 | OCTET STRING | read-write | Name of the user to be authenticated. |
| OCT wtWebGraphAirQualityMailAuthPassword | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.7 | OCTET STRING | read-write | Authentication password. |
| OCT wtWebGraphAirQualityMailPop3Server | 1.3.6.1.4.1.5040.1.2.35.3.1.3.3.8 | OCTET STRING | read-write | Name or Ip-address of the POP3 Servers. |
| wtWebGraphAirQualitySNMP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4 | |||
| OCT wtWebGraphAirQualitySnmpCommunityStringRead | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.1 | OCTET STRING | read-write | Community string read only |
| OCT wtWebGraphAirQualitySnmpCommunityStringReadWrite | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.2 | OCTET STRING | read-write | Community string read / write |
| OCT wtWebGraphAirQualitySystemTrapManagerIP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.3 | OCTET STRING | read-write | Name or IP address of the TCP server which accepts the system trap. |
| OCT wtWebGraphAirQualitySystemTrapEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.4 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2-7: unused |
| OCT wtWebGraphAirQualitySnmpEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.5 | OCTET STRING | read-write | Set bit 0 to enable SNMP. If disabled, the device did not respond to any SNMP requests. Bit 1 decided wether the community string of read operations is compared with the system password or not: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : SNMP enable |
| OCT wtWebGraphAirQualitySnmpCommunityStringTrap | 1.3.6.1.4.1.5040.1.2.35.3.1.3.4.6 | OCTET STRING | read-write | Community string send within traps. |
| wtWebGraphAirQualityUDP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.5 | |||
| INT wtWebGraphAirQualityUdpPort | 1.3.6.1.4.1.5040.1.2.35.3.1.3.5.1 | INTEGER | read-write | Udp port to which the Udp queries ( short form GET requests) can be sent. This port number must be unique within the device. |
| OCT wtWebGraphAirQualityUdpEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.5.2 | OCTET STRING | read-write | Set this bit to enable UDP support: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : UDP enable |
| wtWebGraphAirQualitySyslog | 1.3.6.1.4.1.5040.1.2.35.3.1.3.6 | |||
| OCT wtWebGraphAirQualitySyslogServerIP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.6.1 | OCTET STRING | read-write | Name or IP address of the Syslog server, which accepts the Syslog messgaes. |
| INT wtWebGraphAirQualitySyslogServerPort | 1.3.6.1.4.1.5040.1.2.35.3.1.3.6.2 | INTEGER | read-write | Portnumber of the Syslog servers, default 514. |
| OCT wtWebGraphAirQualitySyslogSystemMessagesEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.6.3 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: ColdStart Bit 1: WarmStart Bit 2: Diag Messages Bit 3-7: unused |
| OCT wtWebGraphAirQualitySyslogEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.6.4 | OCTET STRING | read-write | Set bit 0to enable Syslog: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : Syslog enable |
| wtWebGraphAirQualityFTP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7 | |||
| OCT wtWebGraphAirQualityFTPServerIP | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.1 | OCTET STRING | read-write | Name or IP address of the FTP server, which accepts the FTP messages. |
| INT wtWebGraphAirQualityFTPServerControlPort | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.2 | INTEGER | read-write | Portnumber of the control port of the FTP server, default 21. |
| OCT wtWebGraphAirQualityFTPUserName | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.3 | OCTET STRING | read-write | FTP Loggin: user name. |
| OCT wtWebGraphAirQualityFTPPassword | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.4 | OCTET STRING | read-write | FTP Loggin: user password. |
| OCT wtWebGraphAirQualityFTPAccount | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.5 | OCTET STRING | read-write | FTP Loggin: name of account. |
| OCT wtWebGraphAirQualityFTPOption | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.6 | OCTET STRING | read-write | Bit 0 switches the FTP Server in Passiv-Mode, the Client controls the data connection on its own: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : PASV enable |
| OCT wtWebGraphAirQualityFTPEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.3.7.7 | OCTET STRING | read-write | Set Bit 0 to enable FTP: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 1-7: unused Bit 0 : FTP enable |
| wtWebGraphAirQualityRSS | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8 | |||
| OCT wtWebGraphAirQualityRSSChannelTitle | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.1 | OCTET STRING | read-write | Name of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelLink | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.2 | OCTET STRING | read-write | Link of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelDescription | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.3 | OCTET STRING | read-write | Description of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelImage | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.4 | OCTET STRING | read-write | Link of a picture, which will be shown at the headline of the output window. |
| OCT wtWebGraphAirQualityRSSChannelImageTitle | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.5 | OCTET STRING | read-write | Alias Name of the picture. |
| OCT wtWebGraphAirQualityRSSChannelImageLink | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.6 | OCTET STRING | read-write | Link, which can be selected by clicking on the picture. |
| OCT wtWebGraphAirQualityRSSChannelItemTitle | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.7 | OCTET STRING | read-write | Title of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelItemLink | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.8 | OCTET STRING | read-write | Link of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelItemDescription | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.9 | OCTET STRING | read-write | Text of the RSS Feed. |
| OCT wtWebGraphAirQualityRSSChannelItemQuantity | 1.3.6.1.4.1.5040.1.2.35.3.1.3.8.10 | OCTET STRING | read-write | Number of lines. |
| wtWebGraphAirQualityLedLights | 1.3.6.1.4.1.5040.1.2.35.3.1.3.9 | |||
| OCT wtWebGraphAirQualityLedLightsSensorSel | 1.3.6.1.4.1.5040.1.2.35.3.1.3.9.1 | OCTET STRING | read-write | Binary coded trigger conditions, only one sensor may be selected at a time: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Sensor 1 Temperature Bit 1 : Sensor 2 Humidity Bit 2 : Sensor 3 VOC Bit 3-7: unused |
| OCT wtWebGraphAirQualityLedLightsLimitGreen | 1.3.6.1.4.1.5040.1.2.35.3.1.3.9.2 | OCTET STRING | read-write | Limit to switch on green LED |
| OCT wtWebGraphAirQualityLedLightsLimitYellow | 1.3.6.1.4.1.5040.1.2.35.3.1.3.9.3 | OCTET STRING | read-write | Limit to switch on yellow LED |
| OCT wtWebGraphAirQualityLedLightsLimitRed | 1.3.6.1.4.1.5040.1.2.35.3.1.3.9.4 | OCTET STRING | read-write | Limit to switch on red LED |
| wtWebGraphAirQualityDatalogger | 1.3.6.1.4.1.5040.1.2.35.3.1.4 | |||
| INT wtWebGraphAirQualityLoggerTimebase | 1.3.6.1.4.1.5040.1.2.35.3.1.4.1 | INTEGER | read-write | Time base of the data logger |
| OCT wtWebGraphAirQualityLoggerSensorSel | 1.3.6.1.4.1.5040.1.2.35.3.1.4.2 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Sensor 1 Temperature Bit 1 : Sensor 2 Humidity Bit 2 : Sensor 3 VOC Bit 3-7: unused |
| wtWebGraphAirQualityAlarm | 1.3.6.1.4.1.5040.1.2.35.3.1.5 | |||
| INT wtWebGraphAirQualityAlarmCount | 1.3.6.1.4.1.5040.1.2.35.3.1.5.1 | INTEGER | read-only | Number of independent alarms. |
| wtWebGraphAirQualityAlarmIfTable | 1.3.6.1.4.1.5040.1.2.35.3.1.5.2 | not-accessible | List of alarm indices. | |
| wtWebGraphAirQualityAlarmIfEntry | 1.3.6.1.4.1.5040.1.2.35.3.1.5.2.1 | not-accessible | Numbers of the alarms. | |
| INT wtWebGraphAirQualityAlarmNo | 1.3.6.1.4.1.5040.1.2.35.3.1.5.2.1.1 | INTEGER | read-only | Alarm number. |
| wtWebGraphAirQualityAlarmTable | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3 | not-accessible | List of settings depending on the alarm number. | |
| wtWebGraphAirQualityAlarmEntry | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1 | not-accessible | Alarm parameters of the individual alarms. | |
| OCT wtWebGraphAirQualityAlarmTrigger | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.1 | OCTET STRING | read-write | Binary coded trigger conditions: Octet 1: unused Octet 2: unused Octet 3: Bit 0: Timer Bit 1: ColdStart Bit 2: WarmStart Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2-7: unused |
| OCT wtWebGraphAirQualityAlarmMin | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.2 | OCTET STRING | read-write | Minimum temperature in degrees with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmMax | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.3 | OCTET STRING | read-write | Maximum temperature in degrees with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmHysteresis | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.4 | OCTET STRING | read-write | Temperature changes of this size clears the alarm state (MAX-hyst, MIN+hyst.) , in degrees with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmDelay | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.5 | OCTET STRING | read-write | Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes). |
| OCT wtWebGraphAirQualityAlarmInterval | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.6 | OCTET STRING | read-write | Send interval for alarm messages. |
| OCT wtWebGraphAirQualityAlarmEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.7 | OCTET STRING | read-write | Binary coded alarm enable: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable |
| OCT wtWebGraphAirQualityAlarmEMailAddr | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.8 | OCTET STRING | read-write | E-Mail address for sending the alarm mail to. |
| OCT wtWebGraphAirQualityAlarmMailSubject | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.9 | OCTET STRING | read-write | Subject line for alarm mail. |
| OCT wtWebGraphAirQualityAlarmMailText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.10 | OCTET STRING | read-write | Alarm mail text: provides the current temperature; n = 1..8. provides the current time. |
| OCT wtWebGraphAirQualityAlarmManagerIP | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.11 | OCTET STRING | read-write | Name or IP address of the SNMP Manager which accepts the trap. |
| OCT wtWebGraphAirQualityAlarmTrapText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.12 | OCTET STRING | read-write | This text is sent in the trap body. |
| OCT wtWebGraphAirQualityAlarmMailOptions | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.13 | OCTET STRING | read-write | Binary coded options: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Attach Thermo.csv Enable Bit 1 : CSV-Data_since_last_report Bit 2-7: unused |
| OCT wtWebGraphAirQualityAlarmTcpIpAddr | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.14 | OCTET STRING | read-write | Name or IP address of the TCP server which accepts the trap. |
| INT wtWebGraphAirQualityAlarmTcpPort | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.15 | INTEGER | read-write | Port number of the TCP server which accepts the trap. |
| OCT wtWebGraphAirQualityAlarmTcpText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.16 | OCTET STRING | read-write | This text is sent in the TCP trap body. |
| OCT wtWebGraphAirQualityAlarmClearMailSubject | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.17 | OCTET STRING | read-write | Subject line for alarm clear mail. |
| OCT wtWebGraphAirQualityAlarmClearMailText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.18 | OCTET STRING | read-write | Alarm clear mail text: provides the current temperature; n = 1..8. provides the current time. |
| OCT wtWebGraphAirQualityAlarmClearTrapText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.19 | OCTET STRING | read-write | This text is sent in the trap body. |
| OCT wtWebGraphAirQualityAlarmClearTcpText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.20 | OCTET STRING | read-write | This text is sent in the TCP trap body. |
| OCT wtWebGraphAirQualityAlarmDeltaTemp | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.21 | OCTET STRING | read-write | Maximum rate of change degrees/min with maximum 2 decimal places. Compared with the average of a period of 5 minutes. |
| OCT wtWebGraphAirQualityAlarmRHMin | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.22 | OCTET STRING | read-write | Minimum rel. Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmRHMax | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.23 | OCTET STRING | read-write | Maximum rel.Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmRHHysteresis | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.24 | OCTET STRING | read-write | Hysteresis of rel. Humidity in percent with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmAHMin | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.25 | OCTET STRING | read-write | Minimum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmAHMax | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.26 | OCTET STRING | read-write | Maximum abs. Humidity in g/(m*m*m) with maximum 2 decimal places. |
| IP wtWebGraphAirQualityAlarmSyslogIpAddr | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.27 | IpAddress | read-write | IP address of the syslog server to which the Webio device should send syslog messages. |
| INT wtWebGraphAirQualityAlarmSyslogPort | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.28 | INTEGER | read-write | Port number of the syslog server to which the Webio device should send syslog messages. |
| OCT wtWebGraphAirQualityAlarmSyslogText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.29 | OCTET STRING | read-write | Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. |
| OCT wtWebGraphAirQualityAlarmSyslogClearText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.30 | OCTET STRING | read-write | Every message starts with the priority key, a time stamp and the host ip address, according RFC3164. This text appears in the following syslog message body. |
| OCT wtWebGraphAirQualityAlarmFtpDataPort | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.31 | OCTET STRING | read-write | Local data port: 1..65535 or AUTO: the next free port will be assigned. |
| OCT wtWebGraphAirQualityAlarmFtpFileName | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.32 | OCTET STRING | read-write | Name of the file including path informations. |
| OCT wtWebGraphAirQualityAlarmFtpText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.33 | OCTET STRING | read-write | Message text to store on the FTP server. |
| OCT wtWebGraphAirQualityAlarmFtpClearText | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.34 | OCTET STRING | read-write | Alarm clear message to store on the FTP server. |
| OCT wtWebGraphAirQualityAlarmFtpOption | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.35 | OCTET STRING | read-write | Binary coded options, select only one option at the same time: STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STORE Bit 1 : APPEND Bit 2-7: unused |
| OCT wtWebGraphAirQualityAlarmTimerCron | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.36 | OCTET STRING | read-write | This entry contains 5 space or tab seperated text fields for time trigger definition. Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Range 0-59 2. Hours Range 0-23, 0 is midnight 3: Day of month Range 1-31 4: Month Range 1-12 5: Weekday Range 0-6, 0 is sunday Syntax for every field: - an asterix (*) enables every possible setting of a field - single numbers seperated by commas - a partition within the allowed range (1-5) - step size within an partition of the allowed range (0-59/2: every second minute). |
| OCT wtWebGraphAirQualityAlarmVocMax | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.37 | OCTET STRING | read-write | Maximum VOC in ppm with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmVocHysteresis | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.38 | OCTET STRING | read-write | Hysteresis of VOC in ppm with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityAlarmName | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.39 | OCTET STRING | read-write | Alert name |
| OCT wtWebGraphAirQualityAlarmActive | 1.3.6.1.4.1.5040.1.2.35.3.1.5.3.1.40 | OCTET STRING | read-write | Alert active 1 = ON 0 = OFF |
| wtWebGraphAirQualityGraphics | 1.3.6.1.4.1.5040.1.2.35.3.1.6 | |||
| wtWebGraphAirQualityGraphicsBase | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1 | |||
| OCT wtWebGraphAirQualityGraphicsBaseEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.1 | OCTET STRING | read-write | Defines the viewing options of the graphic: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Auto scroll enable Bit 1 : Show table Bit 2 : Show graph Bit 3 : Show control buttons Bit 4 : Show config menu Bit 5-7: unused |
| INT wtWebGraphAirQualityGraphicsBaseWidth | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.2 | INTEGER | read-write | Defines the width of the graphic in pixels. |
| INT wtWebGraphAirQualityGraphicsBaseHeight | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.3 | INTEGER | read-write | Defines the height of the graphic in pixels. |
| OCT wtWebGraphAirQualityGraphicsBaseFrameColor | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.4 | OCTET STRING | read-write | Frame color definition in RGB. |
| OCT wtWebGraphAirQualityGraphicsBaseBackgroundColor | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.5 | OCTET STRING | read-write | Background color definition in RGB. |
| INT wtWebGraphAirQualityGraphicsBasePollingrate | 1.3.6.1.4.1.5040.1.2.35.3.1.6.1.6 | INTEGER | read-write | Defines the pollingrate in seconds, which defines the refreshing intervall of the graphic. |
| wtWebGraphAirQualityGraphicsSelect | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2 | |||
| OCT wtWebGraphAirQualityGraphicsSelectDisplaySensorSel | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.1 | OCTET STRING | read-write | Binary coded sensor selection: only selected sensors will be shown in the graphical presentation: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3-7: unused |
| OCT wtWebGraphAirQualityGraphicsSelectDisplayShowExtrem | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.2 | OCTET STRING | read-write | Binary coded sensor selection: only selected sensors will be shown with minima and maxima: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Sensor 1 Bit 1: Sensor 2 Bit 2: Sensor 3 Bit 3-7: unused |
| wtWebGraphAirQualitySensorColorTable | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3 | not-accessible | List of sensor colors for the praphical presentation. | |
| wtWebGraphAirQualitySensorColorEntry | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3.1 | not-accessible | Numbers of the sensors. | |
| OCT wtWebGraphAirQualityGraphicsSensorColor | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3.1.1 | OCTET STRING | read-write | Color of the sensors at the praphical presention. |
| OCT wtWebGraphAirQualityGraphicsSelectScale | 1.3.6.1.4.1.5040.1.2.35.3.1.6.2.3.1.2 | OCTET STRING | read-write | Assignes one of 4 scales to a sensor: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Use Scale 1 Bit 1 : Use Scale 2 Bit 2 : Use Scale 3 Bit 3-7: unused |
| wtWebGraphAirQualityGraphicsScale | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3 | |||
| OCT wtWebGraphAirQualityGraphicsScaleAutoScaleEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.1 | OCTET STRING | read-write | Select the Auto Scale Mode: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto scale enable Bit 1 : Scale 2 Auto scale enable Bit 2 : Scale 3 Auto scale enable Bit 3-7: unused |
| OCT wtWebGraphAirQualityGraphicsScaleAutoFitEnable | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.2 | OCTET STRING | read-write | Select the Auto Fit Mode:: Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : Scale 1 Auto fit enable Bit 1 : Scale 2 Auto fit enable Bit 2 : Scale 3 Auto fit enable Bit 3-7: unused |
| INT wtWebGraphAirQualityGraphicsScale1Min | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.3 | INTEGER | read-only | Scale 1: Minimum. |
| INT wtWebGraphAirQualityGraphicsScale2Min | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.4 | INTEGER | read-only | Scale 2: Minimum. |
| INT wtWebGraphAirQualityGraphicsScale3Min | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.5 | INTEGER | read-only | Scale 3: Minimum. |
| INT wtWebGraphAirQualityGraphicsScale4Min | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.6 | INTEGER | read-only | Scale 4: Minimum. |
| INT wtWebGraphAirQualityGraphicsScale1Max | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.7 | INTEGER | read-only | Scale 1: Maximum. |
| INT wtWebGraphAirQualityGraphicsScale2Max | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.8 | INTEGER | read-only | Scale 2: Maximum. |
| INT wtWebGraphAirQualityGraphicsScale3Max | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.9 | INTEGER | read-only | Scale 3: Maximum. |
| INT wtWebGraphAirQualityGraphicsScale4Max | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.10 | INTEGER | read-only | Scale 4: Maximum. |
| OCT wtWebGraphAirQualityGraphicsScale1Unit | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.11 | OCTET STRING | read-only | Scale 1: Unit. |
| OCT wtWebGraphAirQualityGraphicsScale2Unit | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.12 | OCTET STRING | read-only | Scale 2: Unit. |
| OCT wtWebGraphAirQualityGraphicsScale3Unit | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.13 | OCTET STRING | read-only | Scale 3: Unit. |
| OCT wtWebGraphAirQualityGraphicsScale4Unit | 1.3.6.1.4.1.5040.1.2.35.3.1.6.3.14 | OCTET STRING | read-only | Scale 4: Unit. |
| wtWebGraphAirQualityPorts | 1.3.6.1.4.1.5040.1.2.35.3.2 | |||
| wtWebGraphAirQualityPortTable | 1.3.6.1.4.1.5040.1.2.35.3.2.1 | not-accessible | List of settings depending on the sensor number. | |
| wtWebGraphAirQualityPortEntry | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1 | not-accessible | Sensor parameters for the individual sensors. | |
| OCT wtWebGraphAirQualityPortName | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.1 | OCTET STRING | read-write | Name of the sensor. |
| OCT wtWebGraphAirQualityPortText | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.2 | OCTET STRING | read-write | Description of the sensor. |
| OCT wtWebGraphAirQualityPortOffset1 | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.3 | OCTET STRING | read-write | Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 1. |
| OCT wtWebGraphAirQualityPortTemperature1 | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.4 | OCTET STRING | read-write | Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityPortOffset2 | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.5 | OCTET STRING | read-write | Offset calibration: Offset in degrees with maximum 2 decimal places at temperature 2. |
| OCT wtWebGraphAirQualityPortTemperature2 | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.6 | OCTET STRING | read-write | Offset calibration: Reference temperature 1 in degrees with maximum 2 decimal places. |
| OCT wtWebGraphAirQualityPortComment | 1.3.6.1.4.1.5040.1.2.35.3.2.1.1.7 | OCTET STRING | read-write | Offset calibration: informations of date, name of operator, reference devices. |
| wtWebGraphAirQualityManufact | 1.3.6.1.4.1.5040.1.2.35.3.3 | |||
| OCT wtWebGraphAirQualityMfName | 1.3.6.1.4.1.5040.1.2.35.3.3.1 | OCTET STRING | read-write | Manufacturer company name |
| OCT wtWebGraphAirQualityMfAddr | 1.3.6.1.4.1.5040.1.2.35.3.3.2 | OCTET STRING | read-write | Manufacturer address. |
| OCT wtWebGraphAirQualityMfHotline | 1.3.6.1.4.1.5040.1.2.35.3.3.3 | OCTET STRING | read-write | Manufacturer hotline. |
| OCT wtWebGraphAirQualityMfInternet | 1.3.6.1.4.1.5040.1.2.35.3.3.4 | OCTET STRING | read-write | Manufacturer Internet address. |
| OCT wtWebGraphAirQualityMfDeviceTyp | 1.3.6.1.4.1.5040.1.2.35.3.3.5 | OCTET STRING | read-write | Manufacturer device name (model number). |
| OCT wtWebGraphAirQualityMfOrderNo | 1.3.6.1.4.1.5040.1.2.35.3.3.6 | OCTET STRING | read-write | Manufacturer part number. |
| wtWebGraphAirQualityDiag | 1.3.6.1.4.1.5040.1.2.35.4 | |||
| INT wtWebGraphAirQualityDiagErrorCount | 1.3.6.1.4.1.5040.1.2.35.4.1 | INTEGER | read-only | Number of entries in the error memory. |
| OCT wtWebGraphAirQualityDiagBinaryError | 1.3.6.1.4.1.5040.1.2.35.4.2 | OCTET STRING | read-only | Error causes coded bit-by-bit. |
| INT wtWebGraphAirQualityDiagErrorIndex | 1.3.6.1.4.1.5040.1.2.35.4.3 | INTEGER | read-write | The value of this variable is used as an index to read an error massege from wtWebGraphAirQualityDiagErrorMessage. Errors are numbered from 1 to wtWebGraphAirQualityDiagErrorCount. Writing a valid value into this variable, making the appropriate message readable from wtWebGraphAirQualityDiagErrorMessage. |
| OCT wtWebGraphAirQualityDiagErrorMessage | 1.3.6.1.4.1.5040.1.2.35.4.4 | OCTET STRING | read-only | Using wtWebGraphAirQualityDiagErrorIndex as an index, the appropriate message is available. |
| INT wtWebGraphAirQualityDiagErrorClear | 1.3.6.1.4.1.5040.1.2.35.4.5 | INTEGER | write-only | Writing 1 into this variable clears all diagnosis messages. |
RFC description
Manages air quality monitoring sensors and configurations in WebGraph environmental monitoring systems.
Start monitoring WebGraph networked environmental/air-quality sensor appliance (per-sensor reading/threshold-alarm status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.