WebGraph-OLD-Thermo-Hygrometer-US-MIB :: wtWebGraphThermHygroAlarmDelay

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › WebGraph-OLD-Thermo-Hygrometer-US-MIB › wtWebGraphThermHygroAlarmDelay

wtWebGraphThermHygroAlarmDelay

Module: WebGraph-OLD-Thermo-Hygrometer-US-MIB

OID (symbolic): WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmDelay

OID (numeric): 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5

Node type: OBJECT-TYPE

Type: OCTET STRING

Access: read-write

Description: Alarm will be delayed by setting this time while stable alarm condition occur (time in minutes).

What is wtWebGraphThermHygroAlarmDelay?

The number of minutes an alarm condition must persist continuously before the alarm actually fires. Setting this above zero filters out brief, transient excursions so only sustained out-of-range readings generate a notification.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5
snmpwalk -v2c -c public <target> WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmDelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5.1
snmpget -v2c -c public <target> WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmDelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5.1 s <value>

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> wtWebGraphThermHygroAlarmDelay.1

Start monitoring Wiesemann & Theis networked environmental sensors with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the WebGraph-OLD-Thermo-Hygrometer-US-MIB::wtWebGraphThermHygroAlarmDelay OID value, configure state conditions and alerts, and monitor any Wiesemann & Theis networked environmental sensors from a single console.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.5040wutCom-Server-Intern-MIB
1.3.6.1.4.1.5040.1wtComServerCom-Server-Intern-MIB
1.3.6.1.4.1.5040.1.2wtWebioWebGraph-8xThermometer-US-MIB
Numeric OIDNameModule
1.3.6.1.4.1.5040.1.2.9wtWebGraphThermHygroWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3wtWebGraphThermHygroConfigWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3.1wtWebGraphThermHygroDeviceWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3.1.5wtWebGraphThermHygroAlarmWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3.1.5.3wtWebGraphThermHygroAlarmTableWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1wtWebGraphThermHygroAlarmEntryWebGraph-OLD-Thermo-Hygrometer-US-MIB
1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.5wtWebGraphThermHygroAlarmDelayWebGraph-OLD-Thermo-Hygrometer-US-MIB