All MIBs › LIEBERT-SITENET-INTEGRATOR-MIB › envSummaryAlarm
envSummaryAlarm
Module: LIEBERT-SITENET-INTEGRATOR-MIB
OID (symbolic): LIEBERT-SITENET-INTEGRATOR-MIB::envSummaryAlarm
OID (numeric): 1.3.6.1.4.1.476.1.2.1.1.1.6.1
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The envSummaryAlarm varible will be 0 when no Digital Inputs are true and no other alarm conditions exist.
When alarms are active or Digital Inputs are true the value of envSummaryAlarm indicates which alarms and inputs are active as a sum of the values listed below:
DigitalInput1State true(1) 1 DigitalInput2State true(1) 2 DigitalInput3State true(1) 4 DigitalInput4State true(1) 8 DigitalInput5State true(1) 16 DigitalInput6State true(1) 32 DigitalInput7State true(1) 64 DigitalInput8State true(1) 128 DigitalInput9State true(1) 256 DigitalInput10State true(1) 512 Temperature1 above HighLimit 1024 Temperature1 below LowLimit 2048 Temperature2 above HighLimit 4096 Temperature2 below LowLimit 8192 Temperature3 above HighLimit 16384 Temperature3 below LowLimit 32768 Humidity1 above HighLimit 65536 Humidity1 below LowLimit 131072 Humidity2 above HighLimit 262144 Humidity2 below LowLimit 524288
What is envSummaryAlarm?
Reports 0 when no digital inputs are true and no other alarm condition exists, or otherwise a sum of documented bit values identifying which specific digital inputs and temperature/humidity limit conditions are currently active. An operator polls this single object as a quick overall health check instead of reading every individual input and sensor limit object.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.2.1.1.1.6.1 snmpwalk -v2c -c public <target> LIEBERT-SITENET-INTEGRATOR-MIB::envSummaryAlarm
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.2.1.1.1.6.1.1 snmpget -v2c -c public <target> LIEBERT-SITENET-INTEGRATOR-MIB::envSummaryAlarm.1
Start monitoring Liebert (Emerson/Vertiv) SiteNet Integrator environmental monitoring unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-SITENET-INTEGRATOR-MIB::envSummaryAlarm OID value, configure state conditions and alerts, and monitor any Liebert (Emerson/Vertiv) SiteNet Integrator environmental monitoring unit from a single console.
OID Breakdown
Upper-level ancestors (8 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.2 | liebertEnvironment | LIEBERT-SITENET-INTEGRATOR-MIB |
| 1.3.6.1.4.1.476.1.2.1 | leExtensions | LIEBERT-SITENET-INTEGRATOR-MIB |
| 1.3.6.1.4.1.476.1.2.1.1 | leSiteNet01 | LIEBERT-SITENET-INTEGRATOR-MIB |
| 1.3.6.1.4.1.476.1.2.1.1.1 | envMIB | LIEBERT-SITENET-INTEGRATOR-MIB |
| 1.3.6.1.4.1.476.1.2.1.1.1.6 | envAlarms | LIEBERT-SITENET-INTEGRATOR-MIB |
| 1.3.6.1.4.1.476.1.2.1.1.1.6.1 | envSummaryAlarm | LIEBERT-SITENET-INTEGRATOR-MIB |