| OID symbolic | OID numeric | Type | Access | Description |
| sysAlarmConfigEntry | 1.3.6.1.4.1.13858.8.4.1 | | not-accessible | An entry containing information applicable to a
particular temperature probe. |
| sysAlarmConfigTable | 1.3.6.1.4.1.13858.8.4 | | not-accessible | This table describes battery temperature probes. |
| STR sysAlarmCustomName | 1.3.6.1.4.1.13858.8.4.1.3 | DisplayString | read-write | A string identifying probe location. |
| STR sysAlarmDefaultName | 1.3.6.1.4.1.13858.8.4.1.2 | DisplayString | read-only | A string identifying probe location. |
| INT sysAlarmIndex | 1.3.6.1.4.1.13858.8.4.1.1 | INTEGER | read-only | Index into temperature table |
| INT sysAlarmOperStatus | 1.3.6.1.4.1.13858.8.4.1.6 | INTEGER | read-only | Indicates current alarm status |
| INT sysAlarmSeverity | 1.3.6.1.4.1.13858.8.4.1.4 | INTEGER | read-write | Alarm Severity as denoted by Major and Minor Alarm Mask |
| STR sysAlarmToRelayMapping | 1.3.6.1.4.1.13858.8.4.1.5 | DisplayString | read-write | No additional mapping = 0
Map to Relay A = 1
Map to Relay B = 2
Map to Relay C = 4
Map to Relay D = 8
Map to Relay E = 16
Map to Relay F = 32
Map to Relay A and B = (1 + 2) and so on
The major/minor classification of alarms automatically
associates it with Major/Minor relay. Assigning a null
mapping here does not override sysRelayAlarmSeverity for
the alarm.
It should be used to define mapping to additional relays. |
| valereDcPowerMgt | 1.3.6.1.4.1.13858 | | | MIB Version 2.0
History
Apr 26, 2007 Added SysAlarm Config Table Version 2.0
Feb 08, 2003 Changed vpwrTrapDestinationTable to vpwrTrapTable
Corrected entry for vpwrTrapTable to be VpwrTrapTableEntry
This fixes errors generated by MG-SOFT mib compiler.Ver1.0
Oct 30, 2002 initial release - version 0.4 |
| OID vpwrAlarmDescr | 1.3.6.1.4.1.13858.8.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The
object referenced should not be accessible, but rather
be used to provide a unique description of the alarm
condition. |
| vpwrAlarmEntry | 1.3.6.1.4.1.13858.8.2.1 | | not-accessible | An entry containing information applicable to a
particular alarm. |
| NUM vpwrAlarmIndex | 1.3.6.1.4.1.13858.8.2.1.1 | PositiveInteger | read-only | Identifies the alarm associated with the module.
It is unique on per module type basis. For example,
multiple rectifiers can have the same alarm and therefore same
vpwrAlarmIndex active at any one time. |
| G32 vpwrAlarmsPresentEx | 1.3.6.1.4.1.13858.8.1 | Gauge32 | read-only | The present number of active alarm conditions. |
| vpwrAlarmTable | 1.3.6.1.4.1.13858.8.2 | | not-accessible | A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains.
The vpwrAlarmIndex, for each type of module starts at 1
and is limited by the total number of alarams that can be
generated by the module.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), vpwrAlarmDescr, to allow a single table to
reflect alarms for different type of modules.
The number of rows in the table at any given time is
reflected by the value of vpwrAlarmsPresent. |
| TIM vpwrAlarmTime | 1.3.6.1.4.1.13858.8.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was
detected. |
| INT vpwrBatteryTemp | 1.3.6.1.4.1.13858.7.1.1.1.3 | INTEGER | read-only | Current temperature as recorded by the probe. |
| vpwrBatteryTempGroup | 1.3.6.1.4.1.13858.7.1 | | | |
| INT vpwrBatteryTempIndex | 1.3.6.1.4.1.13858.7.1.1.1.1 | INTEGER | read-only | Index into temperature table |
| INT vpwrBatteryTempLThreshold | 1.3.6.1.4.1.13858.7.1.2 | INTEGER | read-write | Temperature value at which a clear trap would be sent.
All three battery temperature must be at or below this value
to trigger this trap. |
| STR vpwrBatteryTempName | 1.3.6.1.4.1.13858.7.1.1.1.2 | DisplayString | read-write | A string identifying probe location. |
| vpwrBatteryTempTable | 1.3.6.1.4.1.13858.7.1.1 | | not-accessible | This table describes battery temperature probes. |
| vpwrBatteryTempTableEntry | 1.3.6.1.4.1.13858.7.1.1.1 | | not-accessible | An entry containing information applicable to a
particular temperature probe. |
| INT vpwrBatteryTempUThreshold | 1.3.6.1.4.1.13858.7.1.3 | INTEGER | read-write | Temperature value at which a set trap would be sent.
Any one of the three battery temperatures at or exceeding this limit
would trigger the trap. |
| vpwrDcPowerAlarmGroup | 1.3.6.1.4.1.13858.8 | | | |
| vpwrDcPowerBatteryGroup | 1.3.6.1.4.1.13858.7 | | | |
| vpwrDcPowerLvd | 1.3.6.1.4.1.13858.4 | | | |
| vpwrDcPowerModuleIdent | 1.3.6.1.4.1.13858.6 | | | |
| vpwrDcPowerProducts | 1.3.6.1.4.1.13858.1 | | | |
| vpwrDcPowerRectifier | 1.3.6.1.4.1.13858.3 | | | |
| vpwrDcPowerSnmpConfig | 1.3.6.1.4.1.13858.9 | | | |
| vpwrDcPowerSystem | 1.3.6.1.4.1.13858.2 | | | |
| vpwrDcPowerTest | 1.3.6.1.4.1.13858.5 | | | |
| vpwrDcPowerTraps | 1.3.6.1.4.1.13858.10 | | | |
| vpwrDcPowerTrapsMsgString | 1.3.6.1.4.1.13858.11 | | | |
| STR vpwrIdentAgentSoftwareVersion | 1.3.6.1.4.1.13858.2.1.4 | DisplayString | read-only | The SNMP agent software version. This variable may or
may not have the same value as
vpwrIdentControllerFirmwareVersion. |
| STR vpwrIdentControllerVersion | 1.3.6.1.4.1.13858.2.1.3 | DisplayString | read-only | The hardware/firmware version(s). This variable
may or may not have the same value as
vpwrIdentAgentSoftwareVersion. |
| STR vpwrIdentManufacturer | 1.3.6.1.4.1.13858.2.1.1 | DisplayString | read-only | The name of the DC Power manufacturer. |
| STR vpwrIdentModel | 1.3.6.1.4.1.13858.2.1.2 | DisplayString | read-only | The DC Power Model designation. |
| STR vpwrIdentName | 1.3.6.1.4.1.13858.2.1.5 | DisplayString | read-write | A string identifying the system. This object should be
set by the administrator. |
| vpwrLvdAlarmCBOpen | 1.3.6.1.4.1.13858.4.2.2 | | | Circuit Breaker open |
| vpwrLvdAlarmContactorOpen | 1.3.6.1.4.1.13858.4.2.1 | | | Contactor open |
| vpwrLvdAlarmGroup | 1.3.6.1.4.1.13858.4.2 | | | |
| vpwrLvdAlarmWarning | 1.3.6.1.4.1.13858.4.2.4 | | | Plant Voltage below warning threshold |
| vpwrLvdConfigGroup | 1.3.6.1.4.1.13858.4.1 | | | |
| INT vpwrLvdDisconnectSetpoint | 1.3.6.1.4.1.13858.4.1.2 | INTEGER | read-write | LVD disconnect voltage setpoint. |
| INT vpwrLvdReconnectDelayTimer | 1.3.6.1.4.1.13858.4.1.4 | INTEGER | read-write | The delay time, in seconds, before LVD is reconnected |
| INT vpwrLvdReconnectSetpoint | 1.3.6.1.4.1.13858.4.1.3 | INTEGER | read-write | LVD Reconnect voltage setpoint. |
| vpwrLvdTestGroup | 1.3.6.1.4.1.13858.4.3 | | | |
| INT vpwrLvdWarningSetpoint | 1.3.6.1.4.1.13858.4.1.1 | INTEGER | read-write | LVD Warning voltage setpoint. |
| INT vpwrModuleCapacity | 1.3.6.1.4.1.13858.2.1.6.1.6 | INTEGER | read-only | The meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Capacity for Rectifier module.
- Not Applicable for LVD module |
| NUM vpwrModuleIndex | 1.3.6.1.4.1.13858.2.1.6.1.2 | PositiveInteger | read-only | This object identifies the module by its position in the shelf.
Module numbering starts from the controller/expansion controller end of
the shelf.
So, the module in the first slot has an index of 1, the next module
is 2 and so on.
Under the current scheme
- Rectifier module can have a number between 1 and 5.
- LVD module starts with an index of 6. |
| OID vpwrModuleOID | 1.3.6.1.4.1.13858.2.1.6.1.3 | OBJECT IDENTIFIER | read-only | It indicates the type of the module by specifiying its OID |
| INT vpwrModuleOperStatus | 1.3.6.1.4.1.13858.2.1.6.1.5 | INTEGER | read-only | This object indicates current over all status of the module. |
| INT vpwrModuleParameter | 1.3.6.1.4.1.13858.2.1.6.1.4 | INTEGER | read-only | The meaning of this object depends upon the module type
which is indicated by vpwrModuleOID as follows
- Current for Rectifier module.
- Not Applicable for LVD module |
| vpwrRectAlarmACFail | 1.3.6.1.4.1.13858.3.2.3 | | | |
| vpwrRectAlarmAmbTemp | 1.3.6.1.4.1.13858.3.2.6 | | | |
| vpwrRectAlarmBoostComm | 1.3.6.1.4.1.13858.3.2.16 | | | |
| vpwrRectAlarmBoostFail | 1.3.6.1.4.1.13858.3.2.2 | | | |
| vpwrRectAlarmDCEnable | 1.3.6.1.4.1.13858.3.2.12 | | | |
| vpwrRectAlarmDCFail | 1.3.6.1.4.1.13858.3.2.1 | | | |
| vpwrRectAlarmFanFail | 1.3.6.1.4.1.13858.3.2.5 | | | |
| vpwrRectAlarmHVSD | 1.3.6.1.4.1.13858.3.2.4 | | | |
| vpwrRectAlarmIntTemp | 1.3.6.1.4.1.13858.3.2.7 | | | |
| vpwrRectAlarmIShare | 1.3.6.1.4.1.13858.3.2.8 | | | |
| vpwrRectAlarmLowVoltage | 1.3.6.1.4.1.13858.3.2.10 | | | |
| vpwrRectAlarmModDisableShutdown | 1.3.6.1.4.1.13858.3.2.14 | | | |
| vpwrRectAlarmRemoteShutdown | 1.3.6.1.4.1.13858.3.2.13 | | | |
| vpwrRectAlarmReserved | 1.3.6.1.4.1.13858.3.2.11 | | | |
| vpwrRectAlarmShortPinShutdown | 1.3.6.1.4.1.13858.3.2.15 | | | |
| vpwrRectAlarmUV | 1.3.6.1.4.1.13858.3.2.9 | | | |
| vpwrRectifierAlarmGroup | 1.3.6.1.4.1.13858.3.2 | | | |
| vpwrRectifierConfigGroup | 1.3.6.1.4.1.13858.3.1 | | | |
| INT vpwrRectifierFVSetpoint | 1.3.6.1.4.1.13858.3.1.1 | INTEGER | read-write | System Float Voltage setting |
| INT vpwrRectifierHVSDSetpoint | 1.3.6.1.4.1.13858.3.1.2 | INTEGER | read-write | System High Voltage Shutdown voltage setting |
| vpwrRectifierTestGroup | 1.3.6.1.4.1.13858.3.3 | | | |
| NUM vpwrShelfIndex | 1.3.6.1.4.1.13858.2.1.6.1.1 | PositiveInteger | read-only | Identifies shelf number that this module belongs to.
The possible values are 1 through 16 limited by vpwrSystemShelfCapacity.
The shelf that contains the controller is identified as shelf number 1. |
| INT vpwrSystemBDAlarmSetpoint | 1.3.6.1.4.1.13858.2.2.7 | INTEGER | read-write | System Battery Discharge voltage setting. |
| vpwrSystemConfigGroup | 1.3.6.1.4.1.13858.2.2 | | | |
| INT vpwrSystemControllerState | 1.3.6.1.4.1.13858.2.3.4 | INTEGER | read-only | Current System state as shown on the enhanced display. |
| INT vpwrSystemCurrent | 1.3.6.1.4.1.13858.2.3.3 | INTEGER | read-only | The current system current. |
| INT vpwrSystemHVAlarmSetpoint | 1.3.6.1.4.1.13858.2.2.6 | INTEGER | read-write | System High voltage alarm voltage setting. |
| vpwrSystemIdentEntry | 1.3.6.1.4.1.13858.2.1.6.1 | | not-accessible | An entry containing information applicable to a
particular module making up the system. |
| vpwrSystemIdentGroup | 1.3.6.1.4.1.13858.2.1 | | | |
| vpwrSystemIdentTable | 1.3.6.1.4.1.13858.2.1.6 | | not-accessible | This table describes shelves and modules
that make up the sysetm. |
| INT vpwrSystemInternalTemperature | 1.3.6.1.4.1.13858.2.3.5 | INTEGER | read-only | The current controller internal temperature. |
| INT vpwrSystemInternalTempLThreshold | 1.3.6.1.4.1.13858.2.2.8 | INTEGER | read-write | Temperature value at which temperature compensation inactive (clear)
trap would be sent if temperature compensation was active when this
value is reached. |
| INT vpwrSystemInternalTempUThreshold | 1.3.6.1.4.1.13858.2.2.9 | INTEGER | read-write | Temperature value at which temperature compensation active (set) trap
would be sent. |
| vpwrSystemParameterGroup | 1.3.6.1.4.1.13858.2.3 | | | |
| INT vpwrSystemShelfCapacity | 1.3.6.1.4.1.13858.2.3.1 | INTEGER | read-only | It describes the maximum number of shelves that can/are controlled
by the controller. Each shelf is uniquely numbered in the range
from 1 to vpwrShelfCapacity. |
| INT vpwrSystemTempCompensation | 1.3.6.1.4.1.13858.2.2.1 | INTEGER | read-write | This parameter enables/disables temperature compensation. |
| INT vpwrSystemTempCompensationSlope | 1.3.6.1.4.1.13858.2.2.4 | INTEGER | read-write | The rate at which float voltage is changed, within the specified limits,
when temperature compensation is active. |
| INT vpwrSystemTempCompensationState | 1.3.6.1.4.1.13858.2.3.6 | INTEGER | read-only | Active or Inactive. Applicable only if temperature compensation is enabled.
This means that the controller is temperature compensating the float voltage. |
| INT vpwrSystemTempCompStartTemperature | 1.3.6.1.4.1.13858.2.2.2 | INTEGER | read-write | The temperature at which temperature compensation becomes
active. |
| INT vpwrSystemTempCompStopVoltage | 1.3.6.1.4.1.13858.2.2.3 | INTEGER | read-write | When temperature compensation is active, vpwrSystemTempCompStopVoltage is the
limit to which float voltage will be reduced.
For example, to set this voltage to 51.75 volts enter a value of 5175. |
| INT vpwrSystemThermalSenseType | 1.3.6.1.4.1.13858.2.2.5 | INTEGER | read-write | This parameter selects the temperature sensing point for temperature
compensation (in)activation. |
| INT vpwrSystemType | 1.3.6.1.4.1.13858.2.3.7 | INTEGER | read-only | This parameter describes the type of the system being managed.
This object is set by Valere Power Inc. |
| INT vpwrSystemVoltage | 1.3.6.1.4.1.13858.2.3.2 | INTEGER | read-only | The current system voltage. |
| NTF vpwrTrapACFAlarm | 1.3.6.1.4.1.13858.10.0.3 | | | AC Fail Alarm |
| NTF vpwrTrapAuxAlarm | 1.3.6.1.4.1.13858.10.0.10 | | | Auxiliary System Alarm |
| NTF vpwrTrapBatteryTempAlarmCleared | 1.3.6.1.4.1.13858.10.0.25 | | | All Battery Temperatures within limits |
| NTF vpwrTrapBatteryTempAlarmSet | 1.3.6.1.4.1.13858.10.0.24 | | | At least one Battery Temperature exceeded upper threshold. |
| NTF vpwrTrapBDAlarm | 1.3.6.1.4.1.13858.10.0.6 | | | Battery on Discharge Alarm |
| INT vpwrTrapCriticality | 1.3.6.1.4.1.13858.9.1.1.3 | INTEGER | read-write | Criticality of traps sent to this IP Address |
| NTF vpwrTrapDistAlarm | 1.3.6.1.4.1.13858.10.0.9 | | | Distribution Open Alarm |
| NTF vpwrTrapHVAlarm | 1.3.6.1.4.1.13858.10.0.4 | | | High Voltage Warning Alarm |
| NTF vpwrTrapHVSDAlarm | 1.3.6.1.4.1.13858.10.0.5 | | | High Voltage Shutdown Alarm |
| NTF vpwrTrapInternalTempAlarmCleared | 1.3.6.1.4.1.13858.10.0.23 | | | Internal Temperature within limits |
| NTF vpwrTrapInternalTempAlarmSet | 1.3.6.1.4.1.13858.10.0.22 | | | Internal Temperature upper threshold exceeded. |
| IP vpwrTrapIpAddress | 1.3.6.1.4.1.13858.9.1.1.2 | IpAddress | read-write | Trap destination IP Address |
| INT vpwrTrapIpIndex | 1.3.6.1.4.1.13858.9.1.1.1 | INTEGER | read-only | Trap Entry Index |
| NTF vpwrTrapIShareAlarm | 1.3.6.1.4.1.13858.10.0.12 | | | Rectifier Current Share Alarm |
| vpwrTrapLvdFuseOpen | 1.3.6.1.4.1.13858.4.2.3 | | | Fuse open |
| NTF vpwrTrapLVDOpenAlarm | 1.3.6.1.4.1.13858.10.0.8 | | | LVD Open Alarm |
| NTF vpwrTrapLVDWarningAlarm | 1.3.6.1.4.1.13858.10.0.7 | | | LVD Warning Alarm |
| NTF vpwrTrapModuleCommAlarm | 1.3.6.1.4.1.13858.10.0.15 | | | Module Communication Alarm |
| NTF vpwrTrapModuleFailAlarm | 1.3.6.1.4.1.13858.10.0.13 | | | Single Rectifier Fail Alarm |
| NTF vpwrTrapModuleInserted | 1.3.6.1.4.1.13858.10.0.18 | | | A new module has been inserted into the system. |
| NTF vpwrTrapModuleRemoved | 1.3.6.1.4.1.13858.10.0.19 | | | A module has been removed from the system. |
| NTF vpwrTrapMultipleModuleFailAlarm | 1.3.6.1.4.1.13858.10.0.14 | | | Multiple Rectifier Fail Alarm |
| NTF vpwrTrapPowerMajorAlarm | 1.3.6.1.4.1.13858.10.0.1 | | | Major Alarm |
| NTF vpwrTrapPowerMinorAlarm | 1.3.6.1.4.1.13858.10.0.2 | | | Minor Alarm |
| STR vpwrTrapsMsgString | 1.3.6.1.4.1.13858.11.1 | DisplayString | not-accessible | Place holder for trap notification message string |
| NTF vpwrTrapSystemOK | 1.3.6.1.4.1.13858.10.0.17 | | | SYSTEM OK - No Active Alarms |
| NTF vpwrTrapSystemOverTemperatureAlarm | 1.3.6.1.4.1.13858.10.0.16 | | | System Over Temperature Alarm |
| NTF vpwrTrapSystemRedundancyAlarm | 1.3.6.1.4.1.13858.10.0.11 | | | System Redundant Capacity Alarm |
| vpwrTrapTable | 1.3.6.1.4.1.13858.9.1 | | not-accessible | A list of possible trap destinations depending upon
the criticality of the trap. |
| vpwrTrapTableEntry | 1.3.6.1.4.1.13858.9.1.1 | | not-accessible | An entry containing information applicable to a
particular trap destination. |
| NTF vpwrTrapThermalCompActive | 1.3.6.1.4.1.13858.10.0.20 | | | Thermal compensation has become active. |
| NTF vpwrTrapThermalCompInactive | 1.3.6.1.4.1.13858.10.0.21 | | | Thermal compensation has been de-activated. |