All MIBs › SITEBOSS-220-STD-MIB
Organization: Asentria Corporation
Last Updated: 2013-06-13
Category: Data Center Infrastructure Monitoring, Remote Site Monitoring
Description: Manages Asentria SiteBoss 220 remote site monitor I/O sensors, alarms, and event notifications.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is SITEBOSS-220-STD-MIB?
SITEBOSS-220-STD-MIB is the vendor MIB for Asentria's SiteBoss 220, a remote telemetry/monitoring unit deployed at unmanned or remote facility sites (cell towers, equipment cabinets, utility huts) to watch environmental and equipment conditions. It exposes a table of monitored 'points' (esPointTable) representing individual analog or digital sensor inputs, each with a name, current integer or string value, and event/alarm state, plus a related table of temperature-point configuration. Its core purpose is hardware and environmental status monitoring: it reports whether a given input point (e.g., a door contact, temperature probe, humidity sensor, or power-fail signal) is in an alarm event state, and what its current numeric or textual reading is, making it central to detecting equipment-room conditions like overheating, power loss, or intrusion. There is no strong evidence of dependency on other standard MIBs beyond generic SNMP conventions, as SiteBoss units are largely self-contained monitoring appliances. It is deployed in remote site monitoring contexts (telecom huts, cabinets, utility sites) where operators need centralized alarm visibility across many unattended locations. Engineers can download the SITEBOSS-220-STD-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in SITEBOSS-220-STD-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Asentria SiteBoss 220 remote site monitor
Monitoring Examples
An administrator polls esPointTable / esPointEntry, using esIndexES/esIndexPC/esIndexPoint to identify a specific sensor point, and checks esPointName alongside esPointInEventState to see if that point (e.g., a temperature sensor) is currently in an alarm condition. esPointValueInt or esPointValueStr gives the actual sensor reading (such as a temperature in degrees), and cross-referencing esPointConfigTempTable / esPointConfigTempEntry (via espcTempIndexES) reveals the configured alarm thresholds, letting the admin confirm whether a reported high temperature genuinely exceeds the configured limit or is a false alarm.
What Can Be Monitored
- sensor/point alarm event state
- sensor value (temperature, contact, etc.)
- point naming/identification
- temperature threshold configuration
This MIB depends on
Related MIBs
Imported Objects
From ASENTRIA-ROOT-MIB
| asentria | MODULE-IDENTITY |
From SNMPv2-SMI
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| TimeTicks |
From SNMPv2-TC
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| s220 | 1.3.6.1.4.1.3052.43 | MIB module for managing Asentria SiteBoss 220 | ||
| notification | 1.3.6.1.4.1.3052.43.0 | |||
| status | 1.3.6.1.4.1.3052.43.1 | |||
| eventSensorStatus | 1.3.6.1.4.1.3052.43.1.1 | |||
| esPointTable | 1.3.6.1.4.1.3052.43.1.1.1 | not-accessible | This table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, relay 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). | |
| esPointEntry | 1.3.6.1.4.1.3052.43.1.1.1.1 | not-accessible | Entry for EventSensor point table | |
| I32 esIndexES | 1.3.6.1.4.1.3052.43.1.1.1.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. |
| I32 esIndexPC | 1.3.6.1.4.1.3052.43.1.1.1.1.2 | Integer32 | read-only | The part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=relay |
| I32 esIndexPoint | 1.3.6.1.4.1.3052.43.1.1.1.1.3 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or relay) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3. |
| STR esPointName | 1.3.6.1.4.1.3052.43.1.1.1.1.4 | DisplayString | read-write | The name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as ''. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as ''. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name. |
| I32 esPointInEventState | 1.3.6.1.4.1.3052.43.1.1.1.1.5 | Integer32 | read-write | A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures the values of this object are: 1=point in event state 2=point in normal state For relays the values of this object are: 1=relay energized (active) 2=relay de-energized (inactive) For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its active (energized) state. Setting it to 2 puts the relay into its inactive (de-energized) state. Setting it to any value greater than 2 puts the relay into its active state for that many seconds (up to 3600), after which time it puts the relay into its inactive state. |
| I32 esPointValueInt | 1.3.6.1.4.1.3052.43.1.1.1.1.6 | Integer32 | read-write | A read-only number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. If the point class is relay, then this object is either 1 (active a.k.a. energized) or 0 (inactive a.k.a. de-energized). This object cannot be used to control the relay (use esPointInEventState for that). |
| STR esPointValueStr | 1.3.6.1.4.1.3052.43.1.1.1.1.7 | DisplayString | read-only | A string referring to the value of a point on an EventSensor. For contact closures this object is either 'Open' or 'Closed'. For relays this object is either 'Active' (energized) or 'Inactive' (de-energized). For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in the configured units appended with the unit name. |
| config | 1.3.6.1.4.1.3052.43.2 | |||
| eventSensorPointConfig | 1.3.6.1.4.1.3052.43.2.2 | |||
| esPointConfigTempTable | 1.3.6.1.4.1.3052.43.2.2.1 | not-accessible | This table organizes 3 basic attributes of temperature sensor points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for temp sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor within the context of this emperature point config table ; namely, which EventSensor, and which sensor (a.k.a. point) (always 1 for temperature sensors). | |
| esPointConfigTempEntry | 1.3.6.1.4.1.3052.43.2.2.1.1 | not-accessible | Entry for EventSensor point config temperature table | |
| I32 espcTempIndexES | 1.3.6.1.4.1.3052.43.2.2.1.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config temperature table; namely, which EventSensor, and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor. |
| I32 espcTempIndexPoint | 1.3.6.1.4.1.3052.43.2.2.1.1.2 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with espcTempIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of temperature point configuration. |
| STR espcTempEnable | 1.3.6.1.4.1.3052.43.2.2.1.1.3 | DisplayString | read-write | ON/OFF enable this temperature sensor |
| STR espcTempName | 1.3.6.1.4.1.3052.43.2.2.1.1.4 | DisplayString | read-write | The name of this temperature sensor |
| STR espcTempScale | 1.3.6.1.4.1.3052.43.2.2.1.1.5 | DisplayString | read-write | Scale (C/F) for this temperature sensor |
| I32 espcTempDeadband | 1.3.6.1.4.1.3052.43.2.2.1.1.6 | Integer32 | read-write | Deadband for this temperature sensor |
| I32 espcTempVHighTemp | 1.3.6.1.4.1.3052.43.2.2.1.1.7 | Integer32 | read-write | Very high temperature event threshold for this temperature sensor |
| STR espcTempVHighClass | 1.3.6.1.4.1.3052.43.2.2.1.1.9 | DisplayString | read-write | Very high temperature event class for this temperature sensor |
| I32 espcTempHighTemp | 1.3.6.1.4.1.3052.43.2.2.1.1.10 | Integer32 | read-write | High temperature event threshold for this temperature sensor |
| STR espcTempHighClass | 1.3.6.1.4.1.3052.43.2.2.1.1.13 | DisplayString | read-write | High temperature event class for this temperature sensor |
| I32 espcTempLowTemp | 1.3.6.1.4.1.3052.43.2.2.1.1.17 | Integer32 | read-write | Low temperature event threshold for this temperature sensor |
| STR espcTempLowClass | 1.3.6.1.4.1.3052.43.2.2.1.1.20 | DisplayString | read-write | Low temperature event class for this temperature sensor |
| I32 espcTempVLowTemp | 1.3.6.1.4.1.3052.43.2.2.1.1.21 | Integer32 | read-write | Very Low temperature event threshold for this temperature sensor |
| STR espcTempVLowClass | 1.3.6.1.4.1.3052.43.2.2.1.1.24 | DisplayString | read-write | Very Low temperature event class for this temperature sensor |
| STR espcTempActions | 1.3.6.1.4.1.3052.43.2.2.1.1.25 | DisplayString | read-write | Temperature event Action |
| esPointConfigCCTable | 1.3.6.1.4.1.3052.43.2.2.2 | not-accessible | This table organizes 3 basic attributes of contact closure points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this contact closure point config table ; namely, which EventSensor and which sensor. | |
| esPointConfigCCEntry | 1.3.6.1.4.1.3052.43.2.2.2.1 | not-accessible | Entry for EventSensor point config contact closure table | |
| I32 espcCCIndexES | 1.3.6.1.4.1.3052.43.2.2.2.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. |
| I32 espcCCIndexPoint | 1.3.6.1.4.1.3052.43.2.2.2.1.2 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with espcCCIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration. |
| STR espcCCEnable | 1.3.6.1.4.1.3052.43.2.2.2.1.3 | DisplayString | read-write | ON/OFF enable for this contact closure |
| STR espcCCName | 1.3.6.1.4.1.3052.43.2.2.2.1.4 | DisplayString | read-write | Name for this contact closure |
| STR espcCCEventState | 1.3.6.1.4.1.3052.43.2.2.2.1.5 | DisplayString | read-write | Event state for this contact closure |
| I32 espcCCThreshold | 1.3.6.1.4.1.3052.43.2.2.2.1.6 | Integer32 | read-write | Threshold (seconds) for this contact closure |
| STR espcCCActions | 1.3.6.1.4.1.3052.43.2.2.2.1.7 | DisplayString | read-write | Event class for this contact closure |
| STR espcCCEventClass | 1.3.6.1.4.1.3052.43.2.2.2.1.9 | DisplayString | read-write | Event class for this contact closure |
| STR espcCCNormalClass | 1.3.6.1.4.1.3052.43.2.2.2.1.12 | DisplayString | read-write | Return-to-normal class for this contact closure |
| STR espcCCAlarmAlias | 1.3.6.1.4.1.3052.43.2.2.2.1.13 | DisplayString | read-write | Event alias for this contact closure |
| STR espcCCNormalAlias | 1.3.6.1.4.1.3052.43.2.2.2.1.14 | DisplayString | read-write | Return-to-normal alias for this contact closure |
| esPointConfigHumidTable | 1.3.6.1.4.1.3052.43.2.2.3 | not-accessible | This table organizes 3 basic attributes of humidity points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number (always 1 for humidity sensors) Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this humidity point config table ; namely, which EventSensor and which sensor. | |
| esPointConfigHumidEntry | 1.3.6.1.4.1.3052.43.2.2.3.1 | not-accessible | Entry for EventSensor point config humidity table | |
| I32 espcHumidIndexES | 1.3.6.1.4.1.3052.43.2.2.3.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. |
| I32 espcHumidIndexPoint | 1.3.6.1.4.1.3052.43.2.2.3.1.2 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with espcHumidIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration. |
| STR espcHumidEnable | 1.3.6.1.4.1.3052.43.2.2.3.1.3 | DisplayString | read-write | ON/OFF enable for this humidity sensor |
| STR espcHumidName | 1.3.6.1.4.1.3052.43.2.2.3.1.4 | DisplayString | read-write | The name for this humidity sensor |
| I32 espcHumidDeadband | 1.3.6.1.4.1.3052.43.2.2.3.1.5 | Integer32 | read-write | Deadband for this humidity sensor |
| I32 espcHumidVHighHumid | 1.3.6.1.4.1.3052.43.2.2.3.1.6 | Integer32 | read-write | Very high event threshold for this humidity sensor |
| STR espcHumidVHighClass | 1.3.6.1.4.1.3052.43.2.2.3.1.8 | DisplayString | read-write | Very high event class for this humidity sensor |
| I32 espcHumidHighHumid | 1.3.6.1.4.1.3052.43.2.2.3.1.9 | Integer32 | read-write | High event threshold for this humidity sensor |
| STR espcHumidHighClass | 1.3.6.1.4.1.3052.43.2.2.3.1.12 | DisplayString | read-write | High event class for this humidity sensor |
| I32 espcHumidLowHumid | 1.3.6.1.4.1.3052.43.2.2.3.1.16 | Integer32 | read-write | Low event threshold for this humidity sensor |
| STR espcHumidLowClass | 1.3.6.1.4.1.3052.43.2.2.3.1.19 | DisplayString | read-write | Low event class for this humidity sensor |
| I32 espcHumidVLowHumid | 1.3.6.1.4.1.3052.43.2.2.3.1.20 | Integer32 | read-write | Very low event threshold for this humidity sensor |
| STR espcHumidVLowClass | 1.3.6.1.4.1.3052.43.2.2.3.1.23 | DisplayString | read-write | Very low event class for this humidity sensor |
| STR espcHumidActions | 1.3.6.1.4.1.3052.43.2.2.3.1.24 | DisplayString | read-write | Humidity event actions for this humidity sensor |
| esPointConfigAITable | 1.3.6.1.4.1.3052.43.2.2.5 | not-accessible | This table organizes 3 basic attributes of analog input points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this analog input point config table ; namely, which EventSensor and which sensor. | |
| esPointConfigAIEntry | 1.3.6.1.4.1.3052.43.2.2.5.1 | not-accessible | Entry for EventSensor point config analog input table | |
| I32 espcAIIndexES | 1.3.6.1.4.1.3052.43.2.2.5.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config contact closure table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. |
| I32 espcAIIndexPoint | 1.3.6.1.4.1.3052.43.2.2.5.1.2 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with espcAIIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of contact closure point configuration. |
| STR espcAIEnable | 1.3.6.1.4.1.3052.43.2.2.5.1.3 | DisplayString | read-write | ON/OFF for this analog input sensor |
| STR espcAIName | 1.3.6.1.4.1.3052.43.2.2.5.1.4 | DisplayString | read-write | Name for this analog input sensor |
| I32 espcAIDeadband | 1.3.6.1.4.1.3052.43.2.2.5.1.5 | Integer32 | read-write | Deadband for this analog input sensor |
| I32 espcAIVhighValue | 1.3.6.1.4.1.3052.43.2.2.5.1.6 | Integer32 | read-write | Very high event threshold (decivolts or tenths of milliamps) for this analog input sensor |
| STR espcAIVhighClass | 1.3.6.1.4.1.3052.43.2.2.5.1.8 | DisplayString | read-write | Very high event class for this analog input sensor |
| I32 espcAIHighValue | 1.3.6.1.4.1.3052.43.2.2.5.1.9 | Integer32 | read-write | High event threshold (decivolts or tenths of milliamps) for this analog input sensor |
| STR espcAIHighClass | 1.3.6.1.4.1.3052.43.2.2.5.1.12 | DisplayString | read-write | High event class for this analog input sensor |
| I32 espcAILowValue | 1.3.6.1.4.1.3052.43.2.2.5.1.16 | Integer32 | read-write | Low event threshold (decivolts or tenths of milliamps) for this analog input sensor |
| STR espcAILowClass | 1.3.6.1.4.1.3052.43.2.2.5.1.19 | DisplayString | read-write | Low event class for this analog input sensor |
| I32 espcAIVlowValue | 1.3.6.1.4.1.3052.43.2.2.5.1.20 | Integer32 | read-write | Very low event threshold (decivolts or tenths of milliamps) for this analog input sensor |
| STR espcAIVlowClass | 1.3.6.1.4.1.3052.43.2.2.5.1.23 | DisplayString | read-write | Very low event class for this analog input sensor |
| STR espcAIActions | 1.3.6.1.4.1.3052.43.2.2.5.1.24 | DisplayString | read-write | Event actions for this analog input sensor |
| STR espcAIConvUnitName | 1.3.6.1.4.1.3052.43.2.2.5.1.25 | DisplayString | read-write | Conversion unit name for this analog input sensor |
| I32 espcAIConvLowValue | 1.3.6.1.4.1.3052.43.2.2.5.1.26 | Integer32 | read-write | Conversion low value for this analog input sensor |
| I32 espcAIConvLowUnit | 1.3.6.1.4.1.3052.43.2.2.5.1.27 | Integer32 | read-write | Conversion low unit value for this analog input sensor |
| I32 espcAIConvHighValue | 1.3.6.1.4.1.3052.43.2.2.5.1.28 | Integer32 | read-write | Conversion high value for this analog input sensor |
| I32 espcAIConvHighUnit | 1.3.6.1.4.1.3052.43.2.2.5.1.29 | Integer32 | read-write | Conversion high unit value for this analog input sensor |
| esPointConfigRelayTable | 1.3.6.1.4.1.3052.43.2.2.6 | not-accessible | This table organizes 3 basic attributes of relay points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: 1. the configuration item (e.g., enable, name, etc.) 2. the eventsensor on which this point resides 3. the point number Points are referenced by a point config index. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the context of this relay point config table ; namely, which EventSensor and which sensor. | |
| esPointConfigRelayEntry | 1.3.6.1.4.1.3052.43.2.2.6.1 | not-accessible | Entry for EventSensor point config relay table | |
| I32 espcRelayIndexES | 1.3.6.1.4.1.3052.43.2.2.6.1.1 | Integer32 | read-only | The part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the information necessary for getting a piece of data off an event sensor within the the context of the eventsensor point config relay table; namely, which EventSensor and which sensor (a.k.a. point). This object's allowable values are 1 through 16, and 200. 200 always refers to the EventSensor inside the unit. 1 through 16 refer to additional attached EventSensors. |
| I32 espcRelayIndexPoint | 1.3.6.1.4.1.3052.43.2.2.6.1.2 | Integer32 | read-only | The part of the point index that delineates which sensor on the EventSensor. So this combined with espcRelayIndexES (which EventSensor) uniquely defines each point attached to a unit within the context of relay point configuration. |
| STR espcRelayEnable | 1.3.6.1.4.1.3052.43.2.2.6.1.3 | DisplayString | read-write | ON/OFF enable for this relay |
| STR espcRelayName | 1.3.6.1.4.1.3052.43.2.2.6.1.4 | DisplayString | read-write | Name for this relay |
| network | 1.3.6.1.4.1.3052.43.2.4 | |||
| ethernet | 1.3.6.1.4.1.3052.43.2.4.1 | |||
| IP ipAddress | 1.3.6.1.4.1.3052.43.2.4.1.1 | IpAddress | read-write | Ethernet IP address |
| IP subnetMask | 1.3.6.1.4.1.3052.43.2.4.1.2 | IpAddress | read-write | Ethernet subnet mask |
| IP router | 1.3.6.1.4.1.3052.43.2.4.1.3 | IpAddress | read-write | Ethernet router |
| snmp | 1.3.6.1.4.1.3052.43.2.4.8 | |||
| STR snmpReadCommunity | 1.3.6.1.4.1.3052.43.2.4.8.2 | DisplayString | read-write | SNMP read community |
| STR snmpWriteCommunity | 1.3.6.1.4.1.3052.43.2.4.8.3 | DisplayString | read-write | SNMP write community |
| STR snmpTrapCommunity | 1.3.6.1.4.1.3052.43.2.4.8.4 | DisplayString | read-write | SNMP trap community |
| snmpServerTable | 1.3.6.1.4.1.3052.43.2.4.8.6 | not-accessible | Table of network hosts to use for network-based actions | |
| snmpServerEntry | 1.3.6.1.4.1.3052.43.2.4.8.6.1 | not-accessible | Entry for table of network hosts to use for network-based actions | |
| I32 snmpServerIndex | 1.3.6.1.4.1.3052.43.2.4.8.6.1.1 | Integer32 | read-only | Index for table of network hosts to use for network-based actions |
| IP snmpServer | 1.3.6.1.4.1.3052.43.2.4.8.6.1.2 | IpAddress | read-write | Hostname/IP address used as destination for network-based action (e.g., trap) |
| STR snmpTestTrap | 1.3.6.1.4.1.3052.43.2.4.8.7 | DisplayString | read-write | SNMP trap community |
| 1.3.6.1.4.1.3052.43.2.4.17 | ||||
| IP emailServer | 1.3.6.1.4.1.3052.43.2.4.17.1 | IpAddress | read-write | SMTP server to which the unit sends email |
| STR emailDomain | 1.3.6.1.4.1.3052.43.2.4.17.2 | DisplayString | read-write | Domain to use in recipient address |
| STR emailAuthEnable | 1.3.6.1.4.1.3052.43.2.4.17.3 | DisplayString | read-write | ON/OFF enable SMTP authentication |
| STR emailAuthUsername | 1.3.6.1.4.1.3052.43.2.4.17.4 | DisplayString | read-write | Username for SMTP authentication |
| STR emailAuthPassword | 1.3.6.1.4.1.3052.43.2.4.17.5 | DisplayString | read-write | Password for SMTP authentication |
| emailTable | 1.3.6.1.4.1.3052.43.2.4.17.6 | not-accessible | Table of email addresses to use for email actions | |
| emailEntry | 1.3.6.1.4.1.3052.43.2.4.17.6.1 | not-accessible | Entry for table of email addresses to use for email actions | |
| I32 emailIndex | 1.3.6.1.4.1.3052.43.2.4.17.6.1.1 | Integer32 | read-only | Index for table of email addresses to use for email actions |
| STR emailAddress | 1.3.6.1.4.1.3052.43.2.4.17.6.1.2 | DisplayString | read-write | email address |
| STR emailTestMail | 1.3.6.1.4.1.3052.43.2.4.17.7 | DisplayString | read-write | Password for SMTP authentication |
| dateTime | 1.3.6.1.4.1.3052.43.2.8 | |||
| STR date | 1.3.6.1.4.1.3052.43.2.8.1 | DisplayString | read-write | Text string for date. |
| STR time | 1.3.6.1.4.1.3052.43.2.8.2 | DisplayString | read-write | Text string for time. |
| STR autodst | 1.3.6.1.4.1.3052.43.2.8.3 | DisplayString | read-write | ON/OFF automatically adjust for Daylight Savings Time |
| action | 1.3.6.1.4.1.3052.43.2.14 | |||
| STR actionSystemAlertAction | 1.3.6.1.4.1.3052.43.2.14.1 | DisplayString | read-write | System Alert Actions are actions that occur when the system needs to alert the user of something. The only time this occurs currently is a powerup alert. |
| STR actionPowerupAlertEnable | 1.3.6.1.4.1.3052.43.2.14.2 | DisplayString | read-write | action Powerup Alert Enable |
| STR actionRTNAlertsEnable | 1.3.6.1.4.1.3052.43.2.14.3 | DisplayString | read-write | Return to Normal Alerts Enabled |
| I32 actionAlarmRepeatFrequency | 1.3.6.1.4.1.3052.43.2.14.4 | Integer32 | read-write | Frequency in minutes of repeats |
| sys | 1.3.6.1.4.1.3052.43.2.16 | |||
| STR sysSerial | 1.3.6.1.4.1.3052.43.2.16.1 | DisplayString | read-write | Serial Number |
| STR sysVersion | 1.3.6.1.4.1.3052.43.2.16.2 | DisplayString | read-write | Serial Number |
| STR sysBuild | 1.3.6.1.4.1.3052.43.2.16.3 | DisplayString | read-write | Serial Number |
| STR sysSitename | 1.3.6.1.4.1.3052.43.2.16.4 | DisplayString | read-write | Serial Number |
| STR sysProduct | 1.3.6.1.4.1.3052.43.2.16.5 | DisplayString | read-write | Serial Number |
| STR thisTrapText | 1.3.6.1.4.1.3052.43.2.16.6 | DisplayString | read-write | A text string included in all traps |
| NTF s220PowerUpTrap | 1.3.6.1.4.1.3052.43.20000 | Sent upon System Alert at power up. | ||
| NTF s220ContactTrap | 1.3.6.1.4.1.3052.43.20001 | Sent to show a contact is in the alarm state. | ||
| NTF s220TempTrap | 1.3.6.1.4.1.3052.43.20010 | Sent to show temperature exceeded threshold. | ||
| NTF s220HumidTrap | 1.3.6.1.4.1.3052.43.20020 | Sent to show humidity exceeded threshold | ||
| NTF s220TestTrap | 1.3.6.1.4.1.3052.43.22000 | Sent to test IP route(s) for traps. |
RFC description
Asentria SiteBoss 220 environmental monitoring for sensors, temperature control, and event status management.
Start monitoring Asentria SiteBoss 220 remote site monitor (analog/digital sensor point/alarm status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.