SITEBOSS-220-STD-MIB :: esIndexPC

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › SITEBOSS-220-STD-MIB › esIndexPC

esIndexPC

Module: SITEBOSS-220-STD-MIB

OID (symbolic): SITEBOSS-220-STD-MIB::esIndexPC

OID (numeric): 1.3.6.1.4.1.3052.43.1.1.1.1.2

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: The part of the point index that refers to point class.

The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point).

The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=relay

What is esIndexPC?

The point-class part of the point index, a number 1-6 that tells you what kind of sensor this row describes: 1=temperature, 2=contact closure, 3=humidity, 4=noise, 5=analog input, 6=relay.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3052.43.1.1.1.1.2
snmpwalk -v2c -c public <target> SITEBOSS-220-STD-MIB::esIndexPC

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3052.43.1.1.1.1.2.1
snmpget -v2c -c public <target> SITEBOSS-220-STD-MIB::esIndexPC.1

Start monitoring Asentria SiteBoss 220 remote site monitor (analog/digital sensor point/alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SITEBOSS-220-STD-MIB::esIndexPC OID value, configure state conditions and alerts, and monitor any Asentria SiteBoss 220 remote site monitor (analog/digital sensor point/alarm status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.3052asentriaASENTRIA-ROOT-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3052.43s220SITEBOSS-220-STD-MIB
1.3.6.1.4.1.3052.43.1statusSITEBOSS-220-STD-MIB
1.3.6.1.4.1.3052.43.1.1eventSensorStatusSITEBOSS-220-STD-MIB
1.3.6.1.4.1.3052.43.1.1.1esPointTableSITEBOSS-220-STD-MIB
1.3.6.1.4.1.3052.43.1.1.1.1esPointEntrySITEBOSS-220-STD-MIB
1.3.6.1.4.1.3052.43.1.1.1.1.2esIndexPCSITEBOSS-220-STD-MIB