All MIBs › DellrPDU-MIB
Category: Domain: Power Management, Domain: Server Hardware, Vendor: Dell
Description: Manages Dell remote Power Distribution Units (rPDU) monitoring outlets, load, and power consumption.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is DellrPDU-MIB?
DellrPDU-MIB (Dell remote Power Distribution Unit MIB) is a vendor-specific MIB for Dell rack PDUs, used to manage and monitor rack power distribution equipment in data centers. It exposes product identity data (display name, description, vendor, firmware version/build number) alongside overall device status objects. It is directly aimed at monitoring hardware status, particularly overall PDU health via productStatusGlobalStatus and its historical counterpart productStatusLastGlobalStatus, plus a timestamp of the last status change, complementing the outlet-level power/load metrics typical of PDU devices. It sits within Dell's PDU-specific enterprise MIB subtree (pdu/pdusub under the dell branch) and likely parallels standard PDU MIB conventions used across the industry. It is typically deployed in data center or server-room environments where administrators track rack power distribution unit availability and condition remotely via SNMP, typically after a DellrPDU-MIB download to load the module's objects into their monitoring platform.
IPNetwork Monitor allows you to monitor SNMP objects defined in DellrPDU-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Dell rPDU (rack Power Distribution Unit)
Monitoring Examples
An operator would poll productStatusGlobalStatus alongside productStatusTimeStamp to detect when the rPDU's overall health transitions to a fault/warning state, comparing against productStatusLastGlobalStatus to see the prior condition. productIDDisplayName, productIDVendor, and productIDVersion/productIDBuildNumber let inventory and monitoring systems confirm exactly which PDU model and firmware revision is deployed. The dell/pdu/pdusub subtree organizes these objects, and productIDDeviceNetworkName helps map SNMP polls back to a specific rack PDU on the network.
What Can Be Monitored
- overall PDU global status
- previous global status
- status change timestamp
- firmware/build version
- device network name/identity
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Gauge | |
| IpAddress | |
| TimeTicks | |
| enterprises |
From RFC1213-MIB
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| dell | 1.3.6.1.4.1.674 | |||
| pdu | 1.3.6.1.4.1.674.10903 | |||
| pdusub | 1.3.6.1.4.1.674.10903.200 | |||
| software | 1.3.6.1.4.1.674.10903.200.1 | |||
| hardware | 1.3.6.1.4.1.674.10903.200.2 | |||
| productID | 1.3.6.1.4.1.674.10903.200.2.100 | |||
| STR productIDDisplayName | 1.3.6.1.4.1.674.10903.200.2.100.1 | DisplayString | read-write | Name of this product for display purposes. |
| STR productIDDescription | 1.3.6.1.4.1.674.10903.200.2.100.2 | DisplayString | read-write | A short description of this product. |
| STR productIDVendor | 1.3.6.1.4.1.674.10903.200.2.100.3 | DisplayString | read-only | The name of the product manufacturer. |
| STR productIDVersion | 1.3.6.1.4.1.674.10903.200.2.100.4 | DisplayString | read-only | The hardware version of this product. |
| STR productIDBuildNumber | 1.3.6.1.4.1.674.10903.200.2.100.5 | DisplayString | read-only | The software build number of the product populating the MIB. |
| STR productIDURL | 1.3.6.1.4.1.674.10903.200.2.100.6 | DisplayString | read-only | The URL of the Web-based application to manage this device, should the device provide one. |
| STR productIDDeviceNetworkName | 1.3.6.1.4.1.674.10903.200.2.100.7 | DisplayString | read-write | Operating system-specific computer name if product SNMP service is hosted. |
| productStatus | 1.3.6.1.4.1.674.10903.200.2.110 | |||
| RPD productStatusGlobalStatus | 1.3.6.1.4.1.674.10903.200.2.110.1 | RpduOtherToNonrecoverableType | read-only | The current status of the product. This is a summary of the status for the entire product including any metered devices. The SNMP monitor performs a get to retrieve additional data when this status is abnormal. Valid values 1: Other 2: Unknown 3: OK 4: Non-critical 5: Critical 6: Non-recoverable. |
| RPD productStatusLastGlobalStatus | 1.3.6.1.4.1.674.10903.200.2.110.2 | RpduOtherToNonrecoverableType | read-only | The status before the current status which induced an initiative to issue a global status change trap. |
| INT productStatusTimeStamp | 1.3.6.1.4.1.674.10903.200.2.110.3 | INTEGER | read-only | The last time that the SNMP table geometries changed or attribute data was significantly updated. Management applications use this OID to trigger a refresh of data acquired from the MIB. This time should be a relative timestamp, for example, the value of MIB II SysUpTime when the values are updated. |
| STR productStatusRESERVED1 | 1.3.6.1.4.1.674.10903.200.2.110.4 | DisplayString | read-only | RESERVED |
| STR productStatusRESERVED2 | 1.3.6.1.4.1.674.10903.200.2.110.5 | DisplayString | read-only | RESERVED |
| STR productStatusRESERVED3 | 1.3.6.1.4.1.674.10903.200.2.110.6 | DisplayString | read-only | RESERVED |
| rPDU | 1.3.6.1.4.1.674.10903.200.2.200 | |||
| rPDUIdentD | 1.3.6.1.4.1.674.10903.200.2.200.100 | |||
| INT rPDUIdentTableSize | 1.3.6.1.4.1.674.10903.200.2.200.100.1 | INTEGER | read-only | The number of connected Rack PDUs. |
| rPDUIdentTable | 1.3.6.1.4.1.674.10903.200.2.200.100.2 | not-accessible | A table of Rack PDU identification data. | |
| rPDUIdentEntry | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1 | not-accessible | Identification data from the Rack PDU being queried. | |
| INT rPDUIdentIndex | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.1 | INTEGER | read-only | The index to the Rack PDU identification table entry. |
| STR rPDUIdentNameD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.2 | DisplayString | read-write | A user-defined string identifying the Rack PDU. |
| STR rPDUIdentLocation | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.3 | DisplayString | read-write | A user-defined string identifying the location of the Rack PDU. |
| STR rPDUIdentHardwareRevD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.4 | DisplayString | read-only | The Rack PDU hardware version. |
| STR rPDUIdentFirmwareRevD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.5 | DisplayString | read-only | The Rack PDU firmware version. |
| STR rPDUIdentDateOfManufactureD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.6 | DisplayString | read-only | The date the Rack PDU was manufactured in mm/dd/yyyy format. |
| STR rPDUIdentModelNumberD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.7 | DisplayString | read-only | The Rack PDU model number. |
| STR rPDUIdentSerialNumberD | 1.3.6.1.4.1.674.10903.200.2.200.100.2.1.8 | DisplayString | read-only | The Rack PDU serial number. |
| rPDUDevice | 1.3.6.1.4.1.674.10903.200.2.200.110 | |||
| INT rPDUDeviceTableSize | 1.3.6.1.4.1.674.10903.200.2.200.110.1 | INTEGER | read-only | The number of connected Rack PDUs. |
| rPDUDeviceStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.110.2 | not-accessible | A table of Rack PDU status information. | |
| rPDUDeviceStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1 | not-accessible | Status information from the Rack PDU being queried. | |
| INT rPDUDeviceStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.1 | INTEGER | read-only | The index to the Rack PDU status table entry. |
| STR rPDUDeviceStatusName | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.2 | DisplayString | read-write | A user-defined string identifying the Rack PDU. |
| INT rPDUDeviceStatusPower | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.3 | INTEGER | read-only | The power consumption of the Rack PDU load in 1/100 of KWatts. |
| INT rPDUDeviceStatusEnergy | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.4 | INTEGER | read-only | A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. |
| INT rPDUDeviceStatusCommandPending | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.5 | INTEGER | read-only | Indicates whether the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices receiving power from the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition. |
| RPD rPDUDeviceStatusLoadState | 1.3.6.1.4.1.674.10903.200.2.200.110.2.1.6 | RpduLowNormalNearOverloadType | read-only | Indicates the present load status of the Rack PDU Device being queried. |
| rPDUDeviceConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.110.3 | not-accessible | A table of Rack PDU configuration data. | |
| rPDUDeviceConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1 | not-accessible | Configuration data from the Rack PDU being queried. | |
| INT rPDUDeviceConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.1 | INTEGER | read-only | The index to the Rack PDU table entry. |
| STR rPDUDeviceConfigName | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.2 | DisplayString | read-write | A user-defined string identifying the Rack PDU. |
| STR rPDUDeviceConfigLocation | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.3 | DisplayString | read-write | The Location of the Rack PDU. |
| INT rPDUDeviceConfigColdstartDelay | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4 | INTEGER | read-write | The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. |
| INT rPDUDeviceCfgLowLoadPwrThresh | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.5 | INTEGER | read-write | The user-defined low power draw alarm threshold, measured in tenths of kilowatts. |
| INT rPDUDeviceCfgNerOvloadPwrThresh | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.6 | INTEGER | read-write | The user-defined near power overload threshold, measured in tenths of kilowatts. |
| INT rPDUDeviceCfgOverloadPwrThresh | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.7 | INTEGER | read-write | The user-defined power overload threshold, measured in tenths of kilowatts. |
| INT rPDUDeviceConfigPowerHeadroom | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.8 | INTEGER | read-only | The amount of input power that is available to the connected devices in hundredths of kilowatt-hours. |
| INT rPDUDeviceConfigPeakPower | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.9 | INTEGER | read-only | The highest input power level recorded by the connected devices in hundredths of kilowatt-hours. |
| STR rPDUDeviceCfgPeakPwrStartTime | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.10 | DisplayString | read-only | The time, in hh:mm:ss, when the device started recording the highest input power level. |
| STR rPDUDeviceConfigPeakPwrCapTime | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.11 | DisplayString | read-only | The time, in hh:mm:ss, when the highest input power level was recorded by the device. |
| INT rPDUDeviceCfgPeakPowerHeadroom | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.12 | INTEGER | read-only | The highest level of input power that is available to the connected devices in hundredths of kilowatt-hours. |
| STR rPDUDeviceCfgEnergyStartTime | 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.13 | DisplayString | read-only | The time, in hh:mm:ss, when the device started recording the input energy level. |
| rPDUDevicePropertiesTable | 1.3.6.1.4.1.674.10903.200.2.200.110.4 | not-accessible | A table of Rack PDU properties. | |
| rPDUDevicePropertiesEntry | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1 | not-accessible | Properties of the Rack PDU being queried. | |
| INT rPDUDevicePropertiesIndex | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.1 | INTEGER | read-only | The index to the Rack PDU properties table entry. |
| STR rPDUDevicePropertiesName | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.2 | DisplayString | read-write | A user-defined string identifying the Rack PDU. |
| INT rPDUDevicePropertiesNumOutlets | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.3 | INTEGER | read-only | The number of outlets on the Rack PDU. |
| INT rPDUDevicePropertiesNumSwdOuts | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.4 | INTEGER | read-only | The number of switched outlets on the Rack PDU. |
| INT rPDUDevicePropertiesNumMtrdOuts | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.5 | INTEGER | read-only | The number of metered outlets on the Rack PDU. |
| INT rPDUDevicePropertiesNumPhases | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.6 | INTEGER | read-only | The number of phases present in the Rack PDU. |
| INT rPDUDevicePropertiesNumBreakers | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.7 | INTEGER | read-only | The number of breakers present in the Rack PDU. |
| INT rPDUDevicePropertiesMaxCurntRtg | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.8 | INTEGER | read-only | The maximum current rating, measured in Amps, for the Rack PDU. |
| INT rPDUDevicePropertiesOutlayout | 1.3.6.1.4.1.674.10903.200.2.200.110.4.1.9 | INTEGER | read-only | The phase wiring for the Rack PDU outlets. PhaseToNeutral and PhaseToPhase: outlets wired consecutively; PhaseToNeutralGrouped and PhaseToPhaseGrouped: groups of outlets wired consecutively. |
| rPDUDeviceControlTable | 1.3.6.1.4.1.674.10903.200.2.200.110.5 | not-accessible | A table of Rack PDU control data. | |
| rPDUDeviceControlEntry | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1 | not-accessible | Control data from the Rack PDU being queried. | |
| INT rPDUDeviceControlIndex | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.1 | INTEGER | read-only | The index to the Rack PDU control table entry. |
| STR rPDUDeviceControlName | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.2 | DisplayString | read-write | A user-defined string identifying the Rack PDU. |
| INT rPDUDeviceControlCommand | 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 | INTEGER | read-write | Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. Setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's rPDUOutSwitchedCfgPowerOnTime OID value. Setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the Rack PDU will then delay the rPDUOutSwtchedCfgRebootDuration OID time, and then perform a turnAllOnSequence. Setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's rPDUOutSwitchedCfgPowerOffTime OID value. Getting this OID will return the noCommand (6) value. |
| rPDUPhase | 1.3.6.1.4.1.674.10903.200.2.200.120 | |||
| INT rPDUPhaseTableSize | 1.3.6.1.4.1.674.10903.200.2.200.120.1 | INTEGER | read-only | The number of connected Rack PDU phases. |
| rPDUPhaseStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.120.2 | not-accessible | A table of Rack PDU phase status data. | |
| rPDUPhaseStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1 | not-accessible | Status data from the currently queried Rack PDU phase. | |
| INT rPDUPhaseStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.1 | INTEGER | read-only | The index to the Rack PDU phase status table entry. |
| INT rPDUPhaseStatusNumber | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.2 | INTEGER | read-only | The numeric phase ID. |
| RPD rPDUPhaseStatusLoadState | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.3 | RpduLowNormalNearOverloadType | read-only | Indicates the present load status of the Rack PDU phase being queried. |
| INT rPDUPhaseStatusCurrent | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.4 | INTEGER | read-only | Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried. |
| INT rPDUPhaseStatusVoltage | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.5 | INTEGER | read-only | Indicates the Voltage, in Volts, of the Rack PDU phase being queried. |
| INT rPDUPhaseStatusPower | 1.3.6.1.4.1.674.10903.200.2.200.120.2.1.6 | INTEGER | read-only | Indicates the load power, in hundredths of kilowatts, consumed on the Rack PDU phase being queried. |
| rPDUPhaseConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.120.3 | not-accessible | A table of Rack PDU phase configuration data. | |
| rPDUPhaseConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1 | not-accessible | Configuration data from the currently queried Rack PDU phase. | |
| INT rPDUPhaseConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.1 | INTEGER | read-only | The index to the Rack PDU phase configuration table entry. |
| INT rPDUPhaseConfigNumber | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.2 | INTEGER | read-only | The numeric phase ID. |
| INT rPDUPhaseCfgOverloadRestriction | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.3 | INTEGER | read-write | This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding phase to turn on. Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigNearOverloadThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding phase to turn on if the rPDULoadConfigOverloadThreshold OID is exceeded. |
| INT rPDUPhCfgLowLoadCurntThreshold | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.4 | INTEGER | read-write | The user-defined threshold for low phase current load, in Amps. |
| INT rPDUPhCfgNerOverloadCurntThresh | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.5 | INTEGER | read-write | The user-defined near phase overload warning threshold in Amps. |
| INT rPDUPhCfgOverloadCurntThreshold | 1.3.6.1.4.1.674.10903.200.2.200.120.3.1.6 | INTEGER | read-write | The user-defined phase overload current threshold in Amps. |
| rPDUOutlet | 1.3.6.1.4.1.674.10903.200.2.200.130 | |||
| rPDUOutletSwitched | 1.3.6.1.4.1.674.10903.200.2.200.130.1 | |||
| INT rPDUOutletSwitchedTableSize | 1.3.6.1.4.1.674.10903.200.2.200.130.1.1 | INTEGER | read-only | The number of switched outlets on connected Rack PDUs. |
| rPDUOutletSwitchedStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2 | not-accessible | A table of Rack PDU switched outlet status information. | |
| rPDUOutletSwitchedStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1 | not-accessible | Status information for the currently-queried Rack PDU switched outlet. | |
| INT rPDUOutletSwitchedStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.1 | INTEGER | read-only | The index to the Rack PDU switched outlet status information table entry. |
| INT rPDUOutletSwitchedStatusNumber | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.2 | INTEGER | read-only | The numeric switched outlet ID. |
| STR rPDUOutletSwitchedStatusName | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.3 | DisplayString | read-write | The user-defined switched outlet ID string. |
| INT rPDUOutletSwitchedStatusState | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.4 | INTEGER | read-only | Indicates the present status of the Rack PDU switched outlet being queried. |
| INT rPDUOutletSwitchedStatCmdPnding | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.5 | INTEGER | read-only | Indicates whether the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices receiving power from the Rack PDU should be shut down. The Rack PDU's power should then be cycled to clear this condition. |
| RPD rPDUOutletSwitchedStatPhLayout | 1.3.6.1.4.1.674.10903.200.2.200.130.1.2.1.6 | RpduOutletPhaseLayoutType | read-only | Phase description of the currently-queried Rack PDU switched outlet. |
| rPDUOutletSwitchedConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3 | not-accessible | A table of Rack PDU switched outlet configuration data. | |
| rPDUOutletSwitchedConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1 | not-accessible | Configuration data from the currently-queried Rack PDU switched outlet. | |
| INT rPDUOutletSwitchedConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.1 | INTEGER | read-only | The index to the Rack PDU switched outlet configuration table entry. |
| INT rPDUOutletSwitchedConfigNumber | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.2 | INTEGER | read-only | The numeric switched outlet ID. |
| STR rPDUOutletSwitchedConfigName | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.3 | DisplayString | read-write | The user-defined switched outlet ID string. |
| INT rPDUOutSwitchedCfgPowerOnTime | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.4 | INTEGER | read-write | The amount of time, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. |
| INT rPDUOutSwitchedCfgPowerOffTime | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.5 | INTEGER | read-write | The amount of time, in seconds, this outlet will delay turning off. |
| INT rPDUOutSwtchedCfgRebootDuration | 1.3.6.1.4.1.674.10903.200.2.200.130.1.3.1.6 | INTEGER | read-write | After turning off power during a reboot sequence, the amount of time, in seconds, to wait before turning on power to this outlet again. |
| rPDUOutletSwitchedControlTable | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4 | not-accessible | A table of Rack PDU switched outlet control data. | |
| rPDUOutletSwitchedControlEntry | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1 | not-accessible | Control data for the currently-queried Rack PDU switched outlet. | |
| INT rPDUOutletSwitchedControlIndex | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.1 | INTEGER | read-only | The index to the Rack PDU switched outlet control data table entry. |
| INT rPDUOutletSwitchedControlNumber | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.2 | INTEGER | read-only | The numeric switched outlet ID. |
| STR rPDUOutletSwitchedControlName | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.3 | DisplayString | read-write | The user-defined switched outlet ID string. |
| INT rPDUOutletSwitchedControlCmd | 1.3.6.1.4.1.674.10903.200.2.200.130.1.4.1.4 | INTEGER | read-write | Getting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet cannot be determined, the outletUnknown (4) value will be returned. If the outletUnknown condition should occur, all devices receiving power from the PDU should be shut down. The PDU's power should then be cycled to clear this condition. Setting this variable to outletOn (1) will turn the outlet on. Setting this variable to outletOff (2) will turn the outlet off. Setting this variable to outletReboot (3) will reboot the outlet. Setting this variable to outletOnWithDelay (5) will turn the outlet on after the rPDUOutSwitchedCfgPowerOnTime OID has elapsed. Setting this variable to outletOffWithDelay (6) will turn the outlet off after the rPDUOutSwitchedCfgPowerOffTime OID has elapsed. Setting this variable to outletRebootWithDelay (7) will turn the outlet off after the rPDUOutSwitchedCfgPowerOffTime OID has elapsed, wait the rPDUOutSwtchedCfgRebootDuration OID time, then turn the outlet back on. |
| rPDUOutletMetered | 1.3.6.1.4.1.674.10903.200.2.200.130.2 | |||
| INT rPDUOutletMeteredTableSize | 1.3.6.1.4.1.674.10903.200.2.200.130.2.1 | INTEGER | read-only | The number of metered outlets on connected Rack PDUs. |
| rPDUOutletMeteredStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2 | not-accessible | A table of Rack PDU metered outlet status data. | |
| rPDUOutletMeteredStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1 | not-accessible | Status data from the currently-queried Rack PDU metered outlet. | |
| INT rPDUOutletMeteredStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.1 | INTEGER | read-only | The index to the Rack PDU metered status table entry. |
| INT rPDUOutletMeteredStatusNumber | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.2 | INTEGER | read-only | The numeric metered outlet ID. |
| STR rPDUOutletMeteredStatusName | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.3 | DisplayString | read-write | The user-defined metered outlet ID string. |
| RPD rPDUOutletMeteredStatusLayout | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.4 | RpduOutletPhaseLayoutType | read-only | Phase description of currently queried Rack PDU metered outlet. |
| INT rPDUOutMeteredStatPowerRating | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.5 | INTEGER | read-only | The power rating for the currently queried Rack PDU metered outlet. |
| INT rPDUOutletMeteredStatusCurrent | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.6 | INTEGER | read-only | Indicates the current draw, in Amps, of the load on the Rack PDU outlet being queried. |
| INT rPDUOutletMeteredStatusEnergy | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.7 | INTEGER | read-only | A user resettable energy meter measuring Rack PDU load energy consumption in kilowatt-hours. |
| INT rPDUOutletMeteredStatusPower | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.8 | INTEGER | read-only | Indicates the power draw of the load on the Rack PDU outlet being queried. |
| INT rPDUOutletMeteredStatPeakPower | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.9 | INTEGER | read-only | The highest power level recorded by the currently queried Rack PDU metered outlet, in kilowatts. |
| STR rPDUOutMeteredStatPeakPwrTime | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.10 | DisplayString | read-only | Indicates the date and time that peak power consumption occured |
| RPD rPDUOutMeteredStatusLoadState | 1.3.6.1.4.1.674.10903.200.2.200.130.2.2.1.11 | RpduLowNormalNearOverloadType | read-only | Indicates the present load status of the Rack PDU Outlet being queried. |
| rPDUOutletMeteredConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4 | not-accessible | A table of Rack PDU metered outlet configuration data. | |
| rPDUOutletMeteredConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1 | not-accessible | Configuration data from the currently queried Rack PDU metered outlet. | |
| INT rPDUOutletMeteredConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.1 | INTEGER | read-only | The index to the Rack PDU metered outlet configuration table entry. |
| INT rPDUOutletMeteredConfigNumber | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.2 | INTEGER | read-only | The numeric switched outlet ID. |
| STR rPDUOutletMeteredConfigName | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.3 | DisplayString | read-write | The user-defined metered outlet ID string. |
| INT rPDUOutMtredCfgLowLdCurntThresh | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.4 | INTEGER | read-write | The user-defined low load outlet current threshold, in Amps. |
| INT rPDUOutMtrdCfgNrOvdCurntThresh | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.5 | INTEGER | read-write | The user-defined near outlet overload warning threshold, in Amps. |
| INT rPDUOutMtredCfgOvrldCurntThresh | 1.3.6.1.4.1.674.10903.200.2.200.130.2.4.1.6 | INTEGER | read-write | The user-defined outlet overload current threshold, in Amps. |
| STR rPDUOutMeteredEnergyStartTime | 1.3.6.1.4.1.674.10903.200.2.200.130.2.5 | DisplayString | read-only | The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the input energy level. |
| STR rPDUOutMeteredPeakPwrStartTime | 1.3.6.1.4.1.674.10903.200.2.200.130.2.6 | DisplayString | read-only | The time, in hh:mm:ss, when the currently queried Rack PDU metered outlet started recording the highest level of input power that is available to the connected device. |
| rPDUPowerSupply | 1.3.6.1.4.1.674.10903.200.2.200.140 | |||
| INT rPDUPowerSupplyAlarmD | 1.3.6.1.4.1.674.10903.200.2.200.140.1 | INTEGER | read-only | Getting this OID will return the status of the power supply alarm. |
| INT rPDUPowerSupplyVoltage | 1.3.6.1.4.1.674.10903.200.2.200.140.2 | INTEGER | read-only | The voltage provided by the power supply in tenths of volts. |
| rPDUSensor | 1.3.6.1.4.1.674.10903.200.2.200.150 | |||
| rPDUSensorStatus | 1.3.6.1.4.1.674.10903.200.2.200.150.1 | |||
| INT rPDUSensorStatusTableSize | 1.3.6.1.4.1.674.10903.200.2.200.150.1.1 | INTEGER | read-only | The number of connected temperature sensors. |
| rPDUSensorStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2 | not-accessible | A table of temperature sensor status data. | |
| rPDUSensorStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1 | not-accessible | Status information from the temperature sensor being queried. | |
| INT rPDUSensorStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.1 | INTEGER | read-only | The index to the status data table entry. |
| STR rPDUSensorStatusName | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.2 | DisplayString | read-write | The user-defined sensor ID string. |
| INT rPDUSensorStatusType | 1.3.6.1.4.1.674.10903.200.2.200.150.1.2.1.3 | INTEGER | read-only | The type of the sensor. |
| rPDUSensorTemp | 1.3.6.1.4.1.674.10903.200.2.200.150.2 | |||
| INT rPDUSensorTempTableSize | 1.3.6.1.4.1.674.10903.200.2.200.150.2.1 | INTEGER | read-only | The number of connected temperature sensors. |
| rPDUSensorTempStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2 | not-accessible | A table of temperature sensor status data. | |
| rPDUSensorTempStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1 | not-accessible | Status information from the temperature sensor being queried. | |
| INT rPDUSensorTempStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.1 | INTEGER | read-only | The index to the temperature status data table entry. |
| STR rPDUSensorTempStatusName | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.2 | DisplayString | read-write | The user-defined temperature-humidity sensor ID string. |
| RPD rPDUSensorTempStatusCommStatus | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.3 | RpduCommNoneOKLostType | read-only | The communications status of the sensor. |
| INT rPDUSensorTempStatusTempF | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.4 | INTEGER | read-only | The sensor temperature reading in tenths of degrees Fahrenheit. |
| INT rPDUSensorTempStatusTempC | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.5 | INTEGER | read-only | The sensor temperature reading in tenths of degrees Celsius. |
| RPD rPDUSensorTempStatusAlarmStatus | 1.3.6.1.4.1.674.10903.200.2.200.150.2.2.1.6 | RpduNotPBMinLowNrmlOHiMaxType | read-only | The alarm status of the sensor. |
| rPDUSensorTempConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3 | not-accessible | A table of temperature-humidity sensor configuration data. | |
| rPDUSensorTempConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1 | not-accessible | Configuration data from the temperature-humidity sensor being queried. | |
| INT rPDUSensorTempConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.1 | INTEGER | read-only | The index to the temperature-humidity sensor configuration data table entry. |
| STR rPDUSensorTempConfigName | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.2 | DisplayString | read-write | The user-defined temperature-humidity sensor ID string. |
| INT rPDUSensorTempCfgTempMaxThreshF | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.3 | INTEGER | read-write | The sensor maximum temperature alarm threshold in Fahrenheit. |
| INT rPDUSnsorTempCfgTempHighThreshF | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.4 | INTEGER | read-write | The sensor high temperature warning alarm threshold in Fahrenheit. |
| INT rPDUSnsorTempCfgTempHysteresisF | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.5 | INTEGER | read-write | The sensor temperature hysteresis setting in Fahrenheit. |
| INT rPDUSensorTempCfgTempMaxThreshC | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.6 | INTEGER | read-write | The sensor maximum temperature alarm threshold in Celsius. |
| INT rPDUSnsorTempCfgTempHighThreshC | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.7 | INTEGER | read-write | The sensor high temperature warning alarm threshold in Celsius. |
| INT rPDUSnsorTempCfgTempHysteresisC | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.8 | INTEGER | read-write | The sensor temperature hysteresis setting in Celsius. |
| RPD rPDUSnsorTempCfgAlarmGeneration | 1.3.6.1.4.1.674.10903.200.2.200.150.2.3.1.9 | RpduEnableDisableType | read-write | Indicates whether the Temp Alarm Generation is enabled. |
| rPDUSensorHumidity | 1.3.6.1.4.1.674.10903.200.2.200.150.3 | |||
| INT rPDUSensorHumidityTableSize | 1.3.6.1.4.1.674.10903.200.2.200.150.3.1 | INTEGER | read-only | The number of connected temperature-humidity sensors. |
| rPDUSensorHumidityStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2 | not-accessible | A table of temperature-humidity sensor status data. | |
| rPDUSensorHumidityStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1 | not-accessible | Status information from the temperature-humidity sensor being queried. | |
| INT rPDUSensorHumidityStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.1 | INTEGER | read-only | The index to the temperature-humidity status data table entry. |
| STR rPDUSensorHumidityStatusName | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.2 | DisplayString | read-write | The user-defined temperature-humidity sensor ID string. |
| RPD rPDUSnsorHumidityStatCommStatus | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.3 | RpduCommNoneOKLostType | read-only | The communications status of the sensor. |
| INT rPDUSnsorHumStatRelativeHumdity | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.4 | INTEGER | read-only | The sensor humidity reading in percent relative humidity. |
| RPD rPDUSnsorHumStatusAlarmStatus | 1.3.6.1.4.1.674.10903.200.2.200.150.3.2.1.5 | RpduNotPBMinLowNrmlOHiMaxType | read-only | The alarm status of the sensor. |
| rPDUSensorHumidityConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3 | not-accessible | A table of temperature-humidity sensor configuration data. | |
| rPDUSensorHumidityConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1 | not-accessible | Configuration data from the temperature-humidity sensor being queried. | |
| INT rPDUSensorHumidityConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.1 | INTEGER | read-only | The index to the temperature-humidity sensor configuration data table entry. |
| STR rPDUSensorHumidityConfigName | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.2 | DisplayString | read-write | The user-defined temperature-humidity sensor ID string. |
| INT rPDUSnsorHumCfgHumdityLowThresh | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.3 | INTEGER | read-write | The sensor low humidity warning alarm threshold in percent relative humidity. |
| INT rPDUSnsorHumCfgHumdityMinThresh | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.4 | INTEGER | read-write | The sensor minimum humidity alarm threshold in percent relative humidity. |
| INT rPDUSnsorHumCfgHumdtyHysteresis | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.5 | INTEGER | read-write | The sensor humidity hysteresis setting in percent relative humidity. |
| RPD rPDUSnsorHumCfgAlarmGeneration | 1.3.6.1.4.1.674.10903.200.2.200.150.3.3.1.6 | RpduEnableDisableType | read-write | Indicates whether the Humidity Alarm Generation is enabled. |
| rPDUSensorDiscrete | 1.3.6.1.4.1.674.10903.200.2.200.150.4 | |||
| INT rPDUSensorDiscreteTableSize | 1.3.6.1.4.1.674.10903.200.2.200.150.4.1 | INTEGER | read-only | The number of connected discrete sensors. |
| rPDUSensorDiscreteStatusTable | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2 | not-accessible | A table of discrete sensor status data. | |
| rPDUSensorDiscreteStatusEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1 | not-accessible | Status information from the discrete sensor being queried. | |
| INT rPDUSensorDiscreteStatusIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.1 | INTEGER | read-only | The index to the discrete sensor status data table entry. |
| STR rPDUSensorDiscreteStatusName | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.2 | DisplayString | read-write | The user-defined discrete sensor ID string. |
| INT rPDUSnsorDiscreteStatCurntState | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.3 | INTEGER | read-only | The current state of the discrete sensor, open, closed, or unknown. |
| RPD rPDUSnsorDiscreteStatAlarmState | 1.3.6.1.4.1.674.10903.200.2.200.150.4.2.1.4 | RpduNormalAlarmType | read-only | Indicates the alarm status of the discrete sensor input. |
| rPDUSensorDiscreteConfigTable | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3 | not-accessible | A table of discrete sensor configuration data. | |
| rPDUSensorDiscreteConfigEntry | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1 | not-accessible | Configuration data from the discrete sensor being queried. | |
| INT rPDUSensorDiscreteConfigIndex | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.1 | INTEGER | read-only | The index to the discrete sensor configuration data table entry. |
| STR rPDUSensorDiscreteConfigName | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.2 | DisplayString | read-write | The user-defined discrete sensor ID string. |
| INT rPDUSnsorDiscreteCfgNormalState | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.3 | INTEGER | read-write | Indicates the normal state of the discrete input contact. |
| RPD rPDUSnsorDiscrteAlarmGeneration | 1.3.6.1.4.1.674.10903.200.2.200.150.4.3.1.4 | RpduEnableDisableType | read-write | Indicates whether Discrete Alarm Generation is enabled. |
| mtrapargsD | 1.3.6.1.4.1.674.10903.200.2.200.160 | |||
| INT contactNumber | 1.3.6.1.4.1.674.10903.200.2.200.160.1 | INTEGER | read-only | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| INT outletNumber | 1.3.6.1.4.1.674.10903.200.2.200.160.2 | INTEGER | read-only | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| STR mtrapargsString | 1.3.6.1.4.1.674.10903.200.2.200.160.3 | DisplayString | read-only | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| INT phaseNumber | 1.3.6.1.4.1.674.10903.200.2.200.160.4 | INTEGER | read-only | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| INT sensorNumber | 1.3.6.1.4.1.674.10903.200.2.200.160.5 | INTEGER | read-only | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| STR deviceNameD | 1.3.6.1.4.1.674.10903.200.2.200.160.6 | DisplayString | read-only | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| STR serialNumber | 1.3.6.1.4.1.674.10903.200.2.200.160.7 | DisplayString | read-only | This OID allows traps to be sent with an octet string argument that may not be defined in the MIB. A get of this OID will return a NULL string. |
| INT testTrapargsInteger | 1.3.6.1.4.1.674.10903.200.2.200.160.8 | INTEGER | read-only | This OID allows traps to be sent with an integer argument that may not be defined in the MIB. A get of this OID will return 0. |
| events | 1.3.6.1.4.1.674.10903.200.2.200.500 | |||
| NTF deviceCommunicationLostCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1 | INFORMATIONAL: Lost communication with device has been re-established. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceCommunicationLostSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.2 | CRITICAL: Lost communication with device. The first argument is the serial number. The second argument is the device name. | ||
| NTF componentCommLostCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.3 | INFORMATIONAL: Lost communication with an on board component has been re-established. The first argument is the serial number. The second argument is the device name. | ||
| NTF componentCommLostSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.4 | CRITICAL: Lost communication with an on board component. The first argument is the serial number. The second argument is the device name. | ||
| NTF cANBusOffCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.5 | INFORMATIONAL: CAN bus off condition was cleared. The first argument is the serial number. The second argument is the device name. | ||
| NTF canBusOffSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.6 | MINOR: CAN bus off condition was set. The first argument is the serial number. The second argument is the device name. | ||
| NTF powerSupplyFailureCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.7 | INFORMATIONAL: Unit's power supply voltage is no longer out of tolerance. The first argument is the serial number. The second argument is the device name. | ||
| NTF powerSupplyFailureSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.8 | CRITICAL: Unit's power supply voltage is out of tolerance. The first argument is the serial number. The second argument is the device name. | ||
| NTF keypadButtonStuckCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.9 | INFORMATIONAL: Keypad button stuck has been cleared. The first argument is the serial number. The second argument is the device name. | ||
| NTF keypadButtonStuckSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.10 | MINOR: Keypad button stuck has been set. The first argument is the serial number. The second argument is the device name. | ||
| NTF dryContactAbnormalCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.11 | INFORMATIONAL: Dry Contact is no longer in an abnormal state. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | ||
| NTF dryContactAbnormalSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.12 | CRITICAL: Dry Contact has moved to an abnormal state. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | ||
| NTF deviceLowLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.13 | INFORMATIONAL: Device load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceLowLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.14 | MINOR: Device load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceNearOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.15 | INFORMATIONAL: Device load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceNearOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.16 | MINOR: Device load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.17 | INFORMATIONAL: Device load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF deviceOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.18 | CRITICAL: Device load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. | ||
| NTF phaseLowLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.19 | INFORMATIONAL: Phase load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF phaseLowLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.20 | MINOR: Phase load has fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF phaseNearOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.21 | INFORMATIONAL: Phase load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF phaseNearOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.22 | MINOR: Phase load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF phaseOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.23 | INFORMATIONAL: Phase load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF phaseOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.24 | CRITICAL: Phase load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF outletLowLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.25 | INFORMATIONAL: Outlet load is no longer below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletLowLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.26 | MINOR: Outlet load had fallen below the 'Low Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletNearOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.27 | INFORMATIONAL: Outlet load no longer exceeds the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletNearOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.28 | MINOR: Outlet load has exceeded the 'Near Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletOverLoadCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.29 | INFORMATIONAL: Outlet load no longer exceeds the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletOverLoadSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.30 | CRITICAL: Outlet load has exceeded the 'Over Load' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF sensorDisconnectedCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.31 | INFORMATIONAL: Sensor disconnected condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF sensorDisconnectedSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.32 | MINOR: Sensor disconnected condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF sensorTypeIndeterminateCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.33 | INFORMATIONAL: Sensor type indeterminate condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF sensorTypeIndeterminateSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.34 | MINOR: Sensor type indeterminate condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF sensorTypeUnsupportedCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.35 | INFORMATIONAL: Sensor type unsupported condition cleared. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF sensorTypeUnsupportedSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.36 | MINOR: Sensor type unsupported condition set. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF maxTemperatureExceededCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.37 | INFORMATIONAL: Sensor Temperature no longer exceeds the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF maxTemperatureExceededSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.38 | CRITICAL: Sensor Temperature has exceeded the 'Max Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF highTemperatureExceededCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.39 | INFORMATIONAL: Sensor Temperature no longer exceeds the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF highTemperatureExceededSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.40 | MINOR: Sensor Temperature has exceeded the 'High Temperature' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF lowHumidityExceededCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.41 | INFORMATIONAL: Sensor Humidity is no longer below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF lowHumidityExceededSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.42 | MINOR: Sensor Humidity has fallen below the 'Low Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF minHumidityExceededCleared | 1.3.6.1.4.1.674.10903.200.2.200.500.0.43 | INFORMATIONAL: Sensor Humidity is no longer below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF minHumidityExceededSet | 1.3.6.1.4.1.674.10903.200.2.200.500.0.44 | CRITICAL: Sensor Humidity has fallen below the 'Min Humidity' threshold value. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF outletTurnOn | 1.3.6.1.4.1.674.10903.200.2.200.500.0.45 | INFORMATIONAL: An outlet has turned on. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF outletTurnOff | 1.3.6.1.4.1.674.10903.200.2.200.500.0.46 | INFORMATIONAL: An outlet has turned off. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF actionCancelled | 1.3.6.1.4.1.674.10903.200.2.200.500.0.47 | INFORMATIONAL: An outlet action has been cancelled. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF deviceConfigurationChange | 1.3.6.1.4.1.674.10903.200.2.200.500.0.48 | INFORMATIONAL: A device configuration has been changed. The first argument is the serial number. The second argument is the device name. | ||
| NTF sensorConfigurationChange | 1.3.6.1.4.1.674.10903.200.2.200.500.0.49 | INFORMATIONAL: A sensor configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF outletConfigurationChange | 1.3.6.1.4.1.674.10903.200.2.200.500.0.50 | INFORMATIONAL: An outlet configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF phaseConfigurationChange | 1.3.6.1.4.1.674.10903.200.2.200.500.0.51 | INFORMATIONAL: A phase configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the phase number. | ||
| NTF dryContactConfigurationChange | 1.3.6.1.4.1.674.10903.200.2.200.500.0.52 | INFORMATIONAL: A dry contact configuration has been changed. The first argument is the serial number. The second argument is the device name. The third argument is the contact number. | ||
| NTF actionInit | 1.3.6.1.4.1.674.10903.200.2.200.500.0.53 | INFORMATIONAL: An outlet action has been initialized. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF actionFailed | 1.3.6.1.4.1.674.10903.200.2.200.500.0.54 | MINOR: An outlet action has failed to complete. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF actionDeleted | 1.3.6.1.4.1.674.10903.200.2.200.500.0.55 | INFORMATIONAL: An outlet action has been deleted. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF syncCommandFailed | 1.3.6.1.4.1.674.10903.200.2.200.500.0.56 | MINOR: An outlet sync command to another unit has failed. The first argument is the serial number. The second argument is the device name. The third argument is the outlet number. | ||
| NTF mPOPicFwDownloadStarted | 1.3.6.1.4.1.674.10903.200.2.200.500.0.57 | INFORMATIONAL: MPO pic fw download started. The first argument is the serial number. The second argument is the device name. | ||
| NTF mPOPicFwDownloadComplete | 1.3.6.1.4.1.674.10903.200.2.200.500.0.58 | INFORMATIONAL: MPO pic fw download complete. The first argument is the serial number. The second argument is the device name. | ||
| NTF mPOPicFwDownloadAborted | 1.3.6.1.4.1.674.10903.200.2.200.500.0.59 | INFORMATIONAL: MPO pic fw download aborted. The first argument is the serial number. The second argument is the device name. | ||
| NTF sensorCommEstablished | 1.3.6.1.4.1.674.10903.200.2.200.500.0.60 | INFORMATIONAL: Sensor comm established. The first argument is the serial number. The second argument is the device name. The third argument is the sensor number. | ||
| NTF configChangeSNMP | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1000 | MINOR: The SNMP configuration has been changed. | ||
| NTF accessViolationConsole | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1001 | MINOR: Someone attempted console login with incorrect password three times. | ||
| NTF accessViolationHTTP | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1002 | MINOR: Someone attempted login via HTTP with incorrect password. | ||
| NTF dellTestTrap | 1.3.6.1.4.1.674.10903.200.2.200.500.0.1003 | INFORMATIONAL: Trap used to test SNMP trap functionality. The first argument is a place holder for test variables. | ||
| system | 1.3.6.1.4.1.674.10903.200.3 | |||
| sysRPDUV1 | 1.3.6.1.4.1.674.10903.200.3.1 |
RFC description
Dell Remote Power Distribution Unit management for outlet control and power monitoring.
Start monitoring Dell rPDU (rack Power Distribution Unit) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.