All MIBs › DellrPDU-MIB › rPDUDeviceControlCommand
rPDUDeviceControlCommand
Module: DellrPDU-MIB
OID (symbolic): DellrPDU-MIB::rPDUDeviceControlCommand
OID (numeric): 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Setting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by each outlet's sPDUOutletPowerOnTime OID value. Setting this OID to turnAllOff (3) will turn all outlets off immediately. Setting this OID to rebootAllNow (4) will reboot all outlets immediately. Setting this OID to rebootAllSequence (5) reboots all outlets, with power returned to the outlets in the sequence defined by each outlet's rPDUOutSwitchedCfgPowerOnTime OID value. Setting this OID to rebootAllSequence (5) will cause a turnAllOffSequence to be performed. Once all outlets are off, the Rack PDU will then delay the rPDUOutSwtchedCfgRebootDuration OID time, and then perform a turnAllOnSequence. Setting this OID to turnAllOffSequence (7) will turn all outlets off as defined by each outlet's rPDUOutSwitchedCfgPowerOffTime OID value. Getting this OID will return the noCommand (6) value.
What is rPDUDeviceControlCommand?
A command object an admin writes to turn all outlets on/off immediately or in sequence, or reboot all outlets; for example writing rebootAllSequence(5) power-cycles every outlet in the order set by each outlet's configured power-on time, while a get always returns noCommand(6).
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 snmpwalk -v2c -c public <target> DellrPDU-MIB::rPDUDeviceControlCommand
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3.1 snmpget -v2c -c public <target> DellrPDU-MIB::rPDUDeviceControlCommand.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3.1 i <value>
Start monitoring Dell rPDU (rack Power Distribution Unit) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DellrPDU-MIB::rPDUDeviceControlCommand OID value, configure state conditions and alerts, and monitor any Dell rPDU (rack Power Distribution Unit) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.674 | dell | ArrayManager-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.674.10903 | pdu | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200 | pdusub | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2 | hardware | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2.200 | rPDU | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2.200.110 | rPDUDevice | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5 | rPDUDeviceControlTable | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1 | rPDUDeviceControlEntry | DellrPDU-MIB |
| 1.3.6.1.4.1.674.10903.200.2.200.110.5.1.3 | rPDUDeviceControlCommand | DellrPDU-MIB |