All MIBs › DeltaUPS-MIB
Category: Domain: Power Management, Vendor: Delta
Description: Monitors Delta brand UPS systems including battery status, input/output power, and alarm conditions.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is DeltaUPS-MIB?
DeltaUPS-MIB is a private enterprise MIB for monitoring and managing Delta brand uninterruptible power supply (UPS) systems. It is organized around standard UPS management areas—identification, control, and configuration—covering battery status, AC input/output power parameters, and alarm conditions typical of UPS devices. Its core purpose is monitoring the hardware health and power status of the UPS itself: battery charge/runtime and condition, input/output voltage and load, and active alarm/fault conditions (e.g., on battery, low battery, overload, input failure) that indicate the protected equipment's power backup is degraded or engaged. Naming conventions (dupsIdent, dupsControl, dupsConfig) mirror the structure of the IETF UPS-MIB (RFC 1628), suggesting this vendor MIB parallels or extends that standard rather than being wholly independent. It is deployed wherever Delta UPS units protect servers, network equipment, or other critical infrastructure, polled by data-center or facilities monitoring systems for power-event alerting. Network engineers evaluating or troubleshooting this functionality can download the DeltaUPS-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in DeltaUPS-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Delta UPS (uninterruptible power supply) system
Monitoring Examples
An admin would poll objects under dupsIdent to retrieve the UPS model/firmware identity, dupsConfig for configured battery and output parameters (e.g., nominal voltage, low-battery threshold), and dupsControl-related status to see current operating state such as on-battery or bypass. A transition to an on-battery or low-battery alarm state, combined with dropping output load capacity, would indicate a utility power outage is in progress and the UPS's battery runtime is running down. Because the detailed object list wasn't fully provided beyond these top-level groups, finer per-battery-cell or per-outlet objects can't be confirmed here.
What Can Be Monitored
- battery status/charge
- on-battery/alarm state
- AC input voltage/status
- AC output voltage/load
- UPS identification/firmware
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| IpAddress | |
| enterprises |
From RFC1213-MIB
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| delta | 1.3.6.1.4.1.2254 | |||
| ups | 1.3.6.1.4.1.2254.2 | |||
| upsv4 | 1.3.6.1.4.1.2254.2.4 | |||
| dupsIdent | 1.3.6.1.4.1.2254.2.4.1 | |||
| STR dupsIdentManufacturer | 1.3.6.1.4.1.2254.2.4.1.1 | DisplayString | read-only | The name of the UPS manufacturer. |
| STR dupsIdentModel | 1.3.6.1.4.1.2254.2.4.1.2 | DisplayString | read-only | The UPS Model designation. |
| STR dupsIdentUPSSoftwareVersion | 1.3.6.1.4.1.2254.2.4.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not has the same value as upsIdentAgentSoftwareVersion in some implementations. |
| STR dupsIdentAgentSoftwareVersion | 1.3.6.1.4.1.2254.2.4.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not has the same value as upsIdentUPSSoftwareVersion in some implementations. |
| STR dupsIdentName | 1.3.6.1.4.1.2254.2.4.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator. |
| STR dupsAttachedDevices | 1.3.6.1.4.1.2254.2.4.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. |
| INT dupsRatingOutputVA | 1.3.6.1.4.1.2254.2.4.1.7 | INTEGER | read-only | The magnitude of the nominal output VA rating. |
| INT dupsRatingOutputVoltage | 1.3.6.1.4.1.2254.2.4.1.8 | INTEGER | read-only | The magnitude of the nominal output voltage rating. |
| INT dupsRatingOutputFrequency | 1.3.6.1.4.1.2254.2.4.1.9 | INTEGER | read-only | The magnitude of the nominal output frequency rating. |
| INT dupsRatingInputVoltage | 1.3.6.1.4.1.2254.2.4.1.10 | INTEGER | read-only | The magnitude of the nominal input voltage rating. |
| INT dupsRatingInputFrequency | 1.3.6.1.4.1.2254.2.4.1.11 | INTEGER | read-only | The magnitude of the nominal input frequency rating. |
| INT dupsRatingBatteryVoltage | 1.3.6.1.4.1.2254.2.4.1.12 | INTEGER | read-only | The magnitude of the nominal battery voltage rating. |
| INT dupsLowTransferVoltUpBound | 1.3.6.1.4.1.2254.2.4.1.13 | INTEGER | read-only | The minimum input line voltage upper bound allowed before the UPS system transfers to battery backup. |
| INT dupsLowTransferVoltLowBound | 1.3.6.1.4.1.2254.2.4.1.14 | INTEGER | read-only | The minimum input line voltage lower bound allowed before the UPS system transfers to battery backup. |
| INT dupsHighTransferVoltUpBound | 1.3.6.1.4.1.2254.2.4.1.15 | INTEGER | read-only | The maximum input line voltage upper bound allowed before the UPS system transfers to battery backup. |
| INT dupsHighTransferVoltLowBound | 1.3.6.1.4.1.2254.2.4.1.16 | INTEGER | read-only | The maximum input line voltage lower bound allowed before the UPS system transfers to battery backup. |
| INT dupsLowBattTime | 1.3.6.1.4.1.2254.2.4.1.17 | INTEGER | read-only | Minutes, time from low battery to low battery shutdown. |
| INT dupsOutletRelays | 1.3.6.1.4.1.2254.2.4.1.18 | INTEGER | read-only | Number of outlet relay. If it is 0, the function is not available for the UPS. |
| INT dupsType | 1.3.6.1.4.1.2254.2.4.1.19 | INTEGER | read-only | Indicate the UPS type. |
| dupsControl | 1.3.6.1.4.1.2254.2.4.2 | |||
| INT dupsShutdownType | 1.3.6.1.4.1.2254.2.4.2.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off. |
| INT dupsAutoReboot | 1.3.6.1.4.1.2254.2.4.2.2 | INTEGER | read-write | In backup mode, the UPS may shutdown normally by SDA command, dry-contact remote shutdown signal or low battery shutdown. This command is used to determine the unit should restart or not next time when the power restores |
| INT dupsShutdownAction | 1.3.6.1.4.1.2254.2.4.2.3 | INTEGER | read-write | If the value is greater than 0 the UPS performs shutdown action that defined by ShutdownType after the seconds. 0, aborted. |
| INT dupsRestartAction | 1.3.6.1.4.1.2254.2.4.2.4 | INTEGER | read-write | UPS will restart after the indicated number of minutes. -1, aborted. |
| INT dupsSetOutletRelay | 1.3.6.1.4.1.2254.2.4.2.5 | INTEGER | read-write | Indicate which outlet relay, from 1,2,3... . |
| INT dupsRelayOffDelay | 1.3.6.1.4.1.2254.2.4.2.6 | INTEGER | read-write | Turn the relay off after the seconds. The relay was indicated by SetOutletRelay. |
| INT dupsRelayOnDelay | 1.3.6.1.4.1.2254.2.4.2.7 | INTEGER | read-write | Turn the relay on after the seconds. The relay was indicated by SetOutletRelay. |
| dupsConfig | 1.3.6.1.4.1.2254.2.4.3 | |||
| INT dupsConfigBuzzerAlarm | 1.3.6.1.4.1.2254.2.4.3.1 | INTEGER | read-write | UPS will keep silence but will alarm again when next power event is occurred |
| INT dupsConfigBuzzerState | 1.3.6.1.4.1.2254.2.4.3.2 | INTEGER | read-write | If it is disabled then the UPS is always muted. |
| INT dupsConfigSensitivity | 1.3.6.1.4.1.2254.2.4.3.3 | INTEGER | read-write | The seneitivity of the UPS to utility line abnormalities or noises. |
| INT dupsConfigLowVoltageTransferPoint | 1.3.6.1.4.1.2254.2.4.3.4 | INTEGER | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup. |
| INT dupsConfigHighVoltageTransferPoint | 1.3.6.1.4.1.2254.2.4.3.5 | INTEGER | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup. |
| INT dupsConfigShutdownOSDelay | 1.3.6.1.4.1.2254.2.4.3.6 | INTEGER | read-write | The operating system shutdown delay time when the input power fail. -1 will disable this option. |
| INT dupsConfigUPSBootDelay | 1.3.6.1.4.1.2254.2.4.3.7 | INTEGER | read-write | Delay the UPS startup after power restores. The power quality may not stable when power restores, this feature let the UPS wait a period of time to startup the system. |
| INT dupsConfigExternalBatteryPack | 1.3.6.1.4.1.2254.2.4.3.8 | INTEGER | read-write | Indicate the number of external battery pack. |
| dupsInput | 1.3.6.1.4.1.2254.2.4.4 | |||
| INT dupsInputNumLines | 1.3.6.1.4.1.2254.2.4.4.1 | INTEGER | read-only | The number of input lines utilized in this device. |
| INT dupsInputFrequency1 | 1.3.6.1.4.1.2254.2.4.4.2 | INTEGER | read-only | The current input line 1 frequency to the UPS system in 1/10 Hz. |
| INT dupsInputVoltage1 | 1.3.6.1.4.1.2254.2.4.4.3 | INTEGER | read-only | The Input line 1 voltage of the UPS system in 1/10 V. |
| INT dupsInputCurrent1 | 1.3.6.1.4.1.2254.2.4.4.4 | INTEGER | read-only | The Input line 1 current to the UPS system in 1/10 A. |
| INT dupsInputFrequency2 | 1.3.6.1.4.1.2254.2.4.4.5 | INTEGER | read-only | The current input line 2 frequency to the UPS system in 1/10 Hz. |
| INT dupsInputVoltage2 | 1.3.6.1.4.1.2254.2.4.4.6 | INTEGER | read-only | The Input line 2 voltage of the UPS system in 1/10 V. |
| INT dupsInputCurrent2 | 1.3.6.1.4.1.2254.2.4.4.7 | INTEGER | read-only | The Input line 2 current to the UPS system in 1/10 A. |
| INT dupsInputFrequency3 | 1.3.6.1.4.1.2254.2.4.4.8 | INTEGER | read-only | The current input line 3 frequency to the UPS system in 1/10 Hz. |
| INT dupsInputVoltage3 | 1.3.6.1.4.1.2254.2.4.4.9 | INTEGER | read-only | The Input line 3 voltage of the UPS system in 1/10 V. |
| INT dupsInputCurrent3 | 1.3.6.1.4.1.2254.2.4.4.10 | INTEGER | read-only | The Input line 3 current to the UPS system in 1/10 A. |
| dupsOutput | 1.3.6.1.4.1.2254.2.4.5 | |||
| INT dupsOutputSource | 1.3.6.1.4.1.2254.2.4.5.1 | INTEGER | read-only | The present source of output power. The enumeration none(7) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. |
| INT dupsOutputFrequency | 1.3.6.1.4.1.2254.2.4.5.2 | INTEGER | read-only | The present output frequency in 1/10 Hz. |
| INT dupsOutputNumLines | 1.3.6.1.4.1.2254.2.4.5.3 | INTEGER | read-only | The number of output lines utilized in this device. |
| INT dupsOutputVoltage1 | 1.3.6.1.4.1.2254.2.4.5.4 | INTEGER | read-only | The Output line 1 voltage of the UPS system in 1/10 V. |
| INT dupsOutputCurrent1 | 1.3.6.1.4.1.2254.2.4.5.5 | INTEGER | read-only | The Output line 1 current of the UPS system in 1/10 A. |
| INT dupsOutputPower1 | 1.3.6.1.4.1.2254.2.4.5.6 | INTEGER | read-only | The Output line 1 real power of the UPS system in watts. |
| INT dupsOutputLoad1 | 1.3.6.1.4.1.2254.2.4.5.7 | INTEGER | read-only | The current UPS output line 1 load expressed in percent of rated capacity. |
| INT dupsOutputVoltage2 | 1.3.6.1.4.1.2254.2.4.5.8 | INTEGER | read-only | The Output line 2 voltage of the UPS system in 1/10 V. |
| INT dupsOutputCurrent2 | 1.3.6.1.4.1.2254.2.4.5.9 | INTEGER | read-only | The Output line 2 current of the UPS system in 1/10 A. |
| INT dupsOutputPower2 | 1.3.6.1.4.1.2254.2.4.5.10 | INTEGER | read-only | The Output line 2 real power of the UPS system in watts. |
| INT dupsOutputLoad2 | 1.3.6.1.4.1.2254.2.4.5.11 | INTEGER | read-only | The current UPS output line 2 load expressed in percent of rated capacity. |
| INT dupsOutputVoltage3 | 1.3.6.1.4.1.2254.2.4.5.12 | INTEGER | read-only | The Output line 3 voltage of the UPS system in 1/10 V. |
| INT dupsOutputCurrent3 | 1.3.6.1.4.1.2254.2.4.5.13 | INTEGER | read-only | The Output line 3 current of the UPS system in 1/10 A. |
| INT dupsOutputPower3 | 1.3.6.1.4.1.2254.2.4.5.14 | INTEGER | read-only | The Output line 3 real power of the UPS system in watts. |
| INT dupsOutputLoad3 | 1.3.6.1.4.1.2254.2.4.5.15 | INTEGER | read-only | The current UPS output line 3 load expressed in percent of rated capacity. |
| dupsBypass | 1.3.6.1.4.1.2254.2.4.6 | |||
| INT dupsBypassFrequency | 1.3.6.1.4.1.2254.2.4.6.1 | INTEGER | read-only | The present bypass frequency in 1/10 Hz. |
| INT dupsBypassNumLines | 1.3.6.1.4.1.2254.2.4.6.2 | INTEGER | read-only | The number of bypass lines utilized in this device. |
| INT dupsBypassVoltage1 | 1.3.6.1.4.1.2254.2.4.6.3 | INTEGER | read-only | The bypass line 1 voltage of the UPS system in 1/10 V. |
| INT dupsBypassCurrent1 | 1.3.6.1.4.1.2254.2.4.6.4 | INTEGER | read-only | The bypass line 1 current of the UPS system in 1/10 A. |
| INT dupsBypassPower1 | 1.3.6.1.4.1.2254.2.4.6.5 | INTEGER | read-only | The bypass line 1 real power of the UPS system in watts. |
| INT dupsBypassVoltage2 | 1.3.6.1.4.1.2254.2.4.6.6 | INTEGER | read-only | The bypass line 2 voltage of the UPS system in 1/10 V. |
| INT dupsBypassCurrent2 | 1.3.6.1.4.1.2254.2.4.6.7 | INTEGER | read-only | The bypass line 2 current of the UPS system in 1/10 A. |
| INT dupsBypassPower2 | 1.3.6.1.4.1.2254.2.4.6.8 | INTEGER | read-only | The bypass line 2 real power of the UPS system in watts. |
| INT dupsBypassVoltage3 | 1.3.6.1.4.1.2254.2.4.6.9 | INTEGER | read-only | The bypass line 3 voltage of the UPS system in 1/10 V. |
| INT dupsBypassCurrent3 | 1.3.6.1.4.1.2254.2.4.6.10 | INTEGER | read-only | The bypass line 3 current of the UPS system in 1/10 A. |
| INT dupsBypassPower3 | 1.3.6.1.4.1.2254.2.4.6.11 | INTEGER | read-only | The bypass line 3 real power of the UPS system in watts. |
| dupsBattery | 1.3.6.1.4.1.2254.2.4.7 | |||
| INT dupsBatteryCondiction | 1.3.6.1.4.1.2254.2.4.7.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries when AC normal. |
| INT dupsBatteryStatus | 1.3.6.1.4.1.2254.2.4.7.2 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries when AC failed. A value of ok indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of low indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of depleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). |
| INT dupsBatteryCharge | 1.3.6.1.4.1.2254.2.4.7.3 | INTEGER | read-only | |
| INT dupsSecondsOnBattery | 1.3.6.1.4.1.2254.2.4.7.4 | INTEGER | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power. |
| INT dupsBatteryEstimatedTime | 1.3.6.1.4.1.2254.2.4.7.5 | INTEGER | read-only | Estimated time from backup to low battery shutdown. |
| INT dupsBatteryVoltage | 1.3.6.1.4.1.2254.2.4.7.6 | INTEGER | read-only | The magnitude of the present battery voltage in 1/10 V. |
| INT dupsBatteryCurrent | 1.3.6.1.4.1.2254.2.4.7.7 | INTEGER | read-only | The present battery current in 1/10 A. |
| INT dupsBatteryCapacity | 1.3.6.1.4.1.2254.2.4.7.8 | INTEGER | read-only | An estimate of the battery charge remaining expressed as a percent of full charge. |
| INT dupsTemperature | 1.3.6.1.4.1.2254.2.4.7.9 | INTEGER | read-only | The ambient temperature at or near the UPS Battery casing. |
| STR dupsLastReplaceDate | 1.3.6.1.4.1.2254.2.4.7.10 | DisplayString | read-only | The last battery replacement date. The format is YYYYMMDD. |
| STR dupsNextReplaceDate | 1.3.6.1.4.1.2254.2.4.7.11 | DisplayString | read-only | The next battery replacement date. The format is YYYYMMDD. |
| dupsTest | 1.3.6.1.4.1.2254.2.4.8 | |||
| INT dupsTestType | 1.3.6.1.4.1.2254.2.4.8.1 | INTEGER | read-write | Perform the UPS Test procedure. |
| INT dupsTestResultsSummary | 1.3.6.1.4.1.2254.2.4.8.2 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), generalTestFail(3), and batteryTestFail(4) indicate that the test completed either successfully, with a warning, or with an error, respectively.Tests which have not yet concluded are indicated by inProgress(2). The value noTestsInitiated(0) indicates that no previous test results are available. |
| STR dupsTestResultsDetail | 1.3.6.1.4.1.2254.2.4.8.3 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. |
| dupsAlarm | 1.3.6.1.4.1.2254.2.4.9 | |||
| INT dupsAlarmDisconnect | 1.3.6.1.4.1.2254.2.4.9.1 | INTEGER | read-only | Does the UPS disconnect? |
| INT dupsAlarmPowerFail | 1.3.6.1.4.1.2254.2.4.9.2 | INTEGER | read-only | Does the input power fail? |
| INT dupsAlarmBatteryLow | 1.3.6.1.4.1.2254.2.4.9.3 | INTEGER | read-only | Are the UPS batteries low? |
| INT dupsAlarmLoadWarning | 1.3.6.1.4.1.2254.2.4.9.4 | INTEGER | read-only | Does the UPS load percent over the load warning value? |
| INT dupsAlarmLoadSeverity | 1.3.6.1.4.1.2254.2.4.9.5 | INTEGER | read-only | Does the UPS load percent over the load severity value? |
| INT dupsAlarmLoadOnBypass | 1.3.6.1.4.1.2254.2.4.9.6 | INTEGER | read-only | Does the UPS load on bypass? |
| INT dupsAlarmUPSFault | 1.3.6.1.4.1.2254.2.4.9.7 | INTEGER | read-only | Does the UPS general fail? |
| INT dupsAlarmBatteryGroundFault | 1.3.6.1.4.1.2254.2.4.9.8 | INTEGER | read-only | Does the UPS battery ground fault? |
| INT dupsAlarmTestInProgress | 1.3.6.1.4.1.2254.2.4.9.9 | INTEGER | read-only | Does the UPS test in progress? |
| INT dupsAlarmBatteryTestFail | 1.3.6.1.4.1.2254.2.4.9.10 | INTEGER | read-only | Does the UPS test fail? |
| INT dupsAlarmFuseFailure | 1.3.6.1.4.1.2254.2.4.9.11 | INTEGER | read-only | Does the UPS fuse failure? |
| INT dupsAlarmOutputOverload | 1.3.6.1.4.1.2254.2.4.9.12 | INTEGER | read-only | Does the UPS output overload? |
| INT dupsAlarmOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.9.13 | INTEGER | read-only | Does the UPS output overcurrent? |
| INT dupsAlarmInverterAbnormal | 1.3.6.1.4.1.2254.2.4.9.14 | INTEGER | read-only | Does the UPS inverter abnormal? |
| INT dupsAlarmRectifierAbnormal | 1.3.6.1.4.1.2254.2.4.9.15 | INTEGER | read-only | Does the UPS rectifier abnormal? |
| INT dupsAlarmReserveAbnormal | 1.3.6.1.4.1.2254.2.4.9.16 | INTEGER | read-only | Does the UPS reserve abnormal? |
| INT dupsAlarmLoadOnReserve | 1.3.6.1.4.1.2254.2.4.9.17 | INTEGER | read-only | Does the UPS load on reserve? |
| INT dupsAlarmOverTemperature | 1.3.6.1.4.1.2254.2.4.9.18 | INTEGER | read-only | Does the UPS over heat? |
| INT dupsAlarmOutputBad | 1.3.6.1.4.1.2254.2.4.9.19 | INTEGER | read-only | Is the UPS output abnormal? |
| INT dupsAlarmBypassBad | 1.3.6.1.4.1.2254.2.4.9.20 | INTEGER | read-only | Is the UPS bypass bad? |
| INT dupsAlarmUPSOff | 1.3.6.1.4.1.2254.2.4.9.21 | INTEGER | read-only | Is the UPS in standby mode? |
| INT dupsAlarmChargerFail | 1.3.6.1.4.1.2254.2.4.9.22 | INTEGER | read-only | Does the UPS charger fail? |
| INT dupsAlarmFanFail | 1.3.6.1.4.1.2254.2.4.9.23 | INTEGER | read-only | Does the UPS fan fail? |
| INT dupsAlarmEconomicMode | 1.3.6.1.4.1.2254.2.4.9.24 | INTEGER | read-only | Indicates whether the UPS is in the economic mode. |
| INT dupsAlarmOutputOff | 1.3.6.1.4.1.2254.2.4.9.25 | INTEGER | read-only | Indicates whether the UPS output is turned off or not. |
| INT dupsAlarmSmartShutdown | 1.3.6.1.4.1.2254.2.4.9.26 | INTEGER | read-only | Indicates whether the Smart Shutdown is in progress. |
| INT dupsAlarmEmergencyPowerOff | 1.3.6.1.4.1.2254.2.4.9.27 | INTEGER | read-only | UPS emergency power off. |
| INT dupsAlarmUPSShutdown | 1.3.6.1.4.1.2254.2.4.9.28 | INTEGER | read-only | UPS shutdown. |
| dupsEnvironment | 1.3.6.1.4.1.2254.2.4.10 | |||
| INT dupsEnvTemperature | 1.3.6.1.4.1.2254.2.4.10.1 | INTEGER | read-only | The ambient environmental temperature. |
| INT dupsEnvHumidity | 1.3.6.1.4.1.2254.2.4.10.2 | INTEGER | read-only | The environmental humidity. |
| INT dupsEnvSetTemperatureLimit | 1.3.6.1.4.1.2254.2.4.10.3 | INTEGER | read-write | Alarm dupsAlarmOverTemperature on when the environmental temperature over the value. |
| INT dupsEnvSetHumidityLimit | 1.3.6.1.4.1.2254.2.4.10.4 | INTEGER | read-write | Alarm dupsAlarmOverHumidity on when the environmental humidity over the value. |
| INT dupsEnvSetEnvRelay1 | 1.3.6.1.4.1.2254.2.4.10.5 | INTEGER | read-write | |
| INT dupsEnvSetEnvRelay2 | 1.3.6.1.4.1.2254.2.4.10.6 | INTEGER | read-write | |
| INT dupsEnvSetEnvRelay3 | 1.3.6.1.4.1.2254.2.4.10.7 | INTEGER | read-write | |
| INT dupsEnvSetEnvRelay4 | 1.3.6.1.4.1.2254.2.4.10.8 | INTEGER | read-write | |
| INT dupsAlarmOverEnvTemperature | 1.3.6.1.4.1.2254.2.4.10.9 | INTEGER | read-only | Does the environment over temperature? |
| INT dupsAlarmOverEnvHumidity | 1.3.6.1.4.1.2254.2.4.10.10 | INTEGER | read-only | Does the environment over humidity? |
| INT dupsAlarmEnvRelay1 | 1.3.6.1.4.1.2254.2.4.10.11 | INTEGER | read-only | |
| INT dupsAlarmEnvRelay2 | 1.3.6.1.4.1.2254.2.4.10.12 | INTEGER | read-only | |
| INT dupsAlarmEnvRelay3 | 1.3.6.1.4.1.2254.2.4.10.13 | INTEGER | read-only | |
| INT dupsAlarmEnvRelay4 | 1.3.6.1.4.1.2254.2.4.10.14 | INTEGER | read-only | |
| dupsTraps | 1.3.6.1.4.1.2254.2.4.20 | |||
| NTF dupsCommunicationLost | 1.3.6.1.4.1.2254.2.4.20.0.1 | SEVER: Communication with the UPS failed. | ||
| NTF dupsCommunicationEstablished | 1.3.6.1.4.1.2254.2.4.20.0.2 | INFORMATION: Communication with the UPS reestablished. | ||
| NTF dupsPowerFail | 1.3.6.1.4.1.2254.2.4.20.0.3 | WARNING: Power failed! The UPS is operating on battery power. | ||
| NTF dupsPowerRestored | 1.3.6.1.4.1.2254.2.4.20.0.4 | INFORMATION: Power restored! The utility power restored. | ||
| NTF dupsLowBattery | 1.3.6.1.4.1.2254.2.4.20.0.5 | SEVER: The UPS batteries are low and will soon be exhausted. | ||
| NTF dupsReturnFromLowBattery | 1.3.6.1.4.1.2254.2.4.20.0.6 | INFORMATION: The UPS has returned from a low battery condition. | ||
| NTF dupsLoadWarning | 1.3.6.1.4.1.2254.2.4.20.0.7 | INFORMATION: Loading percent of the UPS over the Load Warning value. | ||
| NTF dupsNoLongerLoadWarning | 1.3.6.1.4.1.2254.2.4.20.0.8 | INFORMATION: Returnd from Load Warning condition. | ||
| NTF dupsLoadSeverity | 1.3.6.1.4.1.2254.2.4.20.0.9 | Warning: Loading percent of the UPS over the Load Severity value. | ||
| NTF dupsNoLongerLoadSeverity | 1.3.6.1.4.1.2254.2.4.20.0.10 | INFORMATION: Returned from Load Severity condition. | ||
| NTF dupsLoadOnBypass | 1.3.6.1.4.1.2254.2.4.20.0.11 | SEVER: The UPS loads on bypass. | ||
| NTF dupsNoLongerLoadOnBypass | 1.3.6.1.4.1.2254.2.4.20.0.12 | INFORMATION: The UPS is not on bypass mode. | ||
| NTF dupsUPSFault | 1.3.6.1.4.1.2254.2.4.20.0.13 | SEVER: A general fault caused in the UPS. | ||
| NTF dupsReturnFromUPSFault | 1.3.6.1.4.1.2254.2.4.20.0.14 | INFORMATION: The UPS is returned from general fault. | ||
| NTF dupsBatteryGroundFault | 1.3.6.1.4.1.2254.2.4.20.0.15 | SEVER: The UPS battery ground fault. | ||
| NTF dupsNoLongerBatteryFault | 1.3.6.1.4.1.2254.2.4.20.0.16 | INFORMATION: The UPS recovered from battery ground fault. | ||
| NTF dupsTestInProgress | 1.3.6.1.4.1.2254.2.4.20.0.17 | INFORMATION: The UPS test in progress. | ||
| NTF dupsBatteryTestFail | 1.3.6.1.4.1.2254.2.4.20.0.18 | SEVER: The UPS test fail. | ||
| NTF dupsFuseFailure | 1.3.6.1.4.1.2254.2.4.20.0.19 | SEVER: The UPS fuse failed. | ||
| NTF dupsFuseRecovered | 1.3.6.1.4.1.2254.2.4.20.0.20 | INFORMATION: The UPS fuse recovered. | ||
| NTF dupsOutputOverload | 1.3.6.1.4.1.2254.2.4.20.0.21 | SEVER: The UPS overload!. | ||
| NTF dupsNoLongerOverload | 1.3.6.1.4.1.2254.2.4.20.0.22 | INFORMATION: Recovered from UPS overload. | ||
| NTF dupsOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.20.0.23 | SEVER: The UPS output overcurrent. | ||
| NTF dupsNoLongerOutputOverCurrent | 1.3.6.1.4.1.2254.2.4.20.0.24 | INFORMATION: Recovered from UPS overcurrent. | ||
| NTF dupsInverterAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.25 | SEVER: The UPS inverter abnormal. | ||
| NTF dupsInverterRecovered | 1.3.6.1.4.1.2254.2.4.20.0.26 | INFORMATION: Recovered from UPS inverter abnormal. | ||
| NTF dupsRectifierAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.27 | SEVER: The UPS rectifier abnormal. | ||
| NTF dupsRectifierRecovered | 1.3.6.1.4.1.2254.2.4.20.0.28 | INFORMATION: The UPS recovered from rectifier abnormal. | ||
| NTF dupsReserveAbnormal | 1.3.6.1.4.1.2254.2.4.20.0.29 | SEVER: The UPS rectifier abnormal. | ||
| NTF dupsReserveRecovered | 1.3.6.1.4.1.2254.2.4.20.0.30 | INFORMATION: The UPS rectifier abnormal. | ||
| NTF dupsLoadOnReserve | 1.3.6.1.4.1.2254.2.4.20.0.31 | SEVER: The UPS load on reserve. | ||
| NTF dupsNoLongerLoadOnReserve | 1.3.6.1.4.1.2254.2.4.20.0.32 | INFORMATION: The UPS no longer load on reserve. | ||
| NTF dupsEnvOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.33 | WARNING: The environment overtemperature. | ||
| NTF dupsNoLongerEnvOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.34 | INFORMATION: The environment recovered from overtemperature. | ||
| NTF dupsEnvOverHumidity | 1.3.6.1.4.1.2254.2.4.20.0.35 | WARNING: The environment overhumidity. | ||
| NTF dupsNoLongerEnvOverHumidity | 1.3.6.1.4.1.2254.2.4.20.0.36 | INFORMATION: The environment recovered from overhumidity. | ||
| NTF dupsEnvRelay1Alarm | 1.3.6.1.4.1.2254.2.4.20.0.37 | INFORMATION: The environment relay1 is not in normal state. | ||
| NTF dupsEnvRelay1Normal | 1.3.6.1.4.1.2254.2.4.20.0.38 | INFORMATION: The environment relay1 is in normal state. | ||
| NTF dupsEnvRelay2Alarm | 1.3.6.1.4.1.2254.2.4.20.0.39 | INFORMATION: The environment relay2 is not in normal state. | ||
| NTF dupsEnvRelay2Normal | 1.3.6.1.4.1.2254.2.4.20.0.40 | INFORMATION: The environment relay2 is in normal state. | ||
| NTF dupsEnvRelay3Alarm | 1.3.6.1.4.1.2254.2.4.20.0.41 | INFORMATION: The environment relay3 is not in normal state. | ||
| NTF dupsEnvRelay3Normal | 1.3.6.1.4.1.2254.2.4.20.0.42 | INFORMATION: The environment relay3 is in normal state. | ||
| NTF dupsEnvRelay4Alarm | 1.3.6.1.4.1.2254.2.4.20.0.43 | INFORMATION: The environment relay4 is not in normal state. | ||
| NTF dupsEnvRelay4Normal | 1.3.6.1.4.1.2254.2.4.20.0.44 | INFORMATION: The environment relay4 is in normal state. | ||
| NTF dupsSmartShutdown | 1.3.6.1.4.1.2254.2.4.20.0.45 | SEVER: Smart Shutdown is initiated. | ||
| NTF dupsCancelShutdown | 1.3.6.1.4.1.2254.2.4.20.0.46 | INFORMATION: Cancel UPS Shutdown. | ||
| NTF dupsTestCompleted | 1.3.6.1.4.1.2254.2.4.20.0.47 | INFORMATION: This trap is sent upon completion of a UPS diagnostic test. | ||
| NTF dupsEPOON | 1.3.6.1.4.1.2254.2.4.20.0.48 | INFORMATION: This trap is sent when emergency power off is on. | ||
| NTF dupsEPOOFF | 1.3.6.1.4.1.2254.2.4.20.0.49 | INFORMATION: This trap is sent when UPS recover from emergency power off. | ||
| NTF dupsOverTemperature | 1.3.6.1.4.1.2254.2.4.20.0.50 | SEVER: This trap is sent when the UPS is over heat. | ||
| NTF dupsNormalTemperature | 1.3.6.1.4.1.2254.2.4.20.0.51 | INFORMATION: This trap is sent when UPS recover from over heat. | ||
| NTF dupsBattReplace | 1.3.6.1.4.1.2254.2.4.20.0.52 | WARNING: The battery needs to be replaced. | ||
| NTF dupsReturnFromBattReplace | 1.3.6.1.4.1.2254.2.4.20.0.53 | INFORMATION: The UPS recovered from battery replacement. |
RFC description