DellrPDU-MIB :: rPDUDeviceConfigColdstartDelay

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › DellrPDU-MIB › rPDUDeviceConfigColdstartDelay

rPDUDeviceConfigColdstartDelay

Module: DellrPDU-MIB

OID (symbolic): DellrPDU-MIB::rPDUDeviceConfigColdstartDelay

OID (numeric): 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets.

What is rPDUDeviceConfigColdstartDelay?

The number of seconds an admin configures the PDU to wait, after receiving input power, before it turns on master power to its outlets -- useful for staggering equipment recovery after a site-wide power event.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4
snmpwalk -v2c -c public <target> DellrPDU-MIB::rPDUDeviceConfigColdstartDelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4.1
snmpget -v2c -c public <target> DellrPDU-MIB::rPDUDeviceConfigColdstartDelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4.1 i <value>

Start monitoring Dell rPDU (rack Power Distribution Unit) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DellrPDU-MIB::rPDUDeviceConfigColdstartDelay OID value, configure state conditions and alerts, and monitor any Dell rPDU (rack Power Distribution Unit) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.674dellArrayManager-MIB
Numeric OIDNameModule
1.3.6.1.4.1.674.10903pduDellrPDU-MIB
1.3.6.1.4.1.674.10903.200pdusubDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2hardwareDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2.200rPDUDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2.200.110rPDUDeviceDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2.200.110.3rPDUDeviceConfigTableDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2.200.110.3.1rPDUDeviceConfigEntryDellrPDU-MIB
1.3.6.1.4.1.674.10903.200.2.200.110.3.1.4rPDUDeviceConfigColdstartDelayDellrPDU-MIB