All MIBs › ATEN-PE-CFG-STR
Organization: ATEN
Last Updated: 2013-10-31
Category: Textual Conventions and Registries, Vendor: ATEN
Description: Defines string data structures and configuration objects used by ATEN PE series PDU management MIBs.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is ATEN-PE-CFG-STR?
ATEN-PE-CFG-STR is an ATEN enterprise MIB defining the string/configuration data structures used by ATEN's PE-series power distribution unit (PDU) management MIBs, mounted under enterprises.aten.atenProducts.overip.poweroverip.pe. It exposes device-level electrical telemetry through deviceValueTable (deviceCurrent, deviceVoltage, devicePower, devicePowerDissipation, devicePowerFactor) and equivalent per-outlet telemetry in outletValueTable, alongside a sensorValueTable reporting temperature, humidity, and pressure from up to six environmental sensors. deviceConfigTable and deviceSensorTresholdTable hold minimum/maximum measurement thresholds for current, voltage, power, and environmental readings, while per-outlet objects (outlet1Status through outlet27Status and beyond) allow both status display and remote on/off/reboot control. POP (Power Outlet Protection) and CAP (Current Awareness Protection) objects add configurable overload-protection modes and per-outlet priority for controlled shutdown sequencing. It is deployed on ATEN PE-series switched/metered rack PDUs, and administrators can download the ATEN-PE-CFG-STR MIB file to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in ATEN-PE-CFG-STR. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- ATEN PE-series managed/switched PDUs
Monitoring Examples
An operator polls deviceCurrent and deviceMaxCurMT to check whether total PDU load is approaching its configured maximum-current threshold, and reviews individual outletNStatus values; an outlet reporting fault(5) alongside device current near its threshold would indicate an overloaded outlet that POP protection may soon shut down.
What Can Be Monitored
- device and per-outlet current/voltage/power/power-factor
- environmental sensor temperature/humidity/pressure
- configurable measurement thresholds
- per-outlet on/off/reboot status
- POP (power protection) and CAP priority mode settings
- door sensor status
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Gauge | |
| IpAddress | |
| TimeTicks | |
| enterprises |
From RFC1213-MIB
| DisplayString |
| KeyChange |
From SNMPv2-SMI
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE |
From SNMPv2-TC
| TEXTUAL-CONVENTION |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| aten | 1.3.6.1.4.1.21317 | ATEN PE MIB | ||
| atenProducts | 1.3.6.1.4.1.21317.1 | |||
| overip | 1.3.6.1.4.1.21317.1.3 | |||
| poweroverip | 1.3.6.1.4.1.21317.1.3.2 | |||
| pe | 1.3.6.1.4.1.21317.1.3.2.2 | |||
| userManagement | 1.3.6.1.4.1.21317.1.3.2.2.1 | |||
| usrListTable | 1.3.6.1.4.1.21317.1.3.2.2.1.1 | not-accessible | A list of user. The number of user is given by the value of usrcfgNumber. | |
| usrListEntry | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1 | not-accessible | Status and parameter values for a pe8208 user. | |
| INT usrIndex | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.1 | INTEGER | read-only | The value of usrIndex for the user. We have 1 administrator and 8 users. The index 9 will be the administrator. |
| INT usrType | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.2 | INTEGER | read-only | The user's type. |
| STR usrName | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.3 | DisplayString | read-write | A textual string containing name of the user. string length: 1~16 |
| STR usrPassword | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.4 | DisplayString | read-write | A textual string containing password of the user. string length: 1~16 |
| INT usrPort1Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.5 | INTEGER | read-write | Display or set this user's outlet 1 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort2Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.6 | INTEGER | read-write | Display or set this user's outlet 2 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort3Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.7 | INTEGER | read-write | Display or set this user's outlet 3 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort4Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.8 | INTEGER | read-write | Display or set this user's outlet 4 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort5Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.9 | INTEGER | read-write | Display or set this user's outlet 5 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort6Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.10 | INTEGER | read-write | Dispaly or set this user's outlet 6 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort7Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.11 | INTEGER | read-write | Display or set this user's outlet 7 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort8Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.12 | INTEGER | read-write | Display or set this user's outlet 8 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort9Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.13 | INTEGER | read-write | Display or set this user's outlet 9 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort10Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.14 | INTEGER | read-write | Display or set this user's outlet 10 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort11Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.15 | INTEGER | read-write | Display or set this user's outlet 11 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort12Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.16 | INTEGER | read-write | Display or set this user's outlet 12 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort13Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.17 | INTEGER | read-write | Display or set this user's outlet 13 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort14Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.18 | INTEGER | read-write | Display or set this user's outlet 14 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort15Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.19 | INTEGER | read-write | Display or set this user's outlet 15 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort16Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.20 | INTEGER | read-write | Display or set this user's outlet 16 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort17Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.21 | INTEGER | read-write | Display or set this user's outlet 17 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort18Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.22 | INTEGER | read-write | Display or set this user's outlet 18 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort19Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.23 | INTEGER | read-write | Display or set this user's outlet 19 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort20Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.24 | INTEGER | read-write | Display or set this user's outlet 20 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort21Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.25 | INTEGER | read-write | Display or set this user's outlet 21 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort22Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.26 | INTEGER | read-write | Display or set this user's outlet 22 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort23Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.27 | INTEGER | read-write | Display or set this user's outlet 23 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort24Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.28 | INTEGER | read-write | Display or set this user's outlet 24 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort25Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.29 | INTEGER | read-write | Display or set this user's outlet 25 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort26Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.30 | INTEGER | read-write | Display or set this user's outlet 26 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort27Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.31 | INTEGER | read-write | Display or set this user's outlet 27 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort28Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.32 | INTEGER | read-write | Display or set this user's outlet 28 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort29Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.33 | INTEGER | read-write | Display or set this user's outlet 29 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort30Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.34 | INTEGER | read-write | Display or set this user's outlet 30 authority. Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort31Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.35 | INTEGER | read-write | Display or set this user's outlet 31 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort32Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.36 | INTEGER | read-write | Display or set this user's outlet 32 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort33Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.37 | INTEGER | read-write | Display or set this user's outlet 33 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort34Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.38 | INTEGER | read-write | Display or set this user's outlet 34 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort35Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.39 | INTEGER | read-write | Display or set this user's outlet 35 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort36Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.40 | INTEGER | read-write | Display or set this user's outlet 36 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort37Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.41 | INTEGER | read-write | Display or set this user's outlet 37 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort38Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.42 | INTEGER | read-write | Display or set this user's outlet 38 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort39Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.43 | INTEGER | read-write | Display or set this user's outlet 39 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort40Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.44 | INTEGER | read-write | Display or set this user's outlet 40 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort41Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.45 | INTEGER | read-write | Display or set this user's outlet 41 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrPort42Auth | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.46 | INTEGER | read-write | Display or set this user's outlet 42 authority Port in the pe of series represents outlet. Port in the Energy monitor of series represents a bank or a pdu. |
| INT usrEnable | 1.3.6.1.4.1.21317.1.3.2.2.1.1.1.47 | INTEGER | read-write | Display or set this user is enable or not |
| control | 1.3.6.1.4.1.21317.1.3.2.2.2 | |||
| device | 1.3.6.1.4.1.21317.1.3.2.2.2.1 | |||
| STR modelName | 1.3.6.1.4.1.21317.1.3.2.2.2.1.1 | DisplayString | read-only | Indicate PE device model name. |
| STR deviceName | 1.3.6.1.4.1.21317.1.3.2.2.2.1.2 | DisplayString | read-write | The name of PE device. string length: 1~39 NOTE: Input string as /empty to set this object to NULL. |
| deviceValueTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3 | not-accessible | Device value table. This table displays device's current, voltage, power and power dissipation. | |
| deviceValueEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1 | not-accessible | Single deviceValue entry containing device info. | |
| INT deviceValueIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.1 | INTEGER | read-only | Index of deviceValue. |
| STR deviceCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.2 | DisplayString | read-only | Device electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR deviceVoltage | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.3 | DisplayString | read-only | Device voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR devicePower | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.4 | DisplayString | read-only | Device power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR devicePowerDissipation | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.5 | DisplayString | read-only | Device power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| INT inputMaxVoltage | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.6 | INTEGER | read-only | Device input Voltage value. unit:(V) If the device does not support this OID, we show value 0. |
| INT inputMaxCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.7 | INTEGER | read-only | Device input Current value. unit:(A) If the device does not support this OID, we show value 0. |
| INT powerCapacity | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.8 | INTEGER | read-only | Device power Capacity value.unit:(VA) If the device does not support this OID, we show value 0. |
| STR devicePowerFactor | 1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.9 | DisplayString | read-only | Device power Factor value. If the device does not support this OID, it returns: not-support. |
| sensorValueTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4 | not-accessible | Device's sensor value table. This table displays sensor's temperature, humidity and pressure. | |
| sensorValueEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1 | not-accessible | Single device's sensor value entry containing device info. | |
| INT sensorValueIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.1 | INTEGER | read-only | Index of sensor number. |
| STR sensorTemperature | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.2 | DisplayString | read-only | Sensor's Temperature value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR sensorHumidity | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.3 | DisplayString | read-only | Sensor's Humidity value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR sensorPressure | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.4 | DisplayString | read-only | Sensor's Pressure value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| INT sensorProperty | 1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.5 | INTEGER | read-only | Sensor's Property. |
| deviceOutletStatusTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.5 | not-accessible | Device outlet status value table. | |
| deviceOutletStatusEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1 | not-accessible | Single deviceOutletStatus entry containing device info. | |
| INT deviceOutletStatusIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.1 | INTEGER | read-only | Index of deviceOutletStatus |
| INT displayOutletStatus | 1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.2 | INTEGER | read-only | Display outlet status. |
| deviceConfigTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6 | not-accessible | Device configuration table | |
| deviceConfigEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1 | not-accessible | Single deviceConfig entry containing device info. | |
| INT deviceConfigIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.1 | INTEGER | read-only | Index of deviceConfig |
| INT deviceMinCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.2 | INTEGER | read-write | Display or set device minimum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320. NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMaxCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.3 | INTEGER | read-write | Display or set device maximum electric current measurement threshold. Example: range 0.0~32.0 represents 0~320 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMinVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.4 | INTEGER | read-write | Display or set device minimum voltage measurement threshold. Exapmple: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMaxVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.5 | INTEGER | read-write | Display or set device maximum voltage measurement threshold. Example: range 90.0~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMinPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.6 | INTEGER | read-write | Display or set device minimum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMaxPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.7 | INTEGER | read-write | Display or set device maximum power measurement threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceMaxPDMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.8 | INTEGER | read-write | Display or set device maximum power dissipation measurement threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| deviceSensorTresholdTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7 | not-accessible | Device environment value table | |
| deviceSensorTresholdEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1 | not-accessible | Device's sensor Environment entry containing sensor info. | |
| INT deviceSensorTresholdIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.1 | INTEGER | read-only | Index of sensor number |
| INT sensorMinTempMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.2 | INTEGER | read-write | Display or set sensor minimum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT sensorMaxTempMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.3 | INTEGER | read-write | Display or set sensor maximum temperature measurement threshold. Example: range -20.0 ~ 60.0 represents -200~600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT sensorMinHumMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.4 | INTEGER | read-write | Display or set sensor minimum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT sensorMaxHumMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.5 | INTEGER | read-write | Display or set sensor maximum humidity measurement threshold. Example: range 15.0 ~ 95.0 represents 150~950 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT sensorMinPressMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.6 | INTEGER | read-write | Display or set sensor minimum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT sensorMaxPressMT | 1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.7 | INTEGER | read-write | Display or set sensor maximum pressure measurement threshold. Example: range -250.0 ~ 250.0 represents -2500 ~ 2500 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT deviceOutletControl | 1.3.6.1.4.1.21317.1.3.2.2.2.1.8 | INTEGER | read-write | This function is used for all outlet ports control. Set off(1) to turn off for all outlet ports. Set on(2) to turn on for all outlet ports. Get this object always return nostatus(3), because there is no device status. |
| INT deviceOutletReboot | 1.3.6.1.4.1.21317.1.3.2.2.2.1.9 | INTEGER | read-write | This function is used for all outlet ports to reboot. Only when outlet status is ON can do outlet reboot action to all ports. Set yes(2) to reboot all outlet ports. Get this object always return no(1). |
| INT switchable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.10 | INTEGER | read-only | Outlet is switchable or not. |
| INT perportreading | 1.3.6.1.4.1.21317.1.3.2.2.2.1.11 | INTEGER | read-only | Outlet is per-port reading or not. |
| INT sensornumber | 1.3.6.1.4.1.21317.1.3.2.2.2.1.12 | INTEGER | read-only | Sensor number. |
| INT outletnumber | 1.3.6.1.4.1.21317.1.3.2.2.2.1.13 | INTEGER | read-only | Outlet number. |
| INT banknumber | 1.3.6.1.4.1.21317.1.3.2.2.2.1.14 | INTEGER | read-only | Bank number. |
| doorSensor | 1.3.6.1.4.1.21317.1.3.2.2.2.1.16 | |||
| INT doorSensorStatus | 1.3.6.1.4.1.21317.1.3.2.2.2.1.16.1 | INTEGER | read-only | Display door sensor status. close(0) represents door close. open(1) represents door open. not-attached(2) represents door sensor don't attach to device. |
| INT doorSensorType | 1.3.6.1.4.1.21317.1.3.2.2.2.1.16.2 | INTEGER | read-write | Door Sensor Type Selection |
| pop | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17 | |||
| INT enablePOPmode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.1 | INTEGER | read-write | Enable/Disable POP mode. |
| INT popThreshold | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.2 | INTEGER | read-write | (-1)means default value same as Bank Max Current 16 A. Example: range 0.0~32.0 represents 0~320 You can define the POP threshold or set as default(-1) value. |
| INT enableOutletPOPmode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.3 | INTEGER | read-write | Enable/Disable Outlet POP mode. |
| INT enableLIFOPOPmode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.4 | INTEGER | read-write | Enable/Disable LIFO POP mode. |
| INT enablePriorityPOPmode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.17.5 | INTEGER | read-write | Enable/Disable Priority POP mode. |
| cap | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18 | |||
| INT enableCAPmode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.1 | INTEGER | read-write | Enable/Disable CAP mode. |
| outletCAPTable | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2 | not-accessible | Outlet CAP table | |
| outletCAPEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1 | not-accessible | Outlet CAP entry containing CAP info. | |
| INT outletCAPIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.1 | INTEGER | read-only | Index of outlet's CAP configuration |
| INT outletCAPPriority | 1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.2 | INTEGER | read-write | Display or set the CAP Priority of outlet. Priority 0 means this outlet does not support this OID. |
| INT outletInitMode | 1.3.6.1.4.1.21317.1.3.2.2.2.1.19 | INTEGER | read-write | choose outlet init mode you want. |
| outlet | 1.3.6.1.4.1.21317.1.3.2.2.2.2 | |||
| outletValueTable | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1 | not-accessible | Display total outlet value table | |
| outletValueEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1 | not-accessible | Single outletValue entry containing outlet info. | |
| INT outletValueIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.1 | INTEGER | read-only | Index of outlet number |
| STR outletCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.2 | DisplayString | read-only | Outlet electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR outletVoltage | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.3 | DisplayString | read-only | Outlet voltage value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR outletPower | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.4 | DisplayString | read-only | Outlet power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR outletPowerDissipation | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.5 | DisplayString | read-only | Outlet power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| INT outletMaxCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.6 | INTEGER | read-only | Outlet Max Current value. unit: (A). If the device does not support this OID, we show value 0. |
| STR outletPowerFactor | 1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.7 | DisplayString | read-only | Outlet Power Factor value. If the device does not support this OID, it returns: not-support. |
| INT outlet1Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.2 | INTEGER | read-write | Display and control outlet 1 status. Can't set pending status. |
| INT outlet2Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.3 | INTEGER | read-write | Display and control outlet 2 status. Can't set pending status. |
| INT outlet3Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.4 | INTEGER | read-write | Display and control outlet 3 status. Can't set pending status. |
| INT outlet4Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.5 | INTEGER | read-write | Display and control outlet 4 status. Can't set pending status. |
| INT outlet5Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.6 | INTEGER | read-write | Display and control outlet 5 status. Can't set pending status. |
| INT outlet6Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.7 | INTEGER | read-write | Display and control outlet 6 status. Can't set pending status. |
| INT outlet7Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.8 | INTEGER | read-write | Display and control outlet 7 status. Can't set pending status. |
| INT outlet8Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.9 | INTEGER | read-write | Display and control outlet 8 status. Can't set pending status. |
| outletConfigTable | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10 | not-accessible | Outlet configuration table | |
| outletConfigEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1 | not-accessible | Outlet Config entry containing outlet info. | |
| INT outletConfigIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.1 | INTEGER | read-only | Index of outlet number |
| STR outletName | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.2 | DisplayString | read-write | Display or set the name of outlet. If the device does not support this OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL. |
| INT outletConfirmation | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.3 | INTEGER | read-write | Display or set the confirmation of outlet. |
| INT outletOnDelayTime | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.4 | INTEGER | read-write | Display or set the ON delay time of outlet. When this model does not support the OID, we show value -1. |
| INT outletOffDelayTime | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.5 | INTEGER | read-write | Display or set the OFF delay time of outlet. When this model does not support the OID, we show value -1. |
| INT outletShutdownMethod | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.6 | INTEGER | read-write | Display or set the shutdown mehtod of outlet. |
| STR outletMAC | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.7 | DisplayString | read-write | Display or set the MAC address of ShutdownMethod. If the device does not support this OID, we show n/a. string length: 12 |
| INT outletMinCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.8 | INTEGER | read-write | Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMaxCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.9 | INTEGER | read-write | Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMinVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.10 | INTEGER | read-write | Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMaxVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.11 | INTEGER | read-write | Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMinPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.12 | INTEGER | read-write | Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMaxPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.13 | INTEGER | read-write | Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outletMaxPDMT | 1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.14 | INTEGER | read-write | Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT outlet9Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.11 | INTEGER | read-write | Display and control outlet 9 status. Can't set pending status. |
| INT outlet10Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.12 | INTEGER | read-write | Display and control outlet 10 status. Can't set pending status. |
| INT outlet11Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.13 | INTEGER | read-write | Display and control outlet 11 status. Can't set pending status. |
| INT outlet12Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.14 | INTEGER | read-write | Display and control outlet 12 status. Can't set pending status. |
| INT outlet13Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.15 | INTEGER | read-write | Display and control outlet 13 status. Can't set pending status. |
| INT outlet14Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.16 | INTEGER | read-write | Display and control outlet 14 status. Can't set pending status. |
| INT outlet15Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.17 | INTEGER | read-write | Display and control outlet 15 status. Can't set pending status. |
| INT outlet16Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.18 | INTEGER | read-write | Display and control outlet 16 status. Can't set pending status. |
| INT outlet17Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.19 | INTEGER | read-write | Display and control outlet 17 status. Can't set pending status. |
| INT outlet18Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.20 | INTEGER | read-write | Display and control outlet 18 status. Can't set pending status. |
| INT outlet19Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.21 | INTEGER | read-write | Display and control outlet 19 status. Can't set pending status. |
| INT outlet20Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.22 | INTEGER | read-write | Display and control outlet 20 status. Can't set pending status. |
| INT outlet21Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.23 | INTEGER | read-write | Display and control outlet 21 status. Can't set pending status. |
| INT outlet22Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.24 | INTEGER | read-write | Display and control outlet 22 status. Can't set pending status. |
| INT outlet23Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.25 | INTEGER | read-write | Display and control outlet 23 status. Can't set pending status. |
| INT outlet24Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.26 | INTEGER | read-write | Display and control outlet 24 status. Can't set pending status. |
| INT outlet25Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.27 | INTEGER | read-write | Display and control outlet 25 status. Can't set pending status. |
| INT outlet26Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.28 | INTEGER | read-write | Display and control outlet 26 status. Can't set pending status. |
| INT outlet27Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.29 | INTEGER | read-write | Display and control outlet 27 status. Can't set pending status. |
| INT outlet28Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.30 | INTEGER | read-write | Display and control outlet 28 status. Can't set pending status. |
| INT outlet29Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.31 | INTEGER | read-write | Display and control outlet 29 status. Can't set pending status. |
| INT outlet30Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.32 | INTEGER | read-write | Display and control outlet 30 status. Can't set pending status. |
| INT outlet31Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.33 | INTEGER | read-write | Display and control outlet 31 status. Can't set pending status. |
| INT outlet32Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.34 | INTEGER | read-write | Display and control outlet 32 status. Can't set pending status. |
| INT outlet33Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.35 | INTEGER | read-write | Display and control outlet 33 status. Can't set pending status. |
| INT outlet34Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.36 | INTEGER | read-write | Display and control outlet 34 status. Can't set pending status. |
| INT outlet35Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.37 | INTEGER | read-write | Display and control outlet 35 status. Can't set pending status. |
| INT outlet36Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.38 | INTEGER | read-write | Display and control outlet 36 status. Can't set pending status. |
| INT outlet37Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.39 | INTEGER | read-write | Display and control outlet 37 status. Can't set pending status. |
| INT outlet38Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.40 | INTEGER | read-write | Display and control outlet 38 status. Can't set pending status. |
| INT outlet39Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.41 | INTEGER | read-write | Display and control outlet 39 status. Can't set pending status. |
| INT outlet40Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.42 | INTEGER | read-write | Display and control outlet 40 status. Can't set pending status. |
| INT outlet41Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.43 | INTEGER | read-write | Display and control outlet 41 status. Can't set pending status. |
| INT outlet42Status | 1.3.6.1.4.1.21317.1.3.2.2.2.2.44 | INTEGER | read-write | Display and control outlet 42 status. Can't set pending status. |
| outletSwitchableTable | 1.3.6.1.4.1.21317.1.3.2.2.2.2.70 | not-accessible | ||
| outletSwitchableEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1 | not-accessible | ||
| INT outletSwitchableIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.1 | INTEGER | read-only | Index of outlet number. |
| INT outletSwitchable | 1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.2 | INTEGER | read-only | |
| bank | 1.3.6.1.4.1.21317.1.3.2.2.2.3 | |||
| breakerStatusTable | 1.3.6.1.4.1.21317.1.3.2.2.2.3.1 | not-accessible | Display total bank value table | |
| breakerStatusEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1 | not-accessible | Single bankValue entry containing bank info. | |
| INT breakerStatusIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.1 | INTEGER | read-only | Index of breaker number. |
| INT breakerStatus | 1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.2 | INTEGER | read-only | Breaker status. |
| bankValueTable | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2 | not-accessible | Display total bank value table | |
| bankValueEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1 | not-accessible | Single bankValue entry containing bank info. | |
| INT bankValueIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.1 | INTEGER | read-only | Index of bank number |
| STR bankCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.2 | DisplayString | read-only | Bank electric current value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR bankVoltage | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.3 | DisplayString | read-only | Bank voltage value. We put this OID to write access type for user to set the reference voltage on EC1000 model. And the setting should be the numbers. You can set 0 to clear the setting. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR bankPower | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.4 | DisplayString | read-only | Bank power value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| STR bankPowerDissipation | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.5 | DisplayString | read-only | Bank power dissipation value. If this measurement value is not available, it returns: N/A. If the device does not support this OID, it returns: not-support. |
| INT bankMaxCurrent | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.6 | INTEGER | read-only | The Bank Max Current value. unit: (A) EC1000:0A~320A |
| INT bankAttachStatus | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.7 | INTEGER | read-only | The status of Energy sensor Bank attached status. |
| STR bankPowerFactor | 1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.8 | DisplayString | read-only | Bank Power Factor value. If the device does not support this OID, it returns: not-support. |
| bankConfigTable | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3 | not-accessible | Bank configuration table | |
| bankConfigEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1 | not-accessible | Bank Config entry containing Bank info. | |
| INT bankConfigIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.1 | INTEGER | read-only | Index of bank number |
| STR bankName | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.2 | DisplayString | read-write | Display or set the name of bank. When this model does not support the OID, we show n/a. string length: 0~15 NOTE: Input string as /empty to set this object to NULL. |
| INT bankMinCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3 | INTEGER | read-write | Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMaxCurMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.4 | INTEGER | read-write | Display or set the outlet maximum electric current measurment threshold. Example: range 0.0 ~16.0 represents 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMinVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5 | INTEGER | read-write | Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMaxVolMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.6 | INTEGER | read-write | Display or set the outlet maximum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMinPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.7 | INTEGER | read-write | Display or set the outlet minimum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMaxPMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.8 | INTEGER | read-write | Display or set the outlet maximum power measurment threshold. Example: range 0.0 ~ 9999.9 represents 0~99999 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| INT bankMaxPDMT | 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.9 | INTEGER | read-write | Display or set the outlet maximum power dissipation measurment threshold. Example: range 0.0 ~ 99999.0 represents 0~999990 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000. |
| bankControlTable | 1.3.6.1.4.1.21317.1.3.2.2.2.3.4 | not-accessible | Bank Control table | |
| bankControlEntry | 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1 | not-accessible | Bank control entry. | |
| INT bankControlIndex | 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.1 | INTEGER | read-only | Index of bank number |
| INT bankControlStatus | 1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.2 | INTEGER | read-write | This function is used for outlet control of bank. Set off(1) to turn off for outlet control of bank. Set on(2) to turn on for all outlet control of bank. Set reboot(3) to turn on for outlet control of bank. Get this object always return nostatus(3), because there is no bank status. |
| deviceManagement | 1.3.6.1.4.1.21317.1.3.2.2.3 | |||
| config | 1.3.6.1.4.1.21317.1.3.2.2.3.4 | |||
| STR deviceMAC | 1.3.6.1.4.1.21317.1.3.2.2.3.4.1 | DisplayString | read-only | Display device MAC address. |
| IP deviceIPv4 | 1.3.6.1.4.1.21317.1.3.2.2.3.4.2 | IpAddress | read-only | Display device IP address. |
| STR deviceFWversion | 1.3.6.1.4.1.21317.1.3.2.2.3.4.3 | DisplayString | read-only | Display device FW version. |
| dashBoard | 1.3.6.1.4.1.21317.1.3.2.2.3.4.4 | |||
| INT dashboardRow | 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.1 | INTEGER | read-write | Display or set device's dashboard row number. |
| INT dashboardColumn | 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.2 | INTEGER | read-write | Display or set device's dashboard column number. |
| STR dashboardRackName | 1.3.6.1.4.1.21317.1.3.2.2.3.4.4.3 | DisplayString | read-write | Display or set device's dashboard rack name. string length: 1~32 NOTE: Input string as /empty to set this object to NULL. |
| servicePorts | 1.3.6.1.4.1.21317.1.3.2.2.3.4.5 | |||
| INT httpPort | 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.1 | INTEGER | read-write | Display or set the HTTP port of PE device. |
| INT httpsPort | 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.2 | INTEGER | read-write | Display or set the HTTPs port of PE device. |
| INT httpsOnlyEnable | 1.3.6.1.4.1.21317.1.3.2.2.3.4.5.3 | INTEGER | read-write | Enable to use Webpage HTTPs only or disable to use Webpage HTTP/HTTPs |
| ipv4config | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6 | |||
| INT staticIPEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.1 | INTEGER | read-write | Display or set IPv4 address automatically or not |
| IP fixedIPv4 | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.2 | IpAddress | read-write | Display or set fixed IPv4 address |
| IP subnetMask | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.3 | IpAddress | read-write | Display or set subnet mask address |
| IP gateway | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.4 | IpAddress | read-write | Display or set gateway address |
| INT staticDNSEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.5 | INTEGER | read-write | Display or set DNS address automatically or not |
| IP dnsPreferIPv4 | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.6 | IpAddress | read-write | Display or set prefer DNS address |
| IP dnsAlternateIPv4 | 1.3.6.1.4.1.21317.1.3.2.2.3.4.6.7 | IpAddress | read-write | Display or set alternate DNS address |
| eventNotification | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7 | |||
| devicesnmp | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1 | |||
| INT trapEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.1 | INTEGER | read-write | Indicates if this trap entry is enabled or not. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. |
| INT trapVersion | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.2 | INTEGER | read-write | Choose SNMP Trap version to send trap. You should set the username/auth-password/priv-password first, when choosing snmpv3. You should set the community string first, when choosing snmpv1/v2c. |
| snmpTrapTable | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3 | not-accessible | PE SNMP agent trap setup table. If users want to use trap, they must set enable trap, ip and community first. | |
| snmpTrapEntry | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1 | not-accessible | Single trap entry containing trap receiver info. | |
| INT trapReceiverNumber | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.1 | INTEGER | read-only | Index of trap receiver |
| IP trapReceiverIPAddress | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.2 | IpAddress | read-write | Trap receiver IP address |
| INT trapPort | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.3 | INTEGER | read-write | NMS trap port to be used by agent to send trap |
| STR trapCommunity | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.4 | DisplayString | read-write | If use SNMPv1/v2c to receive trap should set this Community string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. |
| STR trapUsername | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.5 | DisplayString | read-write | If use SNMPv3 to receive trap should set this string. NOTE: Input string as /empty to set this object to NULL. MAX string length: 20 |
| STR trapAuthpassword | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.6 | DisplayString | read-write | If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. |
| STR trapPrivpassword | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.7 | DisplayString | read-write | If use SNMPv3 to receive trap should set this string. MAX string length: 20 NOTE: Input string as /empty to set this object to NULL. |
| syslog | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2 | |||
| INT sysLogServerEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.1 | INTEGER | read-write | Display or set syslog server address automatically or not |
| IP sysLogServerIPv4 | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.2 | IpAddress | read-write | Display or set syslog server address |
| INT sysLogServerPort | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.2.3 | INTEGER | read-write | Display or set syslog server port |
| smtp | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3 | |||
| INT smtpServerEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.1 | INTEGER | read-write | Display or set SMTP server enable status. |
| STR smtpServerName | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.2 | DisplayString | read-write | Display or set a SMTP server name. NOTE: Input string as /empty to set this object to NULL. |
| INT smtpAuthEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.3 | INTEGER | read-write | Display or set authentication of SMTP server. |
| STR smtpAccountName | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.4 | DisplayString | read-write | Display or set a user's name of SMTP server. NOTE: Input string as /empty to set this object to NULL. |
| STR smtpAccountPwd | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.5 | DisplayString | read-write | Display or set a user's password of SMTP server. NOTE: Input string as /empty to set this object to NULL. |
| STR smtpMailFrom | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.6 | DisplayString | read-write | Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL. |
| STR smtpMailTo | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.3.7 | DisplayString | read-write | Display or set a mail of SMTP server. NOTE: Input string as /empty to set this object to NULL. |
| configurationNotification | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9 | |||
| INT configurationNotifyEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.1 | INTEGER | read-write | |
| NTF configurationNotifyTrapMSG | 1.3.6.1.4.1.21317.1.3.2.2.3.4.7.9.2 | |||
| dateTime | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8 | |||
| timeZone | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1 | |||
| INT timeZoneSetting | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.1 | INTEGER | read-write | Display or set the time zone of PE device. (0) [GMT-12:00] Eniwetok Kwajalein (1) [GMT-11:00] Midway Island Samoa (2) [GMT-10:00] Hawaii (3) [GMT-09:00] Alaska (4) [GMT-08:00] Pacific Time (US & Canada); Tijuana (5) [GMT-07:00] Mountain Time (US & Canada) (6) [GMT-07:00] Arizona (7) [GMT-06:00] Central Time (US & Canada) (8) [GMT-06:00] Mexico City (9) [GMT-06:00] Saskatchewan (10)[GMT-06:00] Central America (11)[GMT-05:00] Eastern Time (US & Canada) (12)[GMT-05:00] Indiana (East) (13)[GMT-05:00] Bogota Lima Quito (14)[GMT-04:00] Atlantic Time (Canada) (15)[GMT-04:00] Caracas La Paz (16)[GMT-04:00] Santiago (17)[GMT-03:30] Newfoundland (18)[GMT-03:00] Buenos Aires Georgetown (19)[GMT-03:00] Brasilia (20)[GMT-03:00] Greenland (21)[GMT-02:00] Mid-Atlantic (22)[GMT-01:00] Azores (23)[GMT-01:00] Cape Verde Is (24)[GMT] Casablanca Monrovia (25)[GMT] Greenwich Mean Time: Dublin Edinburgh Lisbon London (26)[GMT+01:00] Amsterdam Copenhagen Madrid Paris Vilnius (27)[GMT+01:00] West Central Africa (28)[GMT+01:00] Belgrade Sarajevo Skopje Sofija Zagreb (29)[GMT+01:00] Bratislava Budapest Ljubljana Prague Warsaw (30)[GMT+01:00] Brussels Berlin Bern Rome Stockholm Vienna (31)[GMT+02:00] Cairo (32)[GMT+02:00] Harare Pretoria (33)[GMT+02:00] Jerusalem (34)[GMT+02:00] Bucharest (35)[GMT+02:00] Helsinki Riga Tallinn (36)[GMT+02:00] Athens Istanbul Minsk (37)[GMT+03:00] Kuwait Riyadh (38)[GMT+03:00] Nairobi (39)[GMT+03:00] Baghdad (40)[GMT+03:00] Moscow St. Petersburg Volgograd (41)[GMT+03:30] Tehran (42)[GMT+04:00] Abu Dhabi Muscat (43)[GMT+04:00] Baku Tbilisi Yerevan (44)[GMT+04:30] Kabul (45)[GMT+05:00] Islamabad Karachi Tashkent (46)[GMT+05:00] Ekaterinburg (47)[GMT+05:30] Calcutta Chennai Mumbai New Delhi (48)[GMT+05:45] Kathmandu (49)[GMT+06:00] Astana Dhaka (50)[GMT+06:00] Sri Jayawardenepura (51)[GMT+06:00] Almaty Novosibirsk (52)[GMT+06:30] Rangoon (53)[GMT+07:00] Bangkok Hanoi Jakarta (54)[GMT+07:00] Krasnoyarsk (55)[GMT+08:00] Beijing Chongqing Hong Kong Urumqi (56)[GMT+08:00] Perth (57)[GMT+08:00] Kuala Lumpur Singapore (58)[GMT+08:00] Taipei (59)[GMT+08:00] Irkutsk Ulaan Bataar (60)[GMT+09:00] Osaka Sapporo Tokyo (61)[GMT+09:00] Seoul (62)[GMT+09:00] Yakutsk (63)[GMT+09:30] Darwin (64)[GMT+09:30] Adelaide (65)[GMT+10:00] Canberra Melbourne Sydney (66)[GMT+10:00] Brisbane (67)[GMT+10:00] Guam Port Moresby (68)[GMT+10:00] Hobart (69)[GMT+10:00] Vladivostok (70)[GMT+11:00] Magadan Solomon Is New Caledonia (71)[GMT+12:00] Fiji Kamchatka Marshall Is. (72)[GMT+12:00] Auckland Wellington (73)[GMT+13:00] Nuku'alofa |
| INT dstEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.1.2 | INTEGER | read-write | Display or set daylight savings time . |
| manualInput | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2 | |||
| STR dateSetting | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.1 | DisplayString | read-write | Display or set date in a manual way.(This is Greenwich Mean Time, GMT) string length: 10 This value format must match the following form: YYYY-MM-DD ex. 2011-01-01 Note: range of year: 2000-2099 range of month: 01-12 range of day: 01-31 |
| STR timeSetting | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.2.2 | DisplayString | read-write | Display or set time in a manual way.(This is Greenwich Mean Time, GMT) string length: 8 This value format must match the following form: HH:MM:SS ex. 02:02:02 Note: range of hour: 00-24 range of minute: 00-60 range of second: 00-60 |
| networkTime | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3 | |||
| INT autoAdjustEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.1 | INTEGER | read-write | Display or set date time useing auto adjustment way. |
| INT preferNTP | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.2 | INTEGER | read-write | Display or set prefer NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79) |
| INT preferServerIPenable | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.3 | INTEGER | read-write | Enable or disable prefer custom server IP. |
| IP preferNTPIp | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.4 | IpAddress | read-write | Display or set prefer NTP server IP. |
| INT alternateNtpEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.5 | INTEGER | read-write | Display or set date time using alternate NTP server. |
| INT alternateNtp | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.6 | INTEGER | read-write | Display or set alternative NTP server. AU | ntp1.cs.mu.OZ.AU(0), AU | ntp0.cs.mu.OZ.AU(1), BE | ntp2.oma.be(2), BE | ntp1.oma.be(3), BR | ntps1.pads.ufrj.br(4), CH | swisstime.ethz.ch(5), CL | ntp.shoa.cl(6), CZ | ntp.nic.cz(7), DE | ntp.stairweb.de(8), DE | ntps1-0.cs.tu-berlin.de(9), DE | ptbtime1.ptb.de(10), DE | ntp1.fau.de(11), DE | ptbtime2.ptb.de(12), DE | time1.one4vision.de(13), DE | rustime01.rus.uni-stuttgart.de(14), DE | ntp.probe-networks.de(15), DE | ntp2.fau.de(16), ES | hora.roa.es(17), HK | stdtime.gov.hk(18), IE | ntp-galway.hea.net(19), IT | ntp1.inrim.it(20), IT | ntp2.inrim.it(21), JP | clock.tl.fukuoka-u.ac.jp(22), JP | ntp.nict.jp(23), JP | clock.nc.fukuoka-u.ac.jp(24), KR | ntp.xbsd.kr(25), MX | cronos.cenam.mx(26), NL | ntp0.nl.uu.net(27), NL | ntp1.nl.uu.net(28), NL | ntp.remco.org(29), NL | ntp0.nl.net(30), PL | vega.cbk.poznan.pl(31), PL | ntp.ntp-servers.com(32), RO | ntp3.usv.ro(33), RO | ntp2.usv.ro(34), RU | ntp1.vniiftri.ru; ntp1.imvp.ru(35), RU | ntp2.vniiftri.ru; ntp2.imvp.ru(36), SE | ntp1.mmo.netnod.se(37), SE | ntp1.sth.netnod.se(38), SE | ntp2.mmo.netnod.se(39), SE | ntp2.sth.netnod.se(40), SE | time2.stupi.se(41), SE | ntp1.sp.se(42), SE | timehost.lysator.liu.se(43), SI | ntp.mostovna.com(44), US CA | timekeeper.isi.edu(45), US CA | clock.sjc.he.net(46), US CA | nist1.symmetricom.com(47), US CA | clock.via.net(48), US CA | nist1.aol-ca.truetime.com(49), US CA | clock.isc.org(50), US CA | clepsydra.dec.com(51), US CA | gps.layer42.net(52), US CA | time.no-such-agency.net(53), US CA | nist1-sj.WiTime.net(54), US CA | clock.fmt.he.net(55), US CO | time-b.timefreq.bldrdoc.gov(56), US CO | time-a.timefreq.bldrdoc.gov(57), US CO | utcnist.colorado.edu(58), US CO | time-c.timefreq.bldrdoc.gov(59), US DE | rackety.udel.edu(60), US DE | mizbeaver.udel.edu(61), US GA | nist1.columbiacountyga.gov(62), US IL | ntp.your.org(63), US MA | bonehed.lcs.mit.edu(64), US MA | time.keneli.org(65), US MA | ntp0.broad.mit.edu(66), US MD | time-a.nist.gov(67), US MD | time-b.nist.gov(68), US MI | nist.netservicesgroup.com(69), US NY | nist1-ny.WiTime.net(70), US NY | clock.nyc.he.net(71), US UT | time.xmission.com(72), US VA | nist1-dc.WiTime.net(73), US VA | nist1.aol-va.truetime.com(74), US WA | time-nw.nist.gov(75), FR | utp.univ-lyon1.fr(76), FR | ntp-sop.inria.fr(77), FR | ntp.tuxfamily.net(78), UK | bear.zoo.bt.co.uk(79) |
| INT alternateServerIPenable | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.7 | INTEGER | read-write | Enable or disable alternate custom server IP. |
| IP alternateNtpIp | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.8 | IpAddress | read-write | Display or set alternative NTP server IP. |
| INT adjustTimeEveryDays | 1.3.6.1.4.1.21317.1.3.2.2.3.4.8.3.9 | INTEGER | read-write | Display or set frequency of adjustment in days. |
| devicesecurity | 1.3.6.1.4.1.21317.1.3.2.2.3.5 | |||
| loginFailures | 1.3.6.1.4.1.21317.1.3.2.2.3.5.1 | |||
| INT loginAllowTimes | 1.3.6.1.4.1.21317.1.3.2.2.3.5.1.1 | INTEGER | read-write | Display or set time of login faliure. |
| INT loginTimeOut | 1.3.6.1.4.1.21317.1.3.2.2.3.5.1.2 | INTEGER | read-write | Display or set login time out. |
| workingMode | 1.3.6.1.4.1.21317.1.3.2.2.3.5.2 | |||
| INT icmpEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.2.1 | INTEGER | read-write | Display or set status of ICMP. |
| accountPolicy | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3 | |||
| INT minUserNameLen | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.1 | INTEGER | read-write | Display or set minimum length of user name. |
| INT minUserPwdLen | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.2 | INTEGER | read-write | Display or set minimum length of user password. |
| INT upperCaseEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.3 | INTEGER | read-write | Display or set one upper case rule in user password. |
| INT lowerCaseEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.4 | INTEGER | read-write | Display or set one lower case rule in user password. |
| INT numberEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.5 | INTEGER | read-write | Display or set one number rule in user password. |
| INT disableDuplicateLogin | 1.3.6.1.4.1.21317.1.3.2.2.3.5.3.6 | INTEGER | read-write | Display or set status of disabled duplicate login rule. |
| loginRestriction | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4 | |||
| STR loginString | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.1 | DisplayString | read-write | Display or set a login string. string length: 0~32 NOTE: Input string as /empty to set this object to NULL. |
| ipFilter | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2 | |||
| INT ipFilterEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.1 | INTEGER | read-write | Display or set status of ip filter. |
| INT ipFilterRule | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.2 | INTEGER | read-write | Display or set status of ip filter rule. |
| ipFilterTable | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3 | not-accessible | A list of restricted ip. | |
| ipFilterEntry | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1 | not-accessible | Status and parameter values for a PE's restricted IP. | |
| INT ipFilterIndex | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.1 | INTEGER | read-only | The value of index for the ip filter. |
| IP ipFilterFrom | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.2 | IpAddress | read-write | A set of restricted ip. ex. 192.168.0.1 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0 |
| IP ipFilterTo | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.3 | IpAddress | read-write | A set of restricted ip. ex. 192.168.0.255 Note: Users must follow in order to set the ip address. Note: To clear the settings to set the ip 0.0.0.0 |
| macFilter | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3 | |||
| INT macFilterEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.1 | INTEGER | read-write | Display or set status of mac filter. |
| INT macFilterRule | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.2 | INTEGER | read-write | Display or set status of mac filter rule. |
| macFilterTable | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3 | not-accessible | A list of restricted mac. | |
| macFilterEntry | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1 | not-accessible | Status and parameter values for a PE's restricted MAC. | |
| INT macFilterIndex | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.1 | INTEGER | read-only | The value of index for the mac filter. |
| STR macFilterSet | 1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.2 | DisplayString | read-write | A set of restricted mac. string length: 12 ex. 004854655511 Note: Users must follow in order to set the MAC address. Note: To clear the settings to set the MAC 000000000000 |
| authentication | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5 | |||
| radius | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1 | |||
| INT radiusEnabled | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.1 | INTEGER | read-write | Display or set status of RADIUS server. |
| IP preferRadiusIp | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.2 | IpAddress | read-write | Display or set prefer RADIUS server IP. |
| INT preferRadiusPort | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.3 | INTEGER | read-write | Display or set prefer RADIUS server port. |
| IP alternateRadiusIp | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.4 | IpAddress | read-write | Display or set alternative RADIUS server IP. |
| INT alternateRadiusPort | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.5 | INTEGER | read-write | Display or set alternative RADIUS server port. |
| INT radiusTimeOut | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.6 | INTEGER | read-write | Display or set time out of authentication using RADIUS server. The unit is sec. |
| INT radiusRetry | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.7 | INTEGER | read-write | Display or set retry times of authentication using RADIUS server. |
| STR radiusSecret | 1.3.6.1.4.1.21317.1.3.2.2.3.5.5.1.8 | DisplayString | read-write | Display or set shared secret of RADIUS server. string length: 6~15 At least 6 characters. NOTE: Input string as /empty to set this object to NULL. |
| NTF customTrapMSG | 1.3.6.1.4.1.21317.1.3.2.2.5 | Display custom trap message. | ||
| INT rebootDevice | 1.3.6.1.4.1.21317.1.3.2.2.6 | INTEGER | read-write | Reboot PE Device |
RFC description
ATEN International vendor-private MIB for PE series Power over IP management, configuration, sensors, and CAP features.
Start monitoring ATEN PE-series intelligent PDUs with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.