All MIBs › ATEN-PE-CFG-STR › bankMinVolMT
bankMinVolMT
Module: ATEN-PE-CFG-STR
OID (symbolic): ATEN-PE-CFG-STR::bankMinVolMT
OID (numeric): 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Display or set the outlet minimum voltage measurment threshold. Example: range 90.0 ~260.0 represents 900~2600 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.
What is bankMinVolMT?
This read-write integer sets the minimum voltage threshold (in tenths of volts, 90-260V range) for bank monitoring. When voltage drops below this value, an alert indicates supply failure. Setting it to 1800 means an alert fires if bank voltage drops below 180.0 volts.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5 snmpwalk -v2c -c public <target> ATEN-PE-CFG-STR::bankMinVolMT
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5.1 snmpget -v2c -c public <target> ATEN-PE-CFG-STR::bankMinVolMT.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5.1 i <value>
Start monitoring ATEN PE-series intelligent PDUs with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ATEN-PE-CFG-STR::bankMinVolMT OID value, configure state conditions and alerts, and monitor any ATEN PE-series intelligent PDUs from a single console.
OID Breakdown
Upper-level ancestors (15 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.21317 | aten | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1 | atenProducts | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3 | overip | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2 | poweroverip | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2.2 | pe | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2.2.2 | control | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2.2.2.3 | bank | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2.2.2.3.3 | bankConfigTable | ATEN-PE-CFG |
| 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1 | bankConfigEntry | ATEN-PE-CFG |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5 | bankMinVolMT | ATEN-PE-CFG-STR |